Rheem furnace error codes

73 codes (39 faults, 34 normal display and menu codes), plus 9 settings tables.

CodeMeaningSeverity / type
0Standby - no call, no faultNormal status
1 blinkSoft lockout (failed ignition)High
2 WK HIST / LIFE HIST menusFurnace user menus - run-time historiesMenu / mode display
2 blinksPressure switch circuit openMedium
3 blinksLimit circuit openHigh
4 blinksPressure switch circuit closed (stuck closed)Medium
5 blinksTwinning fault (optional)Low
6 blinksLine and neutral reversedMedium
10One-hour lockoutHigh
11Failed ignitionHigh
12Low flame senseMedium
13Flame lostHigh
14Unexpected flameCritical
20Twinning faultMedium
22Main limit openHigh
23HALC limit open (HALC LIMIT OPEN)High
26Line and neutral reversedHigh
30Open fuseCritical
33Rollout switch (MRLC) openCritical
44Low pressure switch closed (stuck)High
45Low pressure switch open - inducer high speedHigh
46Low pressure switch open - inducer low speedHigh
55Pressure switch stuck closedHigh
57Pressure switch stuck openHigh
58Water sense circuit openMedium
59Water sensed / blocked drainHigh
60Blower fault - running (BLWR FLT-RUN)Medium
66Blower overspeed (BLOWER OVRSPEED)Medium
68No blower communication (NO BLWR COMM)Critical
82Supply air sensor fault (SA SENSOR FLT)Low
84Outdoor air sensor faultLow
d1No shared data (NO SHARED DATA)Critical
d4No valid model data on memory cardLow
d5Card/hardware conflict (CARD-HRD CNFLCT)Medium
d6Blower HP conflict (BLWR HP CNFLCT)High
d7Blower manufacturer conflict (BLWR MFG CNFLCT)High
d8Old shared data (OLD SHARED DATA)Medium
AFAirflow readout (pushbutton status menu)Menu / mode display
Blank thermostat text areaThermostat text area blank - system found OKNormal status
Blinking decimal pointAirflow readout - blinks of right decimal pointNormal status
CCooling or heat-pump heat (compressor call)Normal status
CFM LED blinksCFM LED blink count = target airflowMenu / mode display
FContinuous fan onNormal status
FAULT HISTORY menuFurnace user menu - FAULT HISTORYMenu / mode display
FIXED FIRE RATEForced low or high fire test (SETUP menu)Menu / mode display
FLFault history (pushbutton status menu)Menu / mode display
FURNACE FOUNDThermostat start-up message - equipment foundNormal status
Fault recallPower-up replay of the last three faultsMenu / mode display
Fault recall - last 5Power-up replay of the last five faultsMenu / mode display
Flame LED offNo flame sensed (troubleshooting aid)Medium
Flame LED slow blinkAmber flame LED - marginal flame senseMedium
Flame LED steady onAmber flame LED steady - normal flame sensedNormal status
FrFire rate readout (pushbutton status menu)Menu / mode display
HGas heat onNormal status
HPHeat-pump heat running (dual fuel)Normal status
Learn buttonLearn button - RX LED rapid blink testMenu / mode display
Power LED onPower LED on - control has 24 VACNormal status
RX LED blinkingGreen RX LED - network traffic presentNormal status
SEARCHINGThermostat start-up message - searchingNormal status
SETUP menuFurnace user menu - SETUPMenu / mode display
STAT LED double blinkRed STAT LED - two slow blinks at power-upNormal status
STATUS 1 menuFurnace user menu - STATUS 1Menu / mode display
STATUS 2 menuFurnace user menu - STATUS 2Menu / mode display
Status LED steady onStatus LED steady - normal (RGRM/RGTM)Normal status
Top and bottom bars (right digit)Fault history cleared confirmationNormal status
UIUnit input readout (pushbutton status menu)Menu / mode display
UNIT INFO menuFurnace user menu - UNIT INFOMenu / mode display
cd / CdDehumidification coolingNormal status
dFDefrost in progress (dual fuel)Normal status
h (lowercase)Low-fire gas heat onNormal status
h flashingCalibrating (CALIBRATE-NO V)Low
rLockout indicatorHigh
trTemperature rise readout (pushbutton status menu)Menu / mode display

