Rheem · Furnace

30 Open fuse

Critical severity R96V/96MDV

What the control is telling you

The 24 V fuse on the furnace control has blown, usually because a low-voltage wire is shorted to common or ground. Nothing else runs while this code is up.

Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces

Likely causes

  • 24 VAC short to ground or common on the thermostat / low-voltage wiring
  • Pinched thermostat cable
  • Miswired accessory or condenser

Test and repair steps

  1. Find and repair the short on the 24 V side (thermostat wires, condenser wiring, humidifier or EAC wiring).
  2. Replace the fuse with the same rating.
  3. If the fuse blows again, isolate circuits one at a time until the shorted branch is found.

Settings for these units

Models that show this code

1 model in R96V/96MDV

96MDV115D50A

Other codes on the same units

  • 14 Unexpected flame
  • 22 Main limit open
  • 23 HALC limit open (HALC LIMIT OPEN)
  • 26 Line and neutral reversed
  • 33 Rollout switch (MRLC) open
  • 44 Low pressure switch closed (stuck)
  • 45 Low pressure switch open - inducer high speed
  • 46 Low pressure switch open - inducer low speed

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, Table 20 p.116. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.