Rheem · technician tips
Rheem service menus, test modes and resets
128 tips for furnace, heat pump: access codes, button combinations, test modes and the resets you need at the appliance.
Jump to: Access & passwords (1) · Button combinations (4) · Service & test modes (8) · Reset & cancel (10) · Settings shortcuts (1) · Commissioning (33) · Other (71)
Access & passwords
Installer and service menu codes, and how to get into them.
Changing dipswitches under the protective cover
Furnace · 96V / 96MDV
The dipswitches have a protective cover that must be pierced to change a switch position. Use a pen or similar tool. This is normal and does not damage the dipswitch.
- Use a pen or similar tool to press through the cover and set the switch.
Applies to: 96V and 96MDV integrated furnace control dipswitches S1, S2, S3
Source: Rheem 96V series installation instructions, p. 88. Written in our own words; check the manual for your exact model.
Button combinations
Key presses that open menus, show readouts or switch modes.
Test communication with the LEARN button (RGPE/RGLE)
Furnace · RGPE/RGLE
Holding LEARN makes the green RX LED blink rapidly if the control is trying to communicate. No blinking means communication cannot be established (check wires 1 and 2 at connector J9 are not reversed).
- Press and hold the LEARN button for two seconds
- Watch the green RX LED: a short burst of rapid blinking = attempting communication
- No blinking: check the 1, 2, R and C wiring between furnace, thermostat and condenser
Applies to: Rheem/Ruud RGPE / RGLE modulating furnaces
Source: RGPE Learn Button, p.42. Written in our own words; check the manual for your exact model.
Turn on extended display mode at power-up
Furnace · 96V, 96MDV
Pressing the pushbutton during the power-up sequence turns on extended display mode, which changes how the seven-segment display behaves.
- Hold or press the pushbutton while the furnace is powering up.
- Refer to the extended display mode table in the full manual for the display changes (the table is not legible on the extracted pages).
Applies to: 96V and 96MDV communicating furnaces
Source: 96V installation instructions, p. 96. Written in our own words; check the manual for your exact model.
Service & test modes
Forced fan, low and high fire, test and diagnostic modes, error history and live data.
Extended display mode
Furnace · R96V/96MDV
Pressing the pushbutton while the control powers up switches the displays to extended mode, which changes what is shown during operation.
- Cut power to the furnace.
- Hold the pushbutton and restore power.
- Cycle power again to return to the normal display (the extended-mode table is not readable in the text copy of the manual; see printed p.96).
Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces
Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, 15 Pushbutton p.96. Written in our own words; check the manual for your exact model.
Fault history display (FL)
Furnace · 96V, 96MDV
Up to six faults are stored, and the newest replaces the oldest. Faults older than 168 powered hours are deleted. Each fault code can be stored up to three times.
- Enter the FL menu with the pushbutton status mode
- Faults are shown one after another from newest to oldest, each for about one second with a short separator
- The sequence repeats until the status menu is exited
Applies to: 96V and 96MDV communicating furnaces
Source: Rheem 96V installation instructions, p. 95. Written in our own words; check the manual for your exact model.
Force high-stage gas heat for testing
Furnace · 96V
Used to test high-stage gas heat with a communicating thermostat.
- Remove the communication connections from the thermostat (E1, E2).
- Jumper W1 to R and R to W2 to set high-stage gas heat.
- Set the FAN switch to AUTO on the thermostat.
- Set the thermostat to call for heat with a temperature differential above 10°F.
- Note the dip switch settings before testing and restore them afterward.
- Test mode times out after one hour; check that the thermostat does not switch to high fire or test mode is not timing out.
Applies to: 96V and 96MDV series 2-stage communicating furnaces
Source: 96V series installation instructions, p. 121-122. Written in our own words; check the manual for your exact model.
Force low or high fire for testing (RGPE/RGLE)
Furnace · RGPE/RGLE
Temporarily locks the gas firing rate and blower to low or high for the heat call already running, up to two hours or until the call ends. Will not engage without a heat call.
- Start a heat call at the thermostat
- Open SETUP in the furnace USER MENU and choose FIXED FIRE RATE
- Select low or high; the setting lasts for this heat call (max 2 hours)
Applies to: Rheem/Ruud RGPE / RGLE modulating furnaces
Source: RGPE Furnace User Menus, SETUP item 5, p.56. Written in our own words; check the manual for your exact model.
Read or clear the six-fault history from the thermostat (RGPE/RGLE)
Furnace · RGPE/RGLE
The FAULT HISTORY user menu shows the six most recent faults, newest first, with the number of powered days ago. The last item, CLEAR FAULTS (yES / no), wipes the list.
- Open the furnace USER MENU at the communicating thermostat and select FAULT HISTORY
- Press the down arrow to step to older faults
- To erase, go to CLEAR FAULTS and pick yES
Applies to: Rheem/Ruud RGPE / RGLE modulating furnaces
Source: RGPE Furnace User Menus, FAULT HISTORY, p.55. Written in our own words; check the manual for your exact model.
Bypass the 3-minute timer and clear a lockout with TEST (PRL-JEC)
Heat pump · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Pressing TEST resets any active-protection lockout and the 3-minute anti-short-cycle timer, and energizes the unit even without a call. Use an insulated probe.
- Use an insulated probe to press TEST for one second, then let go
- With a call present the compressor and outdoor fan start and the display settles on c, C, h or H
- With no call a steady t shows and the compressor runs about 5 seconds
Applies to: Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC
Source: Rheem PRL-JEC Installation Instructions, Comfort Control2 section 12.5, p.23. Written in our own words; check the manual for your exact model.
Force a defrost test (PRL-JEC)
Heat pump · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
With the unit running in heat-pump mode, SW2 forces a defrost that runs until the termination temperature is reached or 14 minutes pass.
- Set the thermostat to heat and make a heat call
- Press SW2 for one second with the unit running in heat-pump mode
- Watch the unit enter defrost; press SW2 again to stop the test early
Applies to: Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC
Source: Rheem PRL-JEC Installation Instructions, 8.4-8.5 Defrost Test Mode. Written in our own words; check the manual for your exact model.
Review or clear stored faults on the ICC display (PRL-JEC)
Heat pump · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Scrolls the stored fault history on the dual display, newest first; up to six are kept and 0 means none. The mode exits by itself after the last fault.
- Press TEST and SW2 together with insulated probes for one second and release
- Watch the display scroll through the faults, newest first
- To erase, hold TEST and SW2 together for five seconds and release; the top and bottom segments flash to confirm
Applies to: Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC
Source: Rheem PRL-JEC Installation Instructions, Comfort Control2 section 12.5, pp.23-24. Written in our own words; check the manual for your exact model.
Reset & cancel
Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.
Clear a lockout
Furnace · 96V
Resets the control after a lockout.
- Shut off main power to the unit.
- Wait 30 seconds, then restore power.
- Or remove the heat call and re-establish it.
Applies to: 96V and 96MDV series 2-stage communicating IFC
Source: 96V series installation instructions, p. 121. Written in our own words; check the manual for your exact model.
Clear fault history by communication command
Furnace · 96V, 96MDV
The fault history can also be cleared over the communication link, without using the pushbutton.
- Send the HW1SHOTS write command with the Clear Alarm History Command field set.
- Confirm the display flashes segments A and D as the pushbutton clear does.
Applies to: 96V and 96MDV communicating furnaces
Source: 96V installation instructions, p. 96. Written in our own words; check the manual for your exact model.
Clear fault history with dipswitch S3-18
Furnace · 96V, 96MDV
Turning S3-18 off, on, off, on, off, on (or the reverse pattern) within less than 30 seconds clears the fault history buffer.
- Toggle S3-18 off/on/off/on/off/on, or on/off/on/off/on/off, three times within less than 30 seconds
Applies to: 96V and 96MDV furnaces, legacy mode
Source: Rheem 96V installation instructions, p. 91. Written in our own words; check the manual for your exact model.
Clear fault history with the pushbutton
Furnace · 96V, 96MDV
The fault buffer can be cleared from the furnace control pushbutton while the Fault History Display menu is active.
- Open the Fault History Display (FL) menu.
- Hold the pushbutton for 5 seconds or more.
- Watch for segments A and D on the right-most displays to flash on and off for one second each, three times, which confirms the buffer is clear.
Applies to: 96V and 96MDV communicating furnaces
Source: 96V installation instructions, p. 96. Written in our own words; check the manual for your exact model.
