Rheem · Furnace

20 Twinning fault

Medium severity Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)R95P

What the control is telling you

Twinning was detected and then lost in the same power cycle.

Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115)

Likely causes

  • TWIN wire broken or disconnected
  • Controls not identical (different part numbers)
  • 24 VAC transformers out of phase
  • TWIN setting wrong on a single furnace

Test and repair steps

  1. Check the wire between the TWIN terminals of both controls and the C and W connections (802P: also W2).
  2. Confirm both IFCs have the same part number (R95P manual: UT 1194-200 board).
  3. Check transformers are in phase (out of phase makes flame LED dim); both furnaces must be on the same power phase.
  4. For a single (non-twinned) furnace make sure TWIN is set to single / nothing connected.
  5. R95P see twinning wiring diagrams Fig. 43 (1-stage) and Fig. 44 (2-stage).

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.32, 40, 51; R95P: Twinning section and fault table, p.80 (PDF p.84). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.