Settings and specs

Filter sizes

Filters · Rheem RGRM/RGTM 90 Plus

Cabinet widthInput (MBTUH)BottomSideQty
17-1/2 in. upflow45, 60, 75A15-3/4 x 2515-3/4 x 251
21 in. upflow75B, 90, 10519-1/4 x 2515-3/4 x 251
24-1/2 in. upflow12022-3/4 x 2515-3/4 x 251
17-1/2 in. downflow/horiz.60, 75A12 x 20-2
21 in. downflow/horiz.75B, 90, 10512 x 20-2
24-1/2 in. downflow/horiz.12014 x 20-2
  • Use both side returns for 1800 CFM or more.
  • Some side filters must be trimmed to fit (21 in. cabinets: remove a 3.5 in. strip; 24.5 in.: a 7 in. strip).
  • Do not double-filter the return.

Source: Rheem RGRM/RGTM Installation Instructions 92-24161-84-01, Table 14 p.50; Filters p.50

Filter sizes (Table 12)

Filters · Rheem 90RJ/90TJ 90 Plus

ConfigurationCabinet widthInput (MBTU/h)Bottom filterSide filterQty
Upflow17-1/2 in.45, 60, 7515-3/4 x 25 in.15-3/4 x 25 in.1
Upflow21 in.90, 10519-1/4 x 25 in.15-3/4 x 25 in.1
Upflow24-1/2 in.12022-3/4 x 25 in.15-3/4 x 25 in.1
Downflow17-1/2 in.45, 60, 7512 x 20 in.-2
Downflow21 in.90, 10512 x 20 in.-2
Downflow24-1/2 in.12014 x 20 in.-2
  • Filters are not factory-installed; they must be field supplied.
  • Side filter on 21 in. units: cut 3.5 in. off the filter and frame; on 24.5 in. units cut 7 in.

Source: Rheem 90RJ/90TJ installation instructions 92-24161-32-08, Table 12 Filter Sizes, PDF p.51

Minimum clearance to combustibles

Clearances · Rheem 90RJ/90TJ 90 Plus

ConfigurationLeft sideRight sideBackTopFrontVent
Upflow0 in.0 in.0 in.1 in.2 in. (24 in. service)0 in.
Downflow0 in.0 in.0 in.1 in.2 in. (24 in. service)0 in.
Horizontal0 in.0 in.0 in.1 in.2 in. (24 in. service)0 in.
  • Same values for every cabinet size.
  • 24 in. service clearance recommended in front of all furnaces.
  • Not approved for installation on its back (doors facing up).

Source: Rheem 90RJ/90TJ installation instructions 92-24161-32-08, Figures 5-7 Clearance to Combustibles, PDF p.9-11

Filter sizes (Table 9)

Filters · Rheem (-)GRC/(-)GTC 90 Plus

ConfigurationCabinet widthInput (MBTU/h)Bottom filterSide filterQty
Upflow17-1/2 in.45, 60, 7515-3/4 x 25 in.15-3/4 x 25 in.1
Upflow21 in.90, 10519-1/4 x 25 in.15-3/4 x 25 in.1
Downflow17-1/2 in.45, 60, 7512 x 20 in.-2
Downflow21 in.9012 x 20 in.-2
Downflow24-1/2 in.10514 x 20 in.-2
  • Side filter on 21 in. units: cut 3.5 in. off the filter and frame; on 24.5 in. units cut 7 in.
  • Do not run the system for long periods without filters.

Source: Rheem (-)GRC/(-)GTC installation instructions 92-24161-88-00, Table 9 Filter Sizes, PDF p.54

Minimum clearance to combustibles

Clearances · Rheem (-)GRC/(-)GTC 90 Plus

ConfigurationLeft sideRight sideBackTopFrontVent
Upflow0 in.0 in.0 in.1 in.2 in. (24 in. service)0 in.
Downflow0 in.0 in.0 in.1 in.2 in. (24 in. service)0 in.
Horizontal0 in.0 in.0 in.1 in.2 in. (24 in. service)0 in.
  • Same values for every cabinet size.
  • 24 in. service clearance recommended in front of all furnaces.
  • Not approved for installation on its back (doors facing up).

Source: Rheem (-)GRC/(-)GTC installation instructions 92-24161-88-00, Figures 6-8 Clearance to Combustibles, PDF p.13-15

Clearance to combustibles (all models)

Clearances · R95P

LocationMinimum clearance
Left side0 in.
Right side0 in.
Back0 in.
Top1 in.
Front2 in.
Vent0 in.
Service (front)24 in. recommended
  • Same values for R95PA040 through 115.
  • Column order read from a rotated drawing header - confirm on the furnace clearance label.
  • Downflow non-zero-clearance installs need the right-side vent clearance in Figure 4, otherwise use kit RXGY-ZK.