Clear the fault history
Furnace · R96V/96MDV
Two ways to wipe the six-fault buffer.
- With FL showing in the pushbutton menu, hold the button 5 seconds or more; the right display flashes its top and bottom bars three times.
- Or flip dipswitch S3-18 off/on three times (or on/off three times) within 30 seconds, then put it back to its original position.
- Faults older than 168 powered hours drop out by themselves.
Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces
Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, 15 Pushbutton p.96; 12.L p.91. Written in our own words; check the manual for your exact model.
Clearing lockouts
Furnace · R96V/96MDV
Soft lockouts (five-minute pressure switch, one-hour ignition/flame) and hard lockouts clear differently.
- Any lockout clears when the cause is fixed and power is cycled off and on.
- Soft lockout only: remove the heat call for more than 2 but less than 20 seconds.
- Hard lockout from a dead blower (61 four times in one call) clears if you cycle the heat call; a 93 hard lockout does not.
- During lockout, cooling and continuous fan still run but the display shows the lockout code instead of C or F.
Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces
Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, Lockout and replacing the furnace control p.121. Written in our own words; check the manual for your exact model.
Replay or clear the fault history on power-up (802P / 80MDP / R95P)
Furnace · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P
After a power cycle the seven-segment display replays the three most recent faults under one week old, newest first. An old code does not mean the fault is active now.
- Switch furnace power off and back on
- Watch the display: up to three stored faults flash, newest first
- To wipe the history, flip the fault-clear DIP switch (SW8 on the 802P control, SW4 on R95P) six times in a row, alternating, within 30 seconds, then put it back where it was
Applies to: Rheem/Ruud (-)802P / 80MDP 80% two-stage furnaces; R95P furnaces
Source: Rheem (-)802PA Installation Instructions, Diagnostics and Fault Codes (UT 1028-928 control), pp.40-41; Flame Status LED and Fault Recall (pp.43-44); R95P Fault Recall (printed p.90). Written in our own words; check the manual for your exact model.
Replay or clear the last five faults (RGPE/RGLE)
Furnace · RGPE/RGLE
On a power reset the dual display plays back the last five faults, newest first. Codes 82, 11, 45, 46 and 57 are not stored twice in a row.
- Cycle power to the furnace control
- Watch the display: the last five faults appear, newest first
- To clear, flip DIP switch SW3-2 four times in a row, alternating, within 30 seconds, then return it to its original position; or use CLEAR FAULTS in the thermostat menu
Applies to: Rheem/Ruud RGPE / RGLE modulating furnaces
Source: RGPE Fault Code Buffer, p.49. Written in our own words; check the manual for your exact model.
Reset a soft lockout (R95P)
Furnace · R95P
Soft lockouts can be cleared by cycling the heat call or power. A 1-hour lockout also resets on its own after one hour; a hard lockout (code 93) needs a power reset; code 61 hard lockout can be reset by cycling the heat call.
- Cycle the heat call off for 2 to 20 seconds, or cycle power
- Code 93 hard lockout: cycle power
Applies to: R95PA040, 060, 070 (1317MSA), R95PA085, 100 (1521MSA), R95PA115 (1524MSA); (-)95P series
Source: Rheem (-)95P Series single-stage condensing furnace Installation Instructions 92-24161-111-03, Sequence of Operation and Lockout, p.90-92. Written in our own words; check the manual for your exact model.
Reset the overtemperature safety switch
Furnace · 96V, 96MDV
The overtemperature switches sit in the burner compartment and trip when combustion air is inadequate. A tripped switch must be reset by hand, but only after the cause is cleared.
- Find the cause of the overtemperature trip, usually inadequate combustion air.
- Correct the cause.
- Press the manual reset on the switch in the burner compartment.
Applies to: All 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 46. Written in our own words; check the manual for your exact model.
Settings shortcuts
Where the useful parameters live and what they are set to from the factory.
Codes look upside down - display orientation switch S1-1
Furnace · R96V/96MDV
The control is used in upflow and downflow cabinets, so the display can be flipped. If a code is not on the list, it is probably being read upside down.
- S1-1 OFF = upflow (as shipped), ON = downflow.
- Set it to match the furnace position before reading fault codes.
Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces
Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, 12.A p.90. Written in our own words; check the manual for your exact model.
Commissioning
Start-up and set-up steps that are easy to miss.
Auxiliary drain pan over finished ceilings and living areas
Furnace · 96V, 96MDV
If the unit is installed over a finished ceiling or living area, put an auxiliary condensate drain pan under the entire unit. The pan must extend under any evaporator coil installed with the furnace and under the open portion of the condensate drain assembly.
Applies to: Installations over finished ceilings or living space
Source: 96V series installation instructions, p. 9. Written in our own words; check the manual for your exact model.
Bend the supply and return flanges before install
Furnace · 96V, 96MDV
Both flanges on the supply and return openings ship flat and must be bent up or down. They cannot be left flat.
- Bend each supply and return flange up or down with duck-billed (folding) pliers along the perforations.
Applies to: All 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 42. Written in our own words; check the manual for your exact model.
Check the IDB coupling arrow before reinstalling
Furnace · 96V, 96MDV
If the IDB coupling is removed during conversion, it must go back in the correct orientation. An arrow on the coupling shows the direction of exhaust flow.
- Find the arrow on the IDB coupling.
- Confirm the arrow points in the direction of exhaust flow before tightening the clamps.
Applies to: All 96V and 96MDV field conversions that remove the IDB coupling
Source: Rheem 96V installation manual, p. 17, 19, 23. Written in our own words; check the manual for your exact model.
Clean the furnace and ducts after construction
Furnace · 96V, 96MDV
After construction is substantially complete, clean the furnace, ductwork and components before final verification.
- Clean the furnace, duct work and components.
- Re-verify ignition, input, temperature rise and venting afterward.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 7. Written in our own words; check the manual for your exact model.
Communicating systems use the thermostat for setup
Furnace · 96V, 96MDV
On communicating systems the dipswitches are not used. Configuration changes are made at the thermostat. The dipswitch settings apply only in legacy (non-communicating) mode.
- Make configuration changes at the thermostat on communicating systems
Applies to: 96V and 96MDV communicating furnaces
Source: Rheem 96V installation instructions, p. 90. Written in our own words; check the manual for your exact model.
Condensate trap priming on first start
Furnace · 96V
The condensate trap is self-priming. It starts dry on the first heat attempt after install or after a long off period. Priming can take several cycles, especially on horizontal installs, because there is less water stored in the collector box.
- Expect the trap to be dry on the first firing after install or after a long summer off period.
- Let the inducer run. Water builds in the collector box until it reaches the lower water level sensor.
- Confirm the trap primes after the heat attempt ends and the inducer shuts off after post purge.
- If the trap is still not primed, allow up to four heat attempts before deciding there is a fault.
Applies to: Condensate drain trap, all 96V installs
Source: 96V series installation instructions, p. 67. Written in our own words; check the manual for your exact model.
Condensate vent tube height options
Furnace · 96V
Two options exist for the condensate vent riser height. The choice decides whether the furnace keeps running when the drain is blocked.
- Option A: put the top of the vent tube below the lower condensate water level sensor. The furnace keeps running when the drain is blocked, but water spills from the tube. Make sure there is a way to handle that water.
- Option B: put the top of the vent tube above the lower condensate water level sensor. A blocked drain shuts the furnace down and no water spills.
- Choose the option based on the customer's acceptance of overflow versus loss of heat.
Applies to: Condensate vent riser on all 96V furnaces
Source: 96V series installation instructions, p. 67. Written in our own words; check the manual for your exact model.
Confirm the gas type matches the rating plate
Furnace · 96V, 96MDV
Use the furnace only with the gas type approved for it. The furnace rating plate lists the approved gas.
- Read the furnace rating plate.
- Confirm the supply gas matches the approved type before firing the unit.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 6. Written in our own words; check the manual for your exact model.
Evaporator coil airflow order and damper control
Furnace · 96V, 96MDV
With a cooling evaporator coil, air must pass over the heat exchanger before it passes over the cooling coil. Cold air over the heat exchanger tubes can cause internal condensation, corrosion and eventual failure. Manual dampers must be arranged so heating or cooling cannot run unless the damper is in the full heat or full cool position.
- Confirm the airflow path goes through the heat exchanger before the cooling coil.
- Confirm manual dampers block heating or cooling operation unless fully in the correct position.
Applies to: Furnaces used with a cooling evaporator coil
Source: 96V series installation instructions, p. 9. Written in our own words; check the manual for your exact model.
