Rheem · Furnace

60 Blower fault - running (BLWR FLT-RUN)

Medium severity RGPE/RGLE

What the control is telling you

ECM blower reports a fault but is still running.

Applies to: RGPE/RGLE 2-stage 80+

Likely causes

  • ECM motor problem
  • High static / restriction
  • Wiring

Test and repair steps

  1. Check all connections between IFC and ECM motor.
  2. Check 24 V at the ECM low-voltage connector, pins 1 and 4.
  3. Check line voltage (115 VAC) to the motor.
  4. Check the PFC choke and its wiring.
  5. Check dipswitch settings.
  6. Check the blower wheel is free and clean.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.