Rheem · Furnace · Ignition
Failed ignition and flame loss retry
What happens, in order
- After a failed ignition, the control shows fault 11 and the inducer runs a post-purge.
- The control makes another ignition attempt.
- After four consecutive failed attempts, the control enters one-hour lockout and shows 10 and 11 alternately.
- After flame loss, the blower runs its off-delay and the inducer runs a post-purge.
- The control removes the fault code and attempts ignition again.
Timings and thresholds
| Item | Value |
|---|---|
| Inducer post-purge after failed ignition or flame loss | 20 seconds |
| Blower off-delay after flame loss | 90 seconds |
| Main limit open before dead blower fault | more than 150 seconds |
Codes you may see during this
Applies to: R96V furnace gas heat
More Rheem furnace sequences
- Condensate trap priming cycle · Startup
- Initial startup and lighting (communicating furnace) · Startup
- Gas heat call, direct spark ignition and retry · Ignition
- Gas heat call, hot surface ignition and retry · Ignition
- Gas heat call, ignition and retry (direct spark) · Ignition
- Heating ignition and blower sequence · Ignition
- Retry sequence when burners do not light or flame is not sensed · Ignition
- Two-stage gas heat call, ignition on high fire and retry · Ignition
Related
Rheem error codes · Rheem tips · Rheem parts · All Rheem sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Rheem 96V installation manual, p. 110-111. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.