Rheem · Furnace

14 Unexpected flame

Critical severity Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)R95PRGPE/RGLER96V/96MDV

What the control is telling you

Flame sensed when the gas valve should be closed. 802P/R95P: amber flame LED blinks rapidly; 1-hour lockout (14 and 10 alternate) that starts once flame is gone. RGPE/RGLE: thermostat also shows Call For Service / CHECK FURNACE.

Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+

Likely causes

  • Gas valve leaking through or stuck open
  • Gas valve relay on IFC stuck closed
  • Voltage fed to the gas valve by miswiring
  • Heat call (W) not fully removed

Test and repair steps

  1. Warning: If flame or gas will not shut off, close the manual gas valve to the appliance BEFORE shutting off electrical power.
  2. Remove the heat call and confirm W to C = 0 V at the IFC.
  3. Check for voltage at the gas valve with no call; if present, check wiring and the IFC gas valve relay (replace IFC if stuck).
  4. If no voltage but flame remains, replace the gas valve.
  5. Do not reset until the cause is found.

Settings for these units

Clearance to combustibles (all models) · R95P

LocationMinimum clearance
Left side0 in.
Right side0 in.
Back0 in.
Top1 in.
Front2 in.
Vent0 in.
Service (front)24 in. recommended

Same values for R95PA040 through 115.

Column order read from a rotated drawing header - confirm on the furnace clearance label.

Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE

Cabinet widthInputBottom filterSide filterQuantity
17-1/2 in.50, 75 (000 Btu/h)15-3/4 x 25 in.15-3/4 x 25 in.1
21 in.75, 100 (000 Btu/h)19-1/4 x 25 in.15-3/4 x 25 in.1
24-1/2 in.125 (000 Btu/h)22-3/4 x 25 in.15-3/4 x 25 in.1

Use one filter location only - do not double-filter or filter the supply side.

21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.

Models that show this code

22 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P, RGPE/RGLE, R96V/96MDV

96MDV115D50AR802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSAR95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSARGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR

Other codes on the same units

  • 10 One-hour lockout
  • 11 Failed ignition
  • 12 Low flame sense
  • 13 Flame lost
  • 20 Twinning fault
  • 22 Main limit open
  • 23 HALC limit open (HALC LIMIT OPEN)
  • 26 Line and neutral reversed

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40-41, 51; R95P: Diagnostics and Fault Codes table, p.87 (PDF p.91); RGPE/RGLE: Table 16 p.49 / Table 20. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.