Rheem · Furnace · Ignition

Failed ignition and flame loss retry

96V96MDV

What happens, in order

  1. After a failed ignition, the control shows fault 11 and the inducer runs a post-purge.
  2. The control makes another ignition attempt.
  3. After four consecutive failed attempts, the control enters one-hour lockout and shows 10 and 11 alternately.
  4. After flame loss, the blower runs its off-delay and the inducer runs a post-purge.
  5. The control removes the fault code and attempts ignition again.

Timings and thresholds

ItemValue
Inducer post-purge after failed ignition or flame loss20 seconds
Blower off-delay after flame loss90 seconds
Main limit open before dead blower faultmore than 150 seconds

Codes you may see during this

10 11 13

Applies to: R96V furnace gas heat

More Rheem furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem 96V installation manual, p. 110-111. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.