Expose fresh copper on reused thermostat wire
Furnace · 96V, 96MDV
Old wire from a previous installation must be prepared before connecting it, or the communication link may not establish.
- Trim back the wire tip past the old insulation.
- Strip a small amount of insulation to expose clean new copper for the communicating connections.
Applies to: 96V and 96MDV communicating systems
Source: 96V installation instructions, p. 99. Written in our own words; check the manual for your exact model.
Gas pressure regulator and purging
Furnace · 96V
A regulator may be needed in the supply line. Its outlet must not exceed the maximum supply pressure on the rating plate. Industrial regulators are not allowed. Gas piping must be purged to a safe location per NFGC section 8.3.
- Confirm the regulator will not deliver more than the maximum supply pressure on the rating plate.
- Do not use an industrial-type gas regulator.
- Purge the gas piping following local codes and NFGC section 8.3 so no explosive mixture can build up.
- Only connect to gas from a commercial utility or commercial fuel provider.
Applies to: Gas supply pressure and purging
Source: 96V series installation instructions, p. 69. Written in our own words; check the manual for your exact model.
Gas valve connection and leak check
Furnace · 96V
Pipe strain can move the burner orifices and cause erratic operation. Leaks must be found with a soap solution, never an open flame.
- Use a back-up wrench on the manifold and gas valve when making the connection so the valve does not twist.
- Do not overtighten the gas valve onto the pipe.
- Use a pipe compound that resists LP gas on all threaded joints.
- Check all gas fittings with a soapy solution. Bubbles mean a leak to fix.
- Never test for leaks with an open flame.
Applies to: Gas valve and piping connections
Source: 96V series installation instructions, p. 70. Written in our own words; check the manual for your exact model.
Ground thermostat wire shield at one point only
Furnace · 96V, 96MDV
Shielded thermostat wire is used where the wiring runs near high voltage, cable TV, Ethernet or radio equipment. The shield must be continuous and grounded in only one place.
- Twist shield wires together across each segment so the shield is continuous.
- Connect the shield to the C terminal or ground at the indoor unit.
- Do not connect the shield to any terminal at the thermostat.
- Do not ground the shield at both ends.
Applies to: 96V and 96MDV communicating systems
Source: 96V installation instructions, p. 99. Written in our own words; check the manual for your exact model.
Install only in an approved location and position
Furnace · 96V, 96MDV
Place the furnace only in a location and position listed in the location requirements section. Any other placement can cause unsatisfactory operation or dangerous conditions and voids the warranty.
- Check the location requirements section before setting the furnace.
- Confirm the installation follows the CSA certification and these instructions.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 6. Written in our own words; check the manual for your exact model.
Leak test gas connections with soap solution only
Furnace · 96V, 96MDV
Never check for gas leaks with an open flame. Use a commercial leak-detection soap solution on all connections covered in the gas supply and piping section.
- Apply leak-detection soap solution to every gas connection.
- Look for bubbles and fix any leak before startup.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 6. Written in our own words; check the manual for your exact model.
Legacy 1-stage thermostat jumper
Furnace · 96V, 96MDV
A legacy 1-stage thermostat with autostaging is wired to the furnace. For one-stage cooling a jumper is needed between Y1 and Y2.
- Wire the legacy 1-stage thermostat per the autostaging wiring diagram.
- Install a jumper between Y1 and Y2 for one-stage cooling.
- The jumper is only used for heat pump installations in the wiring diagram.
Applies to: 96V and 96MDV furnaces with legacy thermostats
Source: 96V installation instructions, p. 101. Written in our own words; check the manual for your exact model.
Level the furnace with a slight tilt toward the front
Furnace · 96V, 96MDV
Install the furnace level from front to back or with a slight tilt so the back is up to 1/2 inch higher than the front. Figure 3 gives the tilt as 1/4 inch minimum to 1/2 inch maximum toward the front in all installations and orientations.
- Set the cabinet level or tilted 1/4 in. to 1/2 in. toward the front.
- Verify the tilt in upflow, downflow and horizontal orientations.
Applies to: All orientations
Source: 96V series installation instructions, p. 9. Written in our own words; check the manual for your exact model.
Limit total static pressure on the distribution system
Furnace · 96V, 96MDV
Total static pressure drop of the whole air distribution system, including any AC coil, air filtration, zoning, and ductwork, must not exceed 0.8 in W.C. Size the duct for the maximum possible airflow, because heating airflow can be higher than cooling airflow. Check the added equipment data for pressure drop at the recommended heating or cooling CFM.
- Size duct to the maximum airflow value, not just the cooling value.
- Add up pressure drop of coil, filters, zoning and ductwork.
- Confirm the total is 0.8 in W.C. or less at recommended CFM.
Applies to: All 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 42. Written in our own words; check the manual for your exact model.
Massachusetts CO detector and signage rules for sidewall horizontal venting
Furnace · 96V, 96MDV
In Massachusetts, sidewall horizontally vented gas equipment with the exhaust termination less than 7 feet above finished grade (including over decks and porches) needs hard-wired CO detectors with battery backup on the floor where the appliance is installed, plus CO detectors on each additional level. A metal or plastic sign reading GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS must be mounted 8 feet above grade in line with the vent. Detectors must meet NFPA 720 and ANSI/UL 2034 and be IAS certified. If the detectors cannot be installed at completion, a battery CO detector must be used during the 30-day allowance.
- Confirm the exhaust termination height above finished grade.
- Install hard-wired CO detectors with battery backup on the appliance floor and on each additional level.
- If not possible at completion, install battery CO detectors and finish the hard-wired installation within 30 days.
- Mount the required warning sign 8 feet above grade in line with the exhaust terminal.
Applies to: Sidewall horizontal vent installations in Massachusetts
Source: 96V series installation instructions, p. 8. Written in our own words; check the manual for your exact model.
Non-communicating condenser wiring
Furnace · 96V, 96MDV
A non-communicating condenser or heat pump used with a communicating furnace and thermostat needs a special configuration.
- Run four dedicated wires (E1, E2, R and C) from the furnace to the condenser.
- Use a daisy-chain layout only; a star layout is not approved.
- Wire the thermostat using the non-communicating condenser diagram.
Applies to: 96V and 96MDV communicating furnaces with non-communicating condensers
Source: 96V installation instructions, p. 100. Written in our own words; check the manual for your exact model.
Preparing the furnace for installation
Furnace · 96V, 96MDV
Remove the solid metal base pan from the top of the furnace. It is for shipping only and must not stay in place after installation. Install the furnace with a 1/4 inch to 1/2 inch forward slope toward the front for drainage. Allow access for service.
- Remove the solid metal base pan from the top of the furnace.
- Set the furnace with a 1/4 inch to 1/2 inch forward slope toward the front.
- Leave room for service access.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 4. Written in our own words; check the manual for your exact model.
Protect the condensate trap and line from freezing
Furnace · 96V
If the furnace sits where temperatures can drop below freezing, the trap and condensate line will freeze. That shuts the furnace down or damages the trap unless freeze protection is installed.
- Install freeze protection on the trap and all condensate lines wherever freezing is possible.
- Do not run the condensate drain outdoors. Frozen condensate can cause property damage.
Applies to: Condensate trap and condensate lines
Source: 96V series installation instructions, p. 67. Written in our own words; check the manual for your exact model.
Receiving and pre-install checks
Furnace · 96V, 96MDV
Inspect all cartons on arrival and note any transit damage on the delivery papers before filing a claim. Verify the carton and rating plate model numbers match the job before opening the carton. Check the rating plate against job specs.
- Inspect cartons immediately for transit damage and note it on the delivery papers.
- Compare the carton label model number with the job order before opening.
- Open the carton and confirm the furnace rating label matches the carton model number.
- Check the rating plate matches the job specifications.
- Read the full instructions before starting.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 4. Written in our own words; check the manual for your exact model.
Replace furnaces immersed in water
Furnace · 96V, 96MDV
Any equipment immersed in water, including by flooding, must be replaced. Water-damaged equipment will have its operation adversely affected and the warranty is void.
- Replace any furnace that has been immersed in water, including by flooding.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 4. Written in our own words; check the manual for your exact model.
Replacing the furnace control: keep the memory card and copy the dipswitches
Furnace · R96V/96MDV
The model data lives on a memory card tethered to the furnace; the new control is useless without it.
- Pull the memory card out of the old control and plug it into P6 of the replacement. Do not cut the plastic tether.
