Weil-McLain · Heat pump

P4 Compressor discharge temperature too high

High severity Weil-McLain ECO HP

What the control is telling you

The discharge line got too hot and the compressor was stopped.

Applies to: ECO HP 41/48/55 MBH outdoor unit (ODU)

Likely causes

  • Same causes as P1 (high pressure)
  • TW_out water outlet sensor loose

Test and repair steps

  1. Do the P1 checks.
  2. Turn off power at the disconnect before opening the unit or touching any wiring.
  3. Reconnect the TW_out sensor.

Models that show this code

3 models in Weil-McLain ECO HP

ECO HP 41ECO HP 48ECO HP 55

Other codes on the same units

  • L9 Compressor speed off target by more than 15 Hz
  • P0 Low pressure protection
  • P1 High pressure protection
  • P3 AC current protection
  • P5 Water temperature difference too high (Tw_out - Tw_in)
  • P6 Inverter module protection
  • CL Water pump communication wire fault
  • EA Compressor discharge temperature sensor (Tp) fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump ODU Product Manual 550-100-587/0824, sec. 11.8 Error codes, p.37. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.