Source: Rheem (-)95P Series single-stage condensing furnace Installation Instructions 92-24161-111-03, Figure 6 Unit Dimensions (Clearance to Combustibles), p.14-15

Filter sizes as shipped, upflow (Table 19)

Filters · RGPE/RGLE

Cabinet widthInputBottom filterSide filterQuantity
17-1/2 in.50, 75 (000 Btu/h)15-3/4 x 25 in.15-3/4 x 25 in.1
21 in.75, 100 (000 Btu/h)19-1/4 x 25 in.15-3/4 x 25 in.1
24-1/2 in.125 (000 Btu/h)22-3/4 x 25 in.15-3/4 x 25 in.1
  • Use one filter location only - do not double-filter or filter the supply side.
  • 21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.
  • Some filters must be ordered or cut to fit.
  • High-efficiency filters add resistance - check airflow if you change filter type.
  • Side return: use both sides at 1800 CFM or more.

Source: Rheem RGPE/RGLE 2-stage 80+ communicating furnace Installation Instructions 92-24161-77-02, Table 19 Filter Sizes, p.60 (printed)

Reduced clearance to combustibles, upflow/horizontal (Fig. 4)

Clearances · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)

Model sizeCabinet width (A)Left sideRight sideBackTopFrontVent
050 (5)14 in.0 in.4 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
075 (7)17-1/2 in.0 in.3 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
100 (10)21 in.0 in.00 in.1 in.3 in.6 in. (note 3)
125 (12)24-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)
150 (15)24-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)
  • Note 2: right side may be 0 in. with type B vent.
  • Note 3: vent clearance may be 1 in. with type B vent.
  • Values are inches from the furnace casing to combustible material.

Source: Rheem (-)802P/(-)(-)80MDP installation instructions 92-24161-146-02, Figure 4 Upflow/Horizontal Dimensions - Clearance to Combustible Material, p.10 (manual page; PDF p.13)

Reduced clearance to combustibles (Fig. 3 and 4)

Clearances · RGPE/RGLE

Model sizeCabinet width (A)Left sideRight sideBackTopFrontVent
RGPE upflow/horizontal 0517-1/2 in.0 in.3 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
RGPE upflow/horizontal 07(A)17-1/2 in.0 in.3 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
RGPE upflow/horizontal 07(B), 1021 in.0 in.00 in.1 in.3 in.6 in. (note 3)
RGPE upflow/horizontal 1224-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)
RGLE downflow 07(A)17-1/2 in.0 in.3 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
RGLE downflow 07(B), 1021 in.0 in.00 in.1 in.3 in.6 in. (note 3)
RGLE downflow 1224-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)
  • Note 2: right side may be 0 in. with type B vent.
  • Note 3: vent clearance may be 1 in. with type B vent.
  • Downflow on a combustible floor needs the combustible floor base unless the furnace sits on a coil box.
  • Do not install the upflow/horizontal furnace on its back with the access doors facing up.
  • Values are inches from the casing to combustible material.

Source: Rheem RGPE/RGLE 2-stage 80+ communicating furnace Installation Instructions 92-24161-77-02, Figure 3 Upflow/Horizontal Dimensions and Figure 4 Downflow Dimensions - Clearance to Combustible Material, p.8-9 (printed; PDF p.12-13)

Models covered

(-)96V060(-)96V070(-)96V085(-)96V100(-)96VA0602317MSA(-)96VA0702317MSA(-)96VA0852521MSA(-)96VA1002521MSA90RJ0490RJ0690RJ0790RJ0990RJ1090RJ1290TJ0490TJ0690TJ0790TJ0990TJ1090TJ1296MDV06096MDV07096MDV08596MDV10096MDV115D50A96VA06096VA07096VA08596VA100R802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSAR95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSARGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMRRGRC-04EMAESRGRC-06EMAESRGRC-07EMAESRGRC-07ERBGSRGRC-09EZAJSRGRC-10EZAJSRGRM-04RGRM-06RGRM-07RGRM-09RGRM-10RGRM-12RGTC-04EMAESRGTC-06EMAESRGTC-07ERBGSRGTC-09EZAJSRGTC-10ERBJSRGTM-06RGTM-07RGTM-09RGTM-10

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.