- Copy every dipswitch position from the old board to the new one.
- Never use a control or card from another furnace, condenser or air handler. A lost card is ordered from ProStock by furnace model and serial number; cycle power after fitting it or the data is not read.
Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces
Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, Replacing the furnace control p.121; 13 Model data card p.92. Written in our own words; check the manual for your exact model.
Return air and outside air limits
Furnace · 96V, 96MDV
When outside air is used, the system must hold return air above 55 F during the heating season. Return grilles and warm air registers must not be blocked or closed. Do not take return air from furnace rooms, garages, cold areas, utility rooms, kitchens, laundry rooms or bathrooms.
- Check return air temperature stays above 55 F with outside air in use.
- Confirm return grilles and warm air registers are open.
- Route return air from an approved area only.
Applies to: All 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 42. Written in our own words; check the manual for your exact model.
Review checklist after horizontal right conversion
Furnace · 96V, 96MDV
Check these items before you leave the job after the horizontal right conversion.
- Make sure all hoses are secure and fully seated.
- Check that no hose has kinks.
- Confirm all hoses and drain parts slope in the direction of water flow.
- Confirm both worm-drive clamps on the flue transition are tight.
- Tighten all clamps and couplings.
- Plug all drain ports.
- Confirm the unit has forward pitch.
- Install heat tape if the site requires it.
- The drain trap must sit on top of the coupling, per the location detail in the general conversion instructions.
Applies to: Horizontal right conversions (96V and 96MDV)
Source: Rheem 96V series installation instructions, p. 30. Written in our own words; check the manual for your exact model.
Set input rate and temperature rise to the rating plate
Furnace · 96V, 96MDV
The furnace must run within its intended temperature-rise range on a duct system with external static pressure in the allowable range. Set input rate and temperature rise to the rating plate markings. Return air temperature must stay between 55°F (13°C) and 80°F (27°C).
- Check external static pressure against the ducting section limits.
- Set the input rate and temperature rise per the rating plate.
- Keep return air between 55°F (13°C) and 80°F (27°C).
- Verify ignition, input rate, temperature rise and venting after the job is complete.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 7. Written in our own words; check the manual for your exact model.
Single-stage thermostat on a two-stage furnace: auto staging
Furnace · R96V/96MDV
With only W1 wired, the furnace can step itself up to high fire after a set time.
- Set S2-10 / S2-11: OFF-OFF normal two-stage (default); ON-OFF 10 min on low then high; OFF-ON 15 min; ON-ON 20 min.
- A W2 call still forces high stage even with auto staging on.
- Communicating systems ignore the dipswitches; staging is set at the thermostat.
Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces
Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, 12.G p.91. Written in our own words; check the manual for your exact model.
Site selection and service clearance
Furnace · 96V, 96MDV
Choose a site near the center of the duct system, keep vent runs short with minimal elbows, and locate the furnace near existing gas piping. Keep at least 24 in. (30 cm) of service clearance in front of all furnaces. Use the 24 in. figure if accessibility clearance is greater than the fire protection clearance.
- Place the furnace near the center of the duct system.
- Keep the vent run short with minimal elbows.
- Keep at least 24 in. (30 cm) in front of the furnace for service.
Applies to: All installations
Source: 96V series installation instructions, p. 10. Written in our own words; check the manual for your exact model.
Test a new safety switch before handing over
Furnace · 96V, 96MDV
A newly installed safety switch must be tested under load with the blower and burner door in place. If the closet door is part of the installation, it must be closed during the test. Multi-stage furnaces need a second test at minimum input.
- Install the blower and burner door.
- Run the furnace at maximum input rate for at least 15 minutes.
- If the closet has a door, keep it closed during the test.
- On a multi-stage furnace, repeat the test at minimum input rate.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 6. Written in our own words; check the manual for your exact model.
Thermostat setpoint for startup tests
Furnace · 96V / 96MDV
High stage is only called when the thermostat setpoint is more than about 2 F above room temperature. Low stage is generally called with the setpoint about 1 F above room temperature. Confirm with the thermostat specs.
- Set the thermostat setpoint for high stage and verify high heat for 15 minutes.
- Set the thermostat setpoint for low stage and verify low heat for 15 minutes.
Applies to: 96V and 96MDV furnaces
Source: Rheem 96V series installation instructions, p. 83. Written in our own words; check the manual for your exact model.
Wire auxiliary switches to T5
Furnace · 96V, 96MDV
Up to two field switches (drain pan, smoke detector, freeze switch and similar) can be wired to the T5 auxiliary inputs on communicating systems only.
- Wire each switch to Aux 1 or Aux 2 on terminal T5.
- At the communicating thermostat, set each input as normally open or normally closed.
- Configure what the system does when the contacts open or close at the thermostat.
Applies to: 96V and 96MDV communicating systems
Source: 96V installation instructions, p. 98. Written in our own words; check the manual for your exact model.
Other
Everything else worth knowing at the appliance.
Alternate horizontal termination
Furnace · 96V, 96MDV
The vent terminal sits 8 to 12 in from the wall. The vent tip portion must remain vertical. The vent may be rotated up to 45° left or right from vertical as long as the tip stays vertical. Maximum length shown is 60 in.
- Set the terminal 8 to 12 in from the wall.
- Keep the tip portion vertical.
- Rotate the vent no more than 45° left or right if needed.
Applies to: Alternate horizontal non-direct vent termination
Source: 96V Series installation instructions, p. 56. Written in our own words; check the manual for your exact model.
Avoid chemicals that contaminate combustion air
Furnace · 96V, 96MDV
Combustion air must not come from a corrosive atmosphere. Acid-forming chemicals such as sulfur, fluorine and chlorine can turn into corrosive acids when burned. Common sources include aerosol sprays, bleaches, cleaning solvents, paint removers, refrigerants, pool chemicals, and cements. Areas like laundry rooms, hobby rooms, indoor pools and chemical storage may need direct vent with outside air.
- Check the combustion air area for chemical exposures listed in the manual.
- If exposure exists, switch to direct vent with outside air.
Applies to: All 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 45. Written in our own words; check the manual for your exact model.
Blower and induced draft motor lubrication
Furnace · 96V, 96MDV
Do not add lubricant to the blower motor or induced draft blower motor bearings. Both motors are permanently lubricated. Adding lubricant can shorten motor life and void the warranty. Clean the motors periodically to prevent overheating from dust buildup on windings or housing.
- Clean blower and induced draft motors periodically, including windings and exterior.
- Keep filters clean so the motor has adequate airflow for cooling.
- Never add lubricant to motor bearings.
Applies to: R96V furnace motors
Source: Rheem 96V installation manual, p. 106. Written in our own words; check the manual for your exact model.
Check vent run against maximum equivalent length
Furnace · 96V, 96MDV
Add the actual pipe length and the equivalent length of all elbows. The total must not exceed the maximum equivalent vent length for the model. Example from the manual: a 60 KBTU direct-vent run of 31 ft of 2 in pipe with 5 long-sweep elbows gives 56 equivalent ft, which is acceptable against a 65 ft maximum. The same run with standard elbows gives 81 ft and is not acceptable.
- Measure the straight pipe length.
- Add 5 ft per long-sweep elbow or 10 ft per standard elbow.
- Compare the total with the model maximum in the vent length table.
Applies to: All 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 48. Written in our own words; check the manual for your exact model.
Condensate drain connection options
Furnace · 96V, 96MDV
Condensate drain has options for 3/4 in. or 1/2 in. PVC connections. The trap also accepts a 5/8 in. rubber hose with a hose clamp when mounted inside the unit. Improper hose connections will stop condensate from draining and may damage the furnace. The trap has two sides, so note the inlet and outlet locations when converting.
- Select 3/4 in. or 1/2 in. PVC, or a 5/8 in. hose with clamp for an internal trap.
- Confirm the trap inlet and outlet sides match the conversion.
- Confirm the drain connection allows condensate to drain freely.
Applies to: All conversions
Source: 96V series installation instructions, p. 12. Written in our own words; check the manual for your exact model.
Condensate neutralizer and overflow line
Furnace · 96V
A neutralizer cartridge is needed only where local codes require it. The overflow line is required only when the neutralizer is used and the drain runs to a floor drain.
- Install the neutralizer cartridge in the horizontal position only.
- When routing to a floor drain, also install an overflow line.
- If no floor drain is available, use a condensate pump.
