Rheem · Furnace · Ignition
Two-stage heat call, high-fire light-off and staging
What happens, in order
- R and W close; control runs a self-check and verifies the pressure switch contacts are open
- Inducer starts on high until the low pressure switch closes (60 s maximum)
- After a 30 s pre-purge the spark igniter energizes and the high fire valve opens
- Remote flame sensor must prove the flame
- If no flame the valve closes, igniter goes off and the process repeats, up to 4 times
- After the 4th failure the furnace goes into a 1 hour soft lockout; reset by breaking power 5 to 10 s at the thermostat or unit disconnect
- Once flame is proven the inducer and gas valve drop to low fire right away
- Main blower starts 20 s after flame on low heat speed
- A single-stage thermostat moves the furnace to high heat after the timer set by jumper P7 (5 or 12 minutes)
- If flame is lost the valve closes, the inducer finishes its post-purge and the cycle restarts; 5 flame losses in one call for heat lead to lockout
Timings and thresholds
| Item | Value |
|---|---|
| Pre-purge | 30 s |
| Pressure switch proving | 60 s max |
| Blower on delay | 20 s after flame |
| Post-purge | 10 s |
| Ignition attempts | 4 |
| Lockout | 1 hour |
| Single-stage low-to-high timer (P7) | 5 or 12 min |
Codes you may see during this
Status LED: 1, 2, 3, 4, 6 blinks
Applies to: Rheem Nature Air RGRM-04 MAES
Models
More Rheem furnace sequences
- Initial startup and lighting (communicating furnace) · Startup
- Gas heat call, direct spark ignition and retry · Ignition
- Gas heat call, hot surface ignition and retry · Ignition
- Gas heat call, ignition and retry (direct spark) · Ignition
- Heating ignition and blower sequence · Ignition
- Retry sequence when burners do not light or flame is not sensed · Ignition
- Two-stage gas heat call, ignition on high fire and retry · Ignition
- Heating call sequence of operation (Honeywell integrated control, direct spark ignition) · Heating
Related
Rheem error codes · Rheem tips · Rheem parts · All Rheem sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Nature Air RGRM-04 MAES installation manual, Sequence of Operation; Status LED table. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.