Rheem · Furnace · Ignition
Two-stage gas heat call, ignition on high fire and retry
What happens, in order
- Thermostat W closes (or a communicating thermostat sends a heat call); control checks that both pressure switches are open
- Inducer starts on high speed for pre-purge
- Low and high pressure switches close
- After the 30 s pre-purge the gas valve opens on high stage for the 8 s trial for ignition
- Spark stays on for up to 7 s
- Flame sensor must prove flame for 1 s at the 8 s mark
- If the burners do not light the control repeats the ignition sequence, up to 4 times, then goes to a 1 hour lockout
- 20 s after flame the gas valve moves to the stage the thermostat is asking for (no change if high stage is called); blower starts at the matching low or high heat speed
- Call for heat ends valve closes, flame goes out, inducer runs a 10 s post-purge and the pressure switch opens
- Main blower runs out the heat off delay set on the board
Timings and thresholds
| Item | Value |
|---|---|
| Pre-purge | 30 s, inducer on high |
| Trial for ignition | 8 s |
| Spark on after valve opens | up to 7 s |
| Stage select / blower start after flame | 20 s |
| Post-purge | 10 s |
| Ignition attempts | 4 |
| Lockout | 1 hour |
Applies to: Rheem R96V and 96V series two-stage condensing furnaces
Models
More Rheem furnace sequences
- Initial startup and lighting (communicating furnace) · Startup
- Gas heat call, direct spark ignition and retry · Ignition
- Gas heat call, hot surface ignition and retry · Ignition
- Gas heat call, ignition and retry (direct spark) · Ignition
- Heating ignition and blower sequence · Ignition
- Retry sequence when burners do not light or flame is not sensed · Ignition
- Two-stage heat call, high-fire light-off and staging · Ignition
- Heating call sequence of operation (Honeywell integrated control, direct spark ignition) · Heating
Related
Rheem error codes · Rheem tips · Rheem parts · All Rheem sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Rheem R96V (-)96V furnace installation 92-24161-124-08, Start-up and Sequence of Operations. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.