Applies to: Condensate drain with optional neutralizer
Source: 96V series installation instructions, p. 67. Written in our own words; check the manual for your exact model.
Condensate pump requirements
Furnace · 96V
The pump must resist acidic water, or a neutralizer must go ahead of it. The pump needs an auxiliary safety switch to stop the furnace if the pump fails.
- Use an acid-resistant condensate pump, or install a neutralizer ahead of the pump.
- Install an auxiliary safety switch on the pump to prevent furnace operation and overflow if the pump fails.
- Wire the safety switch through the R (low voltage) circuit only so the furnace runs in heating or cooling.
Applies to: Condensate pump installs
Source: 96V series installation instructions, p. 67. Written in our own words; check the manual for your exact model.
Conversion configurations and kit requirements
Furnace · 96V, 96MDV
Field conversions are possible from upflow (as shipped) to downflow, horizontal left or horizontal right. Each configuration lists a kit requirement. Upflow with vertical vent uses only the parts bag. The other configurations need kit RXGY-CK, and some also need zero-clearance kit RXGY-ZK. The page layout links kit labels to sections; verify on page 14.
- Select the configuration (upflow, downflow or horizontal, left or right vent).
- Check whether conversion kit RXGY-CK is required.
- Check whether zero-clearance kit RXGY-ZK is also required.
- Follow the page listed for that configuration.
Applies to: All field conversions
Source: 96V series installation instructions, p. 14. Written in our own words; check the manual for your exact model.
Dehumidification dipswitch S2-8 warning
Furnace · 96V / 96MDV
S2-8 (labeled ODD) turns dehumidification on or off. It does not affect humidification. If it is ON with no humidistat installed, cooling airflow is permanently reduced by about 15 percent.
- Set S2-8 OFF unless a humidistat is installed and dehumidification is needed.
Applies to: 96V and 96MDV furnaces with humidification or dehumidification
Source: Rheem 96V series installation instructions, p. 86. Written in our own words; check the manual for your exact model.
Do not bypass or jumper safety switches
Furnace · 96V, 96MDV
Do not bypass, jumper or remove any safety switch. If a safety switch shuts the furnace down or makes it cycle, that is a safety hazard for a qualified technician to fix. Do not reset safety controls without corrective action and verification. Replace safety control parts only with identical OEM parts.
- Find and fix the cause of any safety switch trip.
- Verify safe operation before resetting.
- Replace safety components only with identical OEM parts.
Applies to: All 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 46. Written in our own words; check the manual for your exact model.
Do not connect a phone line to the control
Furnace · 96V / 96MDV
The RJ-14 jack (J-11 / J1) is used only for factory programming. Connecting a telephone or phone line can cause irreparable damage to the furnace control, the telephone or the phone line.
Applies to: 96V and 96MDV communicating furnace control
Source: Rheem 96V series installation instructions, p. 85. Written in our own words; check the manual for your exact model.
Do not install in a mobile home
Furnace · 96V, 96MDV
This furnace is not approved for mobile home installation. Installing it in one can cause fire, property damage, injury or death.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 6. Written in our own words; check the manual for your exact model.
Downflow non-combustible floor base requirement
Furnace · 96V, 96MDV
A downflow unit is certified only for a non-combustible floor. Use the special base listed on the furnace clearance label. The base is sold as an accessory. Not installing it can cause fire, property damage or injury. A base is needed when installing on a combustible floor without an air conditioning plenum.
- Confirm the floor is non-combustible or install the special base from the clearance label.
- Order the base as an accessory if it is not already on site.
Applies to: Downflow installations
Source: 96V series installation instructions, p. 43. Written in our own words; check the manual for your exact model.
Downflow non-zero clearance on the right side
Furnace · 96V, 96MDV
For downflow non-zero clearance installs, the minimum right-side clearance is shown in Figure 4. If that clearance cannot be kept, a downflow zero-clearance kit RXGY-ZK must be installed.
- Check the right-side clearance against Figure 4.
- If the clearance cannot be met, install zero-clearance kit RXGY-ZK.
Applies to: Downflow installations
Source: 96V series installation instructions, p. 10. Written in our own words; check the manual for your exact model.
ECM blower communications are separate
Furnace · 96V / 96MDV
The ECM blower motor does not use the same communications bus as the furnace, condenser or thermostat. It uses a different protocol on its own peer-to-peer network at connector P4.
Applies to: 96V and 96MDV furnaces with ECM blower
Source: Rheem 96V series installation instructions, p. 88. Written in our own words; check the manual for your exact model.
Electrical supply and overcurrent protection
Furnace · 96V, 96MDV
Match the voltage, frequency and phase to the rating plate. For one furnace, maximum overcurrent protection is 15 amps. Use a separate fused or breaker-protected branch circuit run to a disconnect near the furnace.
- Confirm voltage, frequency and phase against the rating plate.
- Protect the circuit with a maximum 15 amp fuse or breaker.
- Run the circuit to an accessible disconnect near the furnace.
- Keep electrical components protected from condensate.
Applies to: Furnace electrical supply
Source: 96V series installation instructions, p. 76. Written in our own words; check the manual for your exact model.
Electronic air cleaner output
Furnace · 96V, 96MDV
Line voltage for an electronic air cleaner comes from the EAC terminal and a neutral terminal on the control board. It runs whenever the circulating blower runs, but only above the minimum target CFM for the model. Maximum current is 1.0 amp.
- Connect the air cleaner to the EAC terminal and control board neutral.
- Confirm the target CFM is above the model threshold, or the output will not energize.
Applies to: Furnaces with EAC output
Source: 96V series installation instructions, p. 78. Written in our own words; check the manual for your exact model.
Factory setting and LP conversion
Furnace · 96V
The furnace is factory set for natural gas only. Conversion to LP needs the special kit listed in the kit index that ships with the furnace. Using the wrong kit can cause fire, CO poisoning or explosion.
- Confirm the fuel on the rating plate matches the gas supply before firing.
- For LP, use only the conversion kit listed in the kit index supplied with the furnace.
- Have a qualified installer, service agency or gas supplier make any conversion, using factory-specified or approved parts.
Applies to: Gas type conversion on all 96V furnaces
Source: 96V series installation instructions, p. 70. Written in our own words; check the manual for your exact model.
Filters and twinning
Furnace · 96V, 96MDV
A filter is not supplied and must be field-installed and kept clean. Twinning of these furnaces is not permitted.
- Install a field-supplied filter and keep it clean.
- Do not twin these furnaces.
Applies to: All 96V and 96MDV furnaces
Source: 96V series installation instructions, p. 78. Written in our own words; check the manual for your exact model.
Flexible gas connector limits
Furnace · 96V, 96MDV
Do not run a flexible gas connector inside the furnace; the cabinet gas pipe gasket does not seal around it. Where codes allow one, use a new listed connector. Massachusetts requires flexible connectors under 36 in.
- Do not run a flexible connector inside the cabinet.
- Use only a new listed connector that has never served another gas appliance.
- In Massachusetts keep flexible connectors under 36 in.
Applies to: Gas connections
Source: 96V series installation instructions, p. 73. Written in our own words; check the manual for your exact model.
Freeze protection for the condensate trap and drain
Furnace · 96V, 96MDV
Where the furnace may see temperatures below 32 °F (0 °C), such as an alcove or attic, protect the drain trap and drain piping from freezing. If the trap is inside the cabinet, no freeze protection is needed. A trap mounted outside or partly outside the cabinet must be protected, and exposed drain piping must be protected per local practice. A UL or CSA listed heat tape or heating cable rated 3-6 watts per foot is acceptable. Verify heat tape operation at installation.
- Check whether the trap is inside or outside the cabinet.
- Install listed heat tape or heating cable rated 3-6 W/ft on any exposed trap or drain piping.
- Verify heat tape operation per its instructions at installation.
Applies to: Attic, alcove, crawl space or other cold-location installs
Source: 96V series installation instructions, p. 9. Written in our own words; check the manual for your exact model.
Gas detectors and LP below-grade limit
Furnace · 96V
UL or CSA recognized fuel gas and CO detectors are recommended on all applications. LP furnaces must not be installed below grade where local law prohibits it.
- Install UL or CSA recognized fuel gas and CO detectors per the detector maker and local rules.
- Do not install LP furnaces below grade (such as a basement) if local rules prohibit it.
Applies to: Installations with natural gas or LP
Source: 96V series installation instructions, p. 69. Written in our own words; check the manual for your exact model.
