Rheem · Furnace · Ignition

Heating ignition and blower sequence

96V

What happens, in order

  1. Thermostat calls for heat and the inducer starts on low speed.
  2. Inducer runs a 30-second pre-purge at low speed.
  3. Igniter sparks and the gas valve is energized for each ignition trial.
  4. Furnace makes up to four ignition attempts.
  5. After burners light, the ECM blower starts on high heat about 15 to 20 seconds later.
  6. Furnace continues on low fire until the thermostat is satisfied or the heat call is removed.
  7. When the heat call ends, the inducer runs a post purge and shuts off after 90 seconds (plus slew).

Timings and thresholds

ItemValue
Inducer pre-purge at low speed30 seconds
Gas valve voltage per ignition trial7 seconds
Ignition attempts before lockout4 attempts
Lockout after failed attempts1 hour
ECM blower start on high heat after burner light15-20 seconds
Inducer post purge after heat call ends90 seconds plus slew
Inducer run before fault shutoff (codes 45, 46, 57)60 seconds, then off 5 minutes

Codes you may see during this

11 13 12 22 33 45 46 57 H

Applies to: 96V and 96MDV series 2-stage communicating furnaces

More Rheem furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: 96V series installation instructions, p. 121-122. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.