Rheem · Furnace · Ignition

Gas heat call, direct spark ignition and retry

UT control, direct spark (90RJ variant)

What happens, in order

  1. Thermostat contacts close and the inducer starts pre-purge
  2. Air proving pressure switch closes
  3. 30 s after the switch closes the spark igniter energizes; inducer runs all through the heat cycle
  4. Gas valve opens for the 8 s trial for ignition
  5. Flame sensor must prove flame for 1 s
  6. Main blower starts 20 s after burners light
  7. If the burners do not light valve closes, igniter off, 10 s post-purge, control checks the pressure switch reopened
  8. Next try 30 s pre-purge, igniter on and valve opens
  9. After the second miss the blower and inducer run together for 3 minutes before the next attempt
  10. Up to 4 attempts, then a 1 hour soft lockout; reset by cutting power for 5 to 10 s or by dropping and re-making the call for heat

Timings and thresholds

ItemValue
Pre-purge30 s
Trial for ignition8 s
Blower on delay20 s after ignition
Post-purge10 s
Self-healing blower/inducer run3 min
Ignition attempts4
Lockout1 hour

Applies to: Rheem 90RJ series (direct spark control)

Models

90RJ series

More Rheem furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem 90RJ installation manual, Sequence of Operation (UT electronic controls, direct spark ignition). Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.