Weil-McLain · Heat pump

bH PED board fault

High severity Weil-McLain ECO HP

What the control is telling you

The PED board is a small board on the inverter module (PCB A). It watches the high pressure switch and stops the compressor right away if the switch opens. This code means that board failed.

Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)

Likely causes

  • PED safety board failed
  • IPM module on the inverter board failed

Test and repair steps

  1. Turn off power at the disconnect before opening the unit or touching any wiring.
  2. Leave the power off for 5 minutes, then power up and see if the code clears.
  3. Still there replace the PED safety board and power up again.
  4. Still there replace the IPM (inverter) module board.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • HE Communication fault with Ta / room thermostat transfer board
  • HF Outdoor unit EEPROM fault
  • HH H6 fan fault 10 times in 120 minutes
  • HP Low pressure in cooling, 3 times in an hour
  • Hb PP three times and Tw_out under 44.6 F
  • PP Tw_out - Tw_in reading not normal
  • Pb Anti-freeze mode
  • Pd Outdoor coil (T3) temperature too high

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.34. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.