Rheem · Furnace · Ignition
Gas heat call, ignition and retry (direct spark)
What happens, in order
- Thermostat W closes; control first confirms the pressure switch is open
- Inducer starts on high speed for pre-purge
- Pressure switches close; on the 802PA board the inducer then drops to low speed
- After the 30 s pre-purge the gas valve opens and the spark igniter fires for the 8 s trial for ignition
- Spark stays on for up to 7 s after the valve opens
- Flame sensor must prove flame by rectification at the 8 s mark, for 1 s
- Main blower starts about 20 s after burners light
- If no flame at 8 s valve closes, igniter off, inducer stops (can take up to 20 s to spin down) and control checks that the pressure switch reopened
- Control repeats pre-purge and trial; up to 4 attempts in total
- After the 4th failed try the control goes into a 1 hour lockout (codes 10 and 11 alternate)
- Call for heat ends valve closes, flame goes out, inducer runs a 10 s post-purge and pressure switch opens
- Main blower keeps running until the heat off delay set on the board expires
Timings and thresholds
| Item | Value |
|---|---|
| Pre-purge | 30 s |
| Trial for ignition | 8 s |
| Spark on after valve opens | up to 7 s |
| Flame proving | 1 s, checked at 8 s |
| Blower on delay | about 20 s after ignition |
| Post-purge | 10 s |
| Ignition attempts | 4, then lockout |
| Lockout | 1 hour |
Codes you may see during this
Applies to: Rheem 802PA two-stage furnace; Rheem R95P
Models
More Rheem furnace sequences
- Initial startup and lighting (communicating furnace) · Startup
- Gas heat call, direct spark ignition and retry · Ignition
- Gas heat call, hot surface ignition and retry · Ignition
- Heating ignition and blower sequence · Ignition
- Retry sequence when burners do not light or flame is not sensed · Ignition
- Two-stage gas heat call, ignition on high fire and retry · Ignition
- Two-stage heat call, high-fire light-off and staging · Ignition
- Heating call sequence of operation (Honeywell integrated control, direct spark ignition) · Heating
Related
Rheem error codes · Rheem tips · Rheem parts · All Rheem sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Rheem (-)802PA050314MSA installation manual, Sequence of Operations (UT electronic controls); Rheem R95P installation manual, Sequence of Operations. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.