Retry sequence when burners do not light or flame is not sensed
What happens, in order
- On each heat call, the control checks that both pressure switches are open, then starts a high stage inducer pre-purge.
- After the 30-second pre-purge, the gas valve opens on high stage for an 8-second ignition trial.
- If the burners do not light or flame is not sensed, the control runs another ignition sequence.
- The control tries up to four times before entering a 1-hour lockout.
Timings and thresholds
| Item | Value |
|---|---|
| Ignition attempts before lockout | up to 4 |
| Lockout after failed attempts | 1 hour |
Applies to: 96V and 96MDV furnaces
More Rheem furnace sequences
- Initial startup and lighting (communicating furnace) · Startup
- Gas heat call, direct spark ignition and retry · Ignition
- Gas heat call, hot surface ignition and retry · Ignition
- Gas heat call, ignition and retry (direct spark) · Ignition
- Heating ignition and blower sequence · Ignition
- Two-stage gas heat call, ignition on high fire and retry · Ignition
- Two-stage heat call, high-fire light-off and staging · Ignition
- Heating call sequence of operation (Honeywell integrated control, direct spark ignition) · Heating
Related
Rheem error codes · Rheem tips · Rheem parts · All Rheem sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Rheem 96V series installation instructions, p. 83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.