Rheem · Furnace · Heating

Heating call sequence of operation (Honeywell integrated control, direct spark ignition)

96V96MDV

What happens, in order

  1. On a heat call (W or communicating call), the control checks that both pressure switches are open.
  2. The inducer starts a pre-purge at high stage.
  3. The air proving (negative pressure) switches, low and high, close.
  4. After the 30-second pre-purge, the gas valve opens on high stage for an 8-second ignition trial.
  5. The spark igniter fires to light the burners and stays on for up to 7 seconds after the gas valve opens.
  6. Eight seconds after the gas valve opens, the flame sensor must prove flame for one second using flame rectification.
  7. Twenty seconds after flame is sensed, the gas valve goes to the thermostat demand (low or high). The main blower starts at low or high heat speed to match the demand.
  8. When the heat call ends, the gas valve closes and flame goes out. The inducer runs a 10-second post-purge, then stops. The negative pressure switch opens.
  9. The main blower runs until its off timing on the integrated control ends.

Timings and thresholds

ItemValue
Pre-purge at high stage30 seconds
Ignition trial on high stage8 seconds
Igniter on after gas valve opensup to 7 seconds
Flame proof after gas valve opens8 seconds, proven for 1 second
Gas valve to thermostat demand after flame sensed20 seconds
Inducer post-purge10 seconds

Applies to: 96V and 96MDV communicating furnaces

More Rheem furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem 96V series installation instructions, p. 83. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.