Rheem · Furnace
11 Failed ignition
What the control is telling you
No flame proven during the ignition trial. The system tries 4 times, then goes into a 1-hour lockout (10 and 11 alternate on 802P/R95P). 802P: valve opens on low fire for 8 seconds, spark up to 7 seconds, flame must prove for 1 second. R95P/RGPE: valve powered about 7 seconds per trial. RGPE/RGLE: not stored back-to-back in the fault buffer.
Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+
Likely causes
- No gas, manual valve switch off, or low gas pressure
- Spark igniter not sparking, cracked, disconnected or misplaced
- Dirty flame sensor or poor sensor wiring
- L1 and neutral reversed
- Poor ground
- Blocked orifice / gas restriction
- R95P: pressure switch or limit opening during the trial
Test and repair steps
- Warning: Verify gas valve inlet and outlet (manifold) pressure with a manometer.
- Confirm the gas valve switch is ON and gas is supplied.
- Watch for spark check igniter wires, connection, cracks and placement/alignment.
- Clean the flame sensor rod (fine steel wool, Scotch-Brite or sandpaper) and check its wire to the IFC (RGPE/RGLE: J1 pin 1).
- Verify L1/neutral polarity at the IFC and junction box and check ground.
- Check orifices and burner alignment; confirm flame carries across all burners.
- R95P check 24 V at the gas valve during the trial and wiring IFC to valve; on 90+ check the aux limit and (upflow) drain pressure switch are closed.
- R95P if a pressure switch or limit opened during the trial, troubleshoot that circuit (57 / 22).
Settings for these units
Clearance to combustibles (all models) · R95P
| Location | Minimum clearance |
|---|---|
| Left side | 0 in. |
| Right side | 0 in. |
| Back | 0 in. |
| Top | 1 in. |
| Front | 2 in. |
| Vent | 0 in. |
| Service (front) | 24 in. recommended |
Same values for R95PA040 through 115.
Column order read from a rotated drawing header - confirm on the furnace clearance label.
Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
| Cabinet width | Input | Bottom filter | Side filter | Quantity |
|---|---|---|---|---|
| 17-1/2 in. | 50, 75 (000 Btu/h) | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 21 in. | 75, 100 (000 Btu/h) | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 24-1/2 in. | 125 (000 Btu/h) | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
Use one filter location only - do not double-filter or filter the supply side.
21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.
- Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Models that show this code
22 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P, RGPE/RGLE, R96V/96MDV
Other codes on the same units
Sequence of operation
What the unit does around this code, step by step.
- Failed ignition and flame loss retry · Ignition
- Gas heat call, ignition and retry (direct spark) · Ignition
- Heating ignition and blower sequence · Ignition
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40, 51; R95P: Diagnostics and Fault Codes table, p.87 (PDF p.91); RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.