Rheem · Furnace
46 Low pressure switch open - inducer low speed
What the control is telling you
Low pressure switch opened while the inducer was on low speed (low-fire operation). RGPE/RGLE: Table 16 text LPC OPEN; meaning per 802P - verify on unit. Not stored back-to-back in the RGPE fault buffer.
Applies to: 802P/80MDP (802PA050-150); RGPE/RGLE 2-stage 80+
Likely causes
- Weak inducer at low speed
- Hose leak or water in hose
- Partial vent blockage
- Wind
Test and repair steps
- Check inducer operation and wiring; RGPE/RGLE: check inducer low speed and 115 VAC on P2, replace inducer if weak.
- Check hoses and switch for moisture.
- Check vent for blockage and wind effects.
- Check switch wiring.
Settings for these units
Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
| Cabinet width | Input | Bottom filter | Side filter | Quantity |
|---|---|---|---|---|
| 17-1/2 in. | 50, 75 (000 Btu/h) | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 21 in. | 75, 100 (000 Btu/h) | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 24-1/2 in. | 125 (000 Btu/h) | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
Use one filter location only - do not double-filter or filter the supply side.
21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.
Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
| Model size | Cabinet width (A) | Left side | Right side | Back | Top | Front | Vent |
|---|---|---|---|---|---|---|---|
| 050 (5) | 14 in. | 0 in. | 4 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| 075 (7) | 17-1/2 in. | 0 in. | 3 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| 100 (10) | 21 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| 125 (12) | 24-1/2 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| 150 (15) | 24-1/2 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
Note 2: right side may be 0 in. with type B vent.
Note 3: vent clearance may be 1 in. with type B vent.
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Models that show this code
16 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), RGPE/RGLE, R96V/96MDV
Other codes on the same units
Sequence of operation
What the unit does around this code, step by step.
- Heating ignition and blower sequence · Ignition
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40, 51; RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.