Rheem · Furnace

59 Water sensed / blocked drain

High severity R95PR96V/96MDV

What the control is telling you

Condensate has reached the electronic water level sensor and gas heat is shut down. If it happens again within 5 minutes of the next attempt in the same heat call, the control enters a 1-hour lockout (59 and 10 alternate). On first start-up or after summer the dry trap may cause this up to 4 times while it primes.

Applies to: R95P (R95PA040-115)

Likely causes

  • Blocked condensate drain, trap or vent
  • Dry trap on first firing (self-priming)
  • Condensate line tied into a common drain with an A/C coil located below
  • Freezing drain line

Test and repair steps

  1. Check the condensate trap, drain line and drain vent for blockage; clear and flush.
  2. On a new install or first firing of the season allow the trap to prime (may repeat up to 4 times, more likely on horizontal installs).
  3. Make sure the furnace drain is not tied into a common drain with an A/C coil below the furnace.
  4. Check heat tape if the drain runs through unheated space.
  5. Check the drain vent riser height option chosen (overflow vs. shutoff).
  6. Check the water sensor and its wiring if the drain is clear.

Settings for these units

Clearance to combustibles (all models) · R95P

LocationMinimum clearance
Left side0 in.
Right side0 in.
Back0 in.
Top1 in.
Front2 in.
Vent0 in.
Service (front)24 in. recommended

Same values for R95PA040 through 115.

Column order read from a rotated drawing header - confirm on the furnace clearance label.

Models that show this code

7 models in R95P, R96V/96MDV

96MDV115D50AR95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSA

Other codes on the same units

  • 46 Low pressure switch open - inducer low speed
  • 55 Pressure switch stuck closed
  • 57 Pressure switch stuck open
  • 58 Water sense circuit open
  • 60 Blower fault - running (BLWR FLT-RUN)
  • 66 Blower overspeed (BLOWER OVRSPEED)
  • 68 No blower communication (NO BLWR COMM)
  • 82 Supply air sensor fault (SA SENSOR FLT)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: R95P: Diagnostics and Fault Codes table, p.87 (PDF p.91). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.