Rheem · Furnace
82 Supply air sensor fault (SA SENSOR FLT)
What the control is telling you
Supply air temperature sensor fault. Not stored back-to-back in the buffer.
Applies to: RGPE/RGLE 2-stage 80+
Likely causes
- Sensor missing/unplugged/failed
- Sensor input enabled with no sensor installed
Test and repair steps
- Check the supply air sensor is installed and connected.
- If no sensor is used, set the supply air sensor input OFF in the furnace setup user menu (factory default ON) - this stops code 82.
- For dual-fuel operation the sensor MUST be installed and enabled.
- Check sensor wiring to the IFC.
Settings for these units
- Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: RGPE/RGLE: Table 16 p.49 / Table 20; user menus p.55. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.