Weil-McLain · Heat pump
PP Tw_out - Tw_in reading not normal
What the control is telling you
The inlet and outlet water sensors give readings that do not make sense together.
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
Likely causes
- Tw_in or Tw_out sensor reading wrong
- Sensor in the wrong place
- Sensor connector loose
- Sensor failed
- Four-way valve stuck
- Four-way valve failed
Test and repair steps
- Turn off power at the disconnect before opening the unit or touching any wiring.
- Measure both sensor resistances.
- Check that both sensors are in the right spots.
- Reconnect any loose Tw_in / Tw_out connector.
- Replace a bad sensor.
- Restart the unit so the four-way valve gets a chance to shift.
- If the four-way valve stays stuck, replace it. R32 (A2L) refrigerant: only a tech qualified for flammable refrigerant should open the refrigerant circuit.
Models that show this code
3 models in Weil-McLain ECO HP
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.3 Error codes, p.56. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.