Rheem · Furnace

45 Low pressure switch open - inducer high speed

High severity Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)RGPE/RGLER96V/96MDV

What the control is telling you

Low pressure switch did not close (or opened) with the inducer on high speed. If not closed after 60 seconds of inducer run, a 5-minute soft lockout follows. RGPE/RGLE: Table 16 text LPC OPEN; meaning per 802P - verify on unit. Not stored back-to-back in the RGPE fault buffer.

Applies to: 802P/80MDP (802PA050-150); RGPE/RGLE 2-stage 80+

Likely causes

  • Inducer not running or weak
  • Loose, leaking, kinked or water-filled pressure hose
  • Blocked vent, improper vent size/length or too many elbows
  • Wind / severe downdraft
  • 802P: leaky inducer gasket
  • Faulty switch or wiring

Test and repair steps

  1. Check the inducer runs, its line voltage and wiring (RGPE/RGLE: J2 pin 1 to pin 4 for high output; check inducer capacitor).
  2. Check pressure switch hoses for cracks, kinks or water.
  3. Check vent and intake for blockage, too many elbows or excessive length; check for wind/downdraft.
  4. 802P check inducer gasket.
  5. Check switch wiring and contacts; verify switch state with a meter while the inducer runs.

Settings for these units

Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE

Cabinet widthInputBottom filterSide filterQuantity
17-1/2 in.50, 75 (000 Btu/h)15-3/4 x 25 in.15-3/4 x 25 in.1
21 in.75, 100 (000 Btu/h)19-1/4 x 25 in.15-3/4 x 25 in.1
24-1/2 in.125 (000 Btu/h)22-3/4 x 25 in.15-3/4 x 25 in.1

Use one filter location only - do not double-filter or filter the supply side.

21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.

Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)

Model sizeCabinet width (A)Left sideRight sideBackTopFrontVent
050 (5)14 in.0 in.4 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
075 (7)17-1/2 in.0 in.3 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
100 (10)21 in.0 in.00 in.1 in.3 in.6 in. (note 3)
125 (12)24-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)
150 (15)24-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)

Note 2: right side may be 0 in. with type B vent.

Note 3: vent clearance may be 1 in. with type B vent.

Models that show this code

16 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), RGPE/RGLE, R96V/96MDV

96MDV115D50AR802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSARGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR

Other codes on the same units

  • 26 Line and neutral reversed
  • 30 Open fuse
  • 33 Rollout switch (MRLC) open
  • 44 Low pressure switch closed (stuck)
  • 46 Low pressure switch open - inducer low speed
  • 55 Pressure switch stuck closed
  • 57 Pressure switch stuck open
  • 58 Water sense circuit open

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40-41, 48, 51; RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.