Gas heat call, hot surface ignition and retry
What happens, in order
- Thermostat W closes and the inducer starts pre-purge
- Pressure switch closes
- 5 s after the pressure switch closes the hot surface igniter heats for 30 s to full temperature; inducer runs for the whole heat cycle
- After the 30 s warm-up the gas valve opens for the 8 s trial for ignition
- Igniter stays on for the first 7 s after the valve opens
- Flame sensor must prove flame for 1 s at the 8 s mark
- Main blower starts about 20 s after burners light
- If no flame valve closes, igniter off, 10 s post-purge, then control confirms the pressure switch reopened
- Next try 30 s pre-purge, 30 s igniter warm-up, valve opens, up to 8 s to find flame
- After a failed second try the control runs the blower and inducer together for 3 minutes (self-healing) before the next attempt
- Up to 4 attempts (first try plus 3 retries); 2nd and 4th attempts use a 30 s pre-purge plus 30 s warm-up to protect the igniter
- After the 4th failure the control enters a 1 hour soft lockout and ignores the W call
- After the hour the whole sequence repeats until flame is proven or the call ends
- Reset lockout by cutting power at the unit or thermostat for 5 to 10 s, or by dropping and re-making the W call
- Call for heat ends valve closes, inducer runs 10 s post-purge, blower runs out the heat off delay
Timings and thresholds
| Item | Value |
|---|---|
| Prepurge | 35 s on first try |
| Igniter warm-up | 30 s |
| Trial for ignition | 8 s |
| Flame proving | 1 s, checked at 8 s |
| Blower on delay | about 20 s after ignition |
| Post-purge | 10 s |
| Self-healing blower/inducer run | 3 min |
| Ignition attempts | 4 |
| Lockout | 1 hour |
Applies to: Rheem 90RJ series; Rheem GRC series
Models
More Rheem furnace sequences
- Initial startup and lighting (communicating furnace) · Startup
- Gas heat call, direct spark ignition and retry · Ignition
- Gas heat call, ignition and retry (direct spark) · Ignition
- Heating ignition and blower sequence · Ignition
- Retry sequence when burners do not light or flame is not sensed · Ignition
- Two-stage gas heat call, ignition on high fire and retry · Ignition
- Two-stage heat call, high-fire light-off and staging · Ignition
- Heating call sequence of operation (Honeywell integrated control, direct spark ignition) · Heating
Related
Rheem error codes · Rheem tips · Rheem parts · All Rheem sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Rheem 90RJ installation manual, Sequence of Operation; Rheem (-)GRC installation manual, Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.