Gas valve operation and gas line purging
Furnace · 96V, 96MDV
The 24-volt gas valve has inlet and outlet pressure taps and a regulator. Its control switch only sets ON or OFF. It opens slowly, taking 2 to 3 seconds. Never purge a gas line into the combustion chamber.
- Check that the gas valve control switch is set to ON or OFF only.
- Allow 2 to 3 seconds for the valve to fully open after it is energized.
- Never purge a gas line into the combustion chamber.
Applies to: Gas valve
Source: 96V series installation instructions, p. 73. Written in our own words; check the manual for your exact model.
Gas valve pressure test limit
Furnace · 96V, 96MDV
Disconnect the furnace and its manual gas stop from supply piping before any test above 1/2 PSIG (3.48 kPa). The gas valve is not rated for high line pressure.
- Disconnect the furnace and its manual gas stop before pressure testing above 1/2 PSIG.
Applies to: Gas supply piping tests
Source: 96V series installation instructions, p. 73. Written in our own words; check the manual for your exact model.
General condensate and conversion rules
Furnace · 96V, 96MDV
All conversions require condensate plumbing to slope in the direction of water flow. Hoses must be free of kinks. Plug or cap any unused hose taps when hose routing changes. The inducer coupling ships with a 10-20 degree tilt for upflow. When converted to downflow, rotate the inducer coupling as shown, at least 10 degrees from horizontal. The IDB coupling arrow must point in the exhaust flow direction when reinstalled.
- Slope all condensate plumbing in the direction of water flow.
- Remove kinks from all condensate hoses.
- Plug or cap unused hose taps.
- Rotate the inducer coupling for downflow, at least 10 degrees from horizontal.
- Reinstall the IDB coupling with the arrow pointing in the exhaust flow direction.
Applies to: All field conversions
Source: 96V series installation instructions, p. 12. Written in our own words; check the manual for your exact model.
Grounding and blower door safety switch
Furnace · 96V, 96MDV
The cabinet needs an uninterrupted ground to the junction box ground screw. Do not use gas piping as ground. Do not disable the blower door safety switch.
- Connect the cabinet to the junction box ground screw.
- Do not use gas piping as the ground.
- Do not disable the blower door safety switch.
Applies to: Electrical installation
Source: 96V series installation instructions, p. 76. Written in our own words; check the manual for your exact model.
Heat loss calculation and duct design
Furnace · 96V, 96MDV
Perform a heat loss calculation to size the furnace BTU output for the structure. Ducts must be designed and installed for proper airflow. Inspect existing ductwork for proper size and sealing. Proper airflow affects comfort and equipment performance.
- Run a heat loss calculation to determine the required furnace BTU size.
- Design and install ducts for proper airflow.
- Inspect existing ducts for correct size and sealing.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 3. Written in our own words; check the manual for your exact model.
Horizontal installation: external condensate trap and clamps
Furnace · 96V, 96MDV
Horizontal installations require the condensate trap mounted externally below the unit. Mount the trap after the unit is at its installation point to avoid damage in transport. Hand-tighten screws when mounting the trap or drain coupling to protect the mounting flange. Allow at least 6 in. of clearance below the furnace. When horizontal, worm drive clamps on the flue transition or IDB couplings must sit above the level midline.
- Mount the trap externally below the unit after the furnace is in place.
- Hand-tighten the trap and drain coupling screws.
- Keep at least 6 in. of clearance below the furnace.
- Position worm drive clamps on the flue transition and IDB couplings above the midline.
- Apply freeze protection if required.
Applies to: Horizontal left and right conversions
Source: 96V series installation instructions, p. 12. Written in our own words; check the manual for your exact model.
Humidifier output
Furnace · 96V, 96MDV
The humidifier output is a set of dry contacts. Logic and wiring diagrams are in the Humidification/Dehumidification section.
- Wire the humidifier to the dry contacts as shown in the Humidification/Dehumidification section.
Applies to: Humidifier accessory
Source: 96V series installation instructions, p. 78. Written in our own words; check the manual for your exact model.
IDB coupling orientation
Furnace · 96V, 96MDV
If the IDB coupling is removed during conversion, it must go back in the right direction. The coupling has an arrow showing exhaust flow direction, and the arrow must point the correct way.
- Before reinstalling the IDB coupling, find the arrow on the coupling.
- Check that the arrow points in the direction of exhaust flow.
Applies to: Horizontal right with vertical vent conversion
Source: Rheem 96V series installation instructions, p. 31. Written in our own words; check the manual for your exact model.
Indoor combustion air protection and exhaust fans
Furnace · 96V, 96MDV
When indoor air is used for combustion, the inlet opening at the furnace must be protected from accidental blockage. Do not take air from a heated space with a fireplace, exhaust fan or other device that may cause negative pressure. If an exhaust fan is installed, provide enough ventilation to prevent negative pressure.
- Protect the furnace combustion air inlet from blockage.
- Do not draw indoor combustion air from spaces with fireplaces or exhaust fans.
- Provide enough ventilation to stop negative pressure from exhaust fans.
Applies to: Non-direct vent installations using indoor air
Source: 96V Series installation instructions, p. 52, 55. Written in our own words; check the manual for your exact model.
Install an auxiliary drain pan where damage could occur
Furnace · 96V, 96MDV
Recognized codes recommend an auxiliary drain pan under the furnace and under any evaporator coil located where an overflow or blocked primary drain could damage the building or its contents.
- Install an auxiliary drain pan under the furnace and any evaporator coil in areas where water damage is possible.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 6. Written in our own words; check the manual for your exact model.
Installation warnings for the cabinet and jacket
Furnace · 96V, 96MDV
Do not install the furnace on its back with access doors facing up. Do not lift the unit by the heat exchanger tubes, as this can damage the heat exchanger. Keep combustible materials, gasoline and other flammable vapors and liquids away from the furnace jacket. Do not use the furnace area as a storage or broom closet.
- Do not install the furnace on its back with access doors up.
- Lift the unit by the cabinet, not the heat exchanger tubes.
- Keep the area around the furnace clear of combustibles and flammable liquids.
Applies to: All installations
Source: 96V series installation instructions, p. 10. Written in our own words; check the manual for your exact model.
Insulate vent in freezing spaces
Furnace · 96V, 96MDV
Vents through unconditioned spaces where below-freezing temperatures are expected must be insulated with approved insulation. Armaflex or Rubatex may be used. Do not apply heat tape to the vent pipe. Un-insulated pipe can freeze and block the vent, preventing furnace operation.
- Insulate the vent through unconditioned space with approved insulation.
- Do not install heat tape on the vent pipe.
Applies to: Vents through unconditioned spaces
Source: 96V Series installation instructions, p. 55. Written in our own words; check the manual for your exact model.
Integrated furnace control layout and key connections
Furnace · 96V / 96MDV
Key items on the integrated furnace control: P1, P2 and P5 are factory-wired low-voltage harness connections. J1 (RJ-14) is for factory programming only. T1 is the spark ignition transformer (about 60 Hz, minimum 12 kV). P3 is the inducer output (120 VAC, high and low speed). T3 is the EAC output. P4 is the ECM blower communications connection. S1, S2 and S3 are dipswitch banks. S4 is the bias/termination dipswitch bank. U38 holds the TX (red) and RX (green) communications LEDs. S8 is the pushbutton. U38 also drives the dual 7-segment display. P6 is the memory card connector. Humidifier relay contacts are labeled HUM.
Applies to: R96V two-stage communicating furnace control
Source: Rheem 96V series installation instructions, p. 84-85. Written in our own words; check the manual for your exact model.
L1 and L2 polarity
Furnace · 96V, 96MDV
L1 (hot) and L2 (neutral) polarity must be correct. If they are reversed, the ignition control may not sense flame.
- Confirm L1 and L2 are not reversed when making field connections.
- If flame sensing faults after install, check line polarity first.
Applies to: Line voltage connections
Source: 96V series installation instructions, p. 76. Written in our own words; check the manual for your exact model.
Leak checking gas connections
Furnace · 96V, 96MDV
Never use matches, flame or any ignition source to find leaks. Use an approved chloride-free soap and water solution or another approved detector. Repair any leak and check again.
- Apply approved chloride-free soap and water solution to each joint.
- Repair any leak and repeat the check.
- Never use a flame to check for leaks.
Applies to: All gas connections
Source: 96V series installation instructions, p. 73. Written in our own words; check the manual for your exact model.
