Rheem · Furnace
84 Outdoor air sensor fault
What the control is telling you
The optional outdoor air sensor on T4 (10K NTC) read open or shorted after it had been seen as valid in this power cycle. Low-level fault: heating continues. It clears itself three minutes after it is detected and is only logged once.
Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces
Likely causes
- Outdoor sensor wire broken or shorted
- Sensor unplugged after power-up
- Failed sensor
Test and repair steps
- Check the OAT sensor wiring at terminal block T4.
- Measure the sensor a 10K NTC thermistor, about 10,000 ohm at 77 F.
- Replace the sensor if it reads open or shorted; or remove it completely and cycle power if it is not wanted.
Settings for these units
- Filter sizes · Rheem RGRM/RGTM 90 Plus
- Filter sizes (Table 12) · Rheem 90RJ/90TJ 90 Plus
- Minimum clearance to combustibles · Rheem 90RJ/90TJ 90 Plus
- Filter sizes (Table 9) · Rheem (-)GRC/(-)GTC 90 Plus
- Minimum clearance to combustibles · Rheem (-)GRC/(-)GTC 90 Plus
- Clearance to combustibles (all models) · R95P
Models that show this code
1 model in R96V/96MDV
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, 16 Supply and outdoor air temperature sensor inputs p.97. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.