Rheem · Furnace · Ignition

Retry sequence when burners do not light or flame is not sensed

96V96MDV

What happens, in order

  1. On each heat call, the control checks that both pressure switches are open, then starts a high stage inducer pre-purge.
  2. After the 30-second pre-purge, the gas valve opens on high stage for an 8-second ignition trial.
  3. If the burners do not light or flame is not sensed, the control runs another ignition sequence.
  4. The control tries up to four times before entering a 1-hour lockout.

Timings and thresholds

ItemValue
Ignition attempts before lockoutup to 4
Lockout after failed attempts1 hour

Applies to: 96V and 96MDV furnaces

More Rheem furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem 96V series installation instructions, p. 83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.