LP tank contamination warning
Furnace · 96V, 96MDV
LP tanks, trucks and other delivery vessels must not hold anything but LP gas, such as fertilizer. Contamination can damage the furnace and voids the warranty. Confirm with the supplier.
- Confirm with the LP supplier that the tanks and vessels are used only for LP gas.
Applies to: LP gas supply
Source: 96V series installation instructions, p. 74. Written in our own words; check the manual for your exact model.
Massachusetts side-wall vent: CO detectors and warning sign
Furnace · 96V, 96MDV
For side-wall horizontal vent terminations less than 7 ft above grade in Massachusetts homes, a hard-wired CO detector with battery backup must be on the floor where the furnace is installed, and a battery or hard-wired CO detector on each additional level. Detectors must meet NFPA 720 and ANSI/UL 2034 and be IAS certified. A metal or plastic sign at least 8 ft above grade, in line with the vent, must read GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS, with letters at least 1/2 inch. If the detectors cannot be installed at completion, the owner has 30 days, and a battery-operated CO detector must be installed in the meantime.
- Confirm a hard-wired CO detector with battery backup is on the furnace floor level.
- Confirm a CO detector is installed on each additional level served.
- Confirm the warning sign is mounted at least 8 ft above grade, in line with the vent terminal.
- Leave the installation manual and venting parts list with the appliance.
Applies to: Side-wall horizontally vented installations in Massachusetts
Source: 96V series installation instructions, p. 8. Written in our own words; check the manual for your exact model.
Model data card replacement
Furnace · 96V, 96MDV
The model data card is wire-tied to the furnace and should only be removed when the control is replaced. Replacement cards are model specific.
- Keep the card with the furnace unless the control is being replaced
- Install the replacement card with the matching model data at connector P6
Applies to: 96V and 96MDV communicating furnaces
Source: Rheem 96V installation instructions, p. 92. Written in our own words; check the manual for your exact model.
Natural gas at high altitude: derate
Furnace · 96V, 96MDV
No high altitude pressure switch changes are needed. Derate the input by 4% per thousand feet above 2,000 ft. Factory orifices are sized for 1100 BTU/ft3 at sea level; regional heating values may remove the need to change them except at extreme altitudes. Above 2,000 ft, follow local codes or NFGC/CSA B149.1.
- Derate the input 4% per 1,000 ft above 2,000 ft.
- Check the local gas heating value before changing orifices.
- Follow local codes, or NFGC / CSA B149.1 where no local code applies.
Applies to: Natural gas above 2,000 ft
Source: 96V series installation instructions, p. 80. Written in our own words; check the manual for your exact model.
Never bypass safety switches
Furnace · 96V, 96MDV
A safety switch that shuts the furnace down or makes it cycle intermittently points to a real hazard that a qualified technician must fix. Do not reset safety controls without correcting the cause and verifying safe operation.
- Do not jumper or remove any safety switch from the control circuit.
- Find and correct the cause before resetting any safety control.
- Replace safety control parts only with identical OEM parts.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 6. Written in our own words; check the manual for your exact model.
Never operate the system without filters
Furnace · 96V, 96MDV
Running without filters lets dust collect in the ducts and at the registers. Dust that reaches the heat exchanger chars and leaves soot on walls, ceilings and furnishings. Soot can also come from certain candles or untrimmed candlewicks.
- Install air filters before operating the system.
- Check that filters are in place at every startup.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 6. Written in our own words; check the manual for your exact model.
Never operate without filters or panels
Furnace · 96V, 96MDV
Running the system for long periods without filters lets dust collect in ducts and registers. Recirculated dust chars on the heat exchanger and soils the home. Replace all blower doors and compartment covers after servicing. Do not run the unit without all panels and doors in place.
- Install or confirm the filter before startup.
- Replace all blower doors and compartment covers after any service.
- Do not operate the furnace without all panels and doors secured.
Applies to: R96V furnace
Source: Rheem 96V installation manual, p. 106-107. Written in our own words; check the manual for your exact model.
Only current vent instructions apply
Furnace · 96V, 96MDV
Only the current vent instructions in this manual apply. All 90 Plus gas furnaces cannot be common-vented with any other appliance.
- Use the current vent instructions for the install.
- Do not common-vent this furnace with any other appliance.
Applies to: All 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 46. Written in our own words; check the manual for your exact model.
Overheating or gas supply that will not shut off
Furnace · 96V / 96MDV
If the furnace overheats or the gas supply does not shut off, close the manual gas valve for the appliance before shutting off electrical power. Otherwise an explosion or fire can result.
- Close the manual gas valve for the appliance first.
- Then shut off electrical power.
Applies to: 96V and 96MDV furnaces
Source: Rheem 96V series installation instructions, p. 83. Written in our own words; check the manual for your exact model.
Polypropylene vent products
Furnace · 96V, 96MDV
Centrotherm Innoflue and DuraventPolypro single-wall and flex products are approved only for single appliance use. Do not exceed listed lengths, diameters or elbows. Use only the terminations listed in Tables 5 and 6. Liners for B-vent or chimney are for non-direct venting only. These products are listed in Canada under ULC-S636.
- Confirm the product and termination are listed in Tables 5 or 6.
- Check the vent length and elbow count against Table 4.
- Follow the manufacturer's instructions for installation.
Applies to: Polypropylene vent systems
Source: 96V Series installation instructions, p. 50. Written in our own words; check the manual for your exact model.
Provide combustion and ventilation air
Furnace · 96V, 96MDV
Combustion and ventilation air must be supplied as required by the National Fuel Gas Code (US) or CSA B149.1 (Canada) and by the combustion and ventilation air section of these instructions.
- Verify combustion and ventilation air provisions before startup.
- Follow the combustion air section of the manual for the installation type.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 6. Written in our own words; check the manual for your exact model.
PVC solvent cement safety
Furnace · 96V, 96MDV
PVC and CPVC solvent cements and primers are highly flammable. Use good ventilation and do not assemble near a heat source or open flame.
- Ventilate the work area.
- Keep cement away from heat sources and open flames.
- Do not use cement that is curdled, lumpy or thick, and do not thin it.
Applies to: PVC vent joints
Source: 96V series installation instructions, p. 47. Written in our own words; check the manual for your exact model.
Read the fault display correctly
Furnace · 96V, 96MDV
Faults flash on for one second and off for half a second, and each fault is shown at least twice. Normal operating codes stay steady on. Check the display orientation first, because an upside-down display changes the reading.
- Confirm display orientation using dipswitch S1-1 before reading codes
- Note the code and any second code shown alternately with it
- Use the fault priority list to pick which fault shows when several are active
Applies to: 96V and 96MDV communicating furnaces
Source: Rheem 96V installation instructions, p. 92. Written in our own words; check the manual for your exact model.
Recommended direct vent installation
Furnace · 96V, 96MDV
Direct vent installations are recommended for better indoor air quality, added safety and performance. Non-direct installations must provide combustion air as set out in the National Fuel Gas Code and, in Canada, CSA B149.1.
- Use direct vent where practical.
- For non-direct, provide combustion air per NFPA 54 or CSA B149.1.
Applies to: Venting type selection
Source: 96V Series installation instructions, p. 52. Written in our own words; check the manual for your exact model.
Recommended elbow count
Furnace · 96V, 96MDV
Exceeding the recommended maximum number of elbows can cause nuisance pressure switch operation. Long sweep elbows are preferred. Mixing elbow types is allowed, but standard 90s and 45s used alone at the maximum count may cause nuisance outages.
- Count elbows against the maximum in the Table 4 elbow column for the model.
- Use long sweep 90s wherever possible.
Applies to: All vent runs
Source: 96V Series installation instructions, p. 48-49. Written in our own words; check the manual for your exact model.
Remove the shipping base pan from the top of the unit
Furnace · 96V, 96MDV
The solid metal base pan must be taken off the top of the furnace before it is installed. If it stays in the shipping position it can damage the furnace or other equipment.
- Remove the solid base panel from the top of the unit before setting the furnace.
Applies to: All 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 42. Written in our own words; check the manual for your exact model.
Residential garage installation height
Furnace · 96V, 96MDV
In a residential garage, the burners and ignition source must be at least 18 inches (450 mm) above the floor to reduce the risk of igniting flammable vapors. The furnace must also be located or protected from physical damage by vehicles.
- Confirm burners and ignition source are at least 18 in. (450 mm) above the floor.
- Locate or guard the furnace to prevent vehicle damage.
