Rheem · Furnace · Heating
Heating call sequence of operation (Honeywell integrated control, direct spark ignition)
What happens, in order
- On a heat call (W or communicating call), the control checks that both pressure switches are open.
- The inducer starts a pre-purge at high stage.
- The air proving (negative pressure) switches, low and high, close.
- After the 30-second pre-purge, the gas valve opens on high stage for an 8-second ignition trial.
- The spark igniter fires to light the burners and stays on for up to 7 seconds after the gas valve opens.
- Eight seconds after the gas valve opens, the flame sensor must prove flame for one second using flame rectification.
- Twenty seconds after flame is sensed, the gas valve goes to the thermostat demand (low or high). The main blower starts at low or high heat speed to match the demand.
- When the heat call ends, the gas valve closes and flame goes out. The inducer runs a 10-second post-purge, then stops. The negative pressure switch opens.
- The main blower runs until its off timing on the integrated control ends.
Timings and thresholds
| Item | Value |
|---|---|
| Pre-purge at high stage | 30 seconds |
| Ignition trial on high stage | 8 seconds |
| Igniter on after gas valve opens | up to 7 seconds |
| Flame proof after gas valve opens | 8 seconds, proven for 1 second |
| Gas valve to thermostat demand after flame sensed | 20 seconds |
| Inducer post-purge | 10 seconds |
Applies to: 96V and 96MDV communicating furnaces
More Rheem furnace sequences
- Initial startup and lighting (communicating furnace) · Startup
- Gas heat call, direct spark ignition and retry · Ignition
- Gas heat call, hot surface ignition and retry · Ignition
- Gas heat call, ignition and retry (direct spark) · Ignition
- Heating ignition and blower sequence · Ignition
- Retry sequence when burners do not light or flame is not sensed · Ignition
- Two-stage gas heat call, ignition on high fire and retry · Ignition
- Two-stage heat call, high-fire light-off and staging · Ignition
Related
Rheem error codes · Rheem tips · Rheem parts · All Rheem sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Rheem 96V series installation instructions, p. 83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.