Rheem · Furnace
30 Open fuse
What the control is telling you
The 24 V fuse on the furnace control has blown, usually because a low-voltage wire is shorted to common or ground. Nothing else runs while this code is up.
Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces
Likely causes
- 24 VAC short to ground or common on the thermostat / low-voltage wiring
- Pinched thermostat cable
- Miswired accessory or condenser
Test and repair steps
- Find and repair the short on the 24 V side (thermostat wires, condenser wiring, humidifier or EAC wiring).
- Replace the fuse with the same rating.
- If the fuse blows again, isolate circuits one at a time until the shorted branch is found.
Settings for these units
- Filter sizes · Rheem RGRM/RGTM 90 Plus
- Filter sizes (Table 12) · Rheem 90RJ/90TJ 90 Plus
- Minimum clearance to combustibles · Rheem 90RJ/90TJ 90 Plus
- Filter sizes (Table 9) · Rheem (-)GRC/(-)GTC 90 Plus
- Minimum clearance to combustibles · Rheem (-)GRC/(-)GTC 90 Plus
- Clearance to combustibles (all models) · R95P
Models that show this code
1 model in R96V/96MDV
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, Table 20 p.116. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.