Applies to: Furnaces installed in residential garages
Source: 96V series installation instructions, p. 9. Written in our own words; check the manual for your exact model.
Seal and install a base plate when the factory return is unused
Furnace · 96V, 96MDV
If the factory return-air connection is not used, it must be sealed with a solid metal base plate. Otherwise carbon monoxide and other contaminants can be drawn into the conditioned air space. Factory base plates are sold as accessories; part numbers are in the furnace spec sheet.
- Install a solid metal base plate over the unused factory return connection.
- Seal the base plate and all return air duct connections.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 6. Written in our own words; check the manual for your exact model.
Seal ducts and equipment where fumes or CO can migrate
Furnace · 96V, 96MDV
Duct leaks can pull dirt, fumes, odors and carbon monoxide into the living space. Equipment or ducts in garages, storage areas or spaces with fuel-burning appliances must have all joints, seams and openings sealed.
- Seal all joints, seams and openings in equipment and ducts located in garages or storage areas.
- Seal equipment and ducts in spaces with water heaters or boilers to prevent depressurization and migration of combustion products.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 7. Written in our own words; check the manual for your exact model.
Seal return air ducts when supply ducts leave the furnace space
Furnace · 96V, 96MDV
If supply ducts carry air to areas outside the furnace space, the return air must also come through ducts sealed to the furnace casing and terminating outside that space.
- Seal return ducts to the furnace casing.
- Terminate return ducts outside the furnace space.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 6. Written in our own words; check the manual for your exact model.
Side return cut-out not allowed in downflow or horizontal
Furnace · 96V, 96MDV
In downflow and horizontal configurations, side return air cut-out is not permitted. Return connections must be airtight to keep toxic fumes and carbon monoxide out of the living space.
- Use the top return in downflow and the return-air end in horizontal.
- Seal the return connection airtight.
Applies to: Downflow and horizontal installations
Source: 96V series installation instructions, p. 43-44. Written in our own words; check the manual for your exact model.
Sidewall vent kit RXGY-G02
Furnace · 96V, 96MDV
The RXGY-G02 sidewall vent kit can be used for both direct and non-direct installations. Figure 20 shows a typical installation with a field supplied reducing coupling. Maximum 18 in of 2 in pipe is shown in the figure.
- Install the field supplied reducing coupling.
- Keep the 2 in pipe run within the 18 in figure maximum.
- Refer to the direct vent sidewall kit option for full directions.
Applies to: Non-direct and direct sidewall termination
Source: 96V Series installation instructions, p. 56. Written in our own words; check the manual for your exact model.
Soapy water for hose installation
Furnace · 96V, 96MDV
Soapy water makes the drain and vent hoses easier to slide onto fittings during conversion.
- Wet the fitting and the hose end with soapy water before pushing the hose on.
Applies to: Horizontal right with right vent conversion
Source: Rheem 96V series installation instructions, p. 29. Written in our own words; check the manual for your exact model.
Support the unit and combustible floor rules
Furnace · 96V, 96MDV
Support the unit when installed. It may be set on combustible wood flooring or on support brackets. Upflow furnaces are certified for combustible floors but must not be set directly on carpet, tile or other combustible material other than wood flooring.
- Support the furnace with brackets where needed.
- Do not place the upflow furnace directly on carpet, tile or non-wood combustible flooring.
Applies to: All installations
Source: 96V series installation instructions, p. 9-10. Written in our own words; check the manual for your exact model.
Suspected gas leak response
Furnace · 96V
If a gas leak is present or suspected, the technician must not search for the source. The leak must be reported and the area cleared.
- Do not try to find the leak source yourself.
- Do not light appliances, touch electrical switches or use a phone in the building.
- Leave the building and call the gas supplier from outside.
- Do not go back in until the gas supplier or fire department says it is safe.
Applies to: Gas leak situations on any gas appliance
Source: 96V series installation instructions, p. 69. Written in our own words; check the manual for your exact model.
Termination clearances from meters and appliances
Furnace · 96V, 96MDV
Keep the vent terminal at least 4 ft horizontally from electric meters, gas meters, regulators and relief equipment. Keep the furnace combustion air inlet at least 3 ft from the vent of any other gas or fuel appliance or clothes dryer, except for multi-venting.
- Measure horizontal distance from the vent terminal to meters, regulators and relief equipment.
- Measure distance from the combustion air inlet to nearby appliance vents and dryer vents.
Applies to: All venting
Source: 96V Series installation instructions, p. 51. Written in our own words; check the manual for your exact model.
Thermostat compatibility and wiring
Furnace · 96V, 96MDV
Use a thermostat that is not current-robbing. Use 24 volt control wire no smaller than 18 AWG. Run the leads into the blower compartment and connect to the low-voltage terminals shown on the wiring diagram.
- Use a thermostat that is not current-robbing.
- Use 24 volt wire of 18 AWG or larger.
- Connect to the low-voltage terminals as shown on the wiring diagram.
- Do not mount the thermostat on an outside wall or where drafts, pipes, ducts, sun or fireplace heat affect it.
Applies to: Thermostat wiring
Source: 96V series installation instructions, p. 77. Written in our own words; check the manual for your exact model.
Use soapy water on hose and tube assemblies
Furnace · 96V, 96MDV
Soapy water makes hoses and tubes slide onto fittings much more easily during drain assembly.
- Lubricate the hose ends and fittings with soapy water before pushing the hose or tube on.
Applies to: Condensate drain hose and tube assembly during conversions
Source: Rheem 96V installation manual, p. 18, 21. Written in our own words; check the manual for your exact model.
Vent combustion products outdoors only
Furnace · 96V, 96MDV
Combustion products must be discharged outdoors. Connect the furnace only to an approved vent system as specified in the vent pipe installation section.
- Connect the furnace only to an approved vent system.
- Follow the vent pipe installation section for pipe and termination requirements.
Applies to: 96V and 96MDV series furnaces
Source: 96V series installation instructions, p. 6. Written in our own words; check the manual for your exact model.
Vent pipe or heat exchanger leaks
Furnace · 96V, 96MDV
Holes in the vent pipe or heat exchanger can let toxic fumes into the home and cause carbon monoxide poisoning or death. The vent pipe or heat exchanger must be replaced if it leaks.
- Replace the vent pipe or heat exchanger if any leak is found.
Applies to: R96V furnace venting
Source: Rheem 96V installation manual, p. 107. Written in our own words; check the manual for your exact model.
Vent termination location guidelines
Furnace · 96V, 96MDV
Avoid terminating under a patio or deck, or behind obstructions. Do not terminate on the side with prevailing winter winds. Avoid areas near shrubs. Use a sleeve for brick or masonry penetrations. Use a corrosion-resistant backing plate behind the vent. Condensate can freeze on walls, eaves and nearby objects. Vent piping may run under a deck only if the termination is not under the deck, and it must be insulated.
- Select a location clear of decks, patios and obstructions.
- Avoid prevailing winter wind side.
- Install a sleeve through brick or masonry.
- Install a backing plate behind the vent.
- Insulate any vent run under a deck.
Applies to: All termination locations
Source: 96V Series installation instructions, p. 51. Written in our own words; check the manual for your exact model.
Vent termination safety warnings
Furnace · 96V, 96MDV
Do not use vent terminations that are not specified in these instructions. Screens of any kind on inlet or exhaust pipes are not permitted and void the warranty. Do not take combustion air from an attic with power ventilation.
- Use only specified terminations.
- Do not install screens on inlet or exhaust pipes.
- Do not draw combustion air from an attic that has power ventilation.
Applies to: All venting
Source: 96V Series installation instructions, p. 51, 55. Written in our own words; check the manual for your exact model.
Vertical and horizontal termination height
Furnace · 96V, 96MDV
Maintain at least 12 in (31 cm) above the highest anticipated snow level or grade, whichever is greater. Canadian installs must follow CSA B149.1-10, Sect. 8.14. Terminations more than 24 in above the roof penetration need additional support. Couplings are required on the exterior and optional on the interior. Reduce 3 in pipe to 2 in before penetrating the roof.
- Confirm termination height above grade and expected snow level.
- Add support for any vent run more than 24 in above the roof penetration.
- Install couplings on the exterior section.
- Reduce 3 in pipe to 2 in before the roof penetration.
Applies to: Non-direct and direct vent terminations
Source: 96V Series installation instructions, p. 55-56. Written in our own words; check the manual for your exact model.
Related
Same tips in your pocket
The HVACopedia app has these tips, every error code and the settings tables offline.
For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.