Rheem · Furnace · Startup
Condensate trap priming cycle
What happens, in order
- On the first heat attempt, the trap is dry and the inducer pulls air through it.
- Condensate collects in the collector box, held there by the negative pressure while the inducer runs.
- When the water reaches the electronic water level sensor, the heat attempt ends.
- The inducer shuts off after post purge, which releases the negative pressure.
- The water falls into the trap and primes it. Up to four attempts may be needed.
Applies to: Condensate trap, first start or after a long off period
More Rheem furnace sequences
- Initial startup and lighting (communicating furnace) · Startup
- Failed ignition and flame loss retry · Ignition
- Gas heat call, direct spark ignition and retry · Ignition
- Gas heat call, hot surface ignition and retry · Ignition
- Gas heat call, ignition and retry (direct spark) · Ignition
- Heating ignition and blower sequence · Ignition
- Retry sequence when burners do not light or flame is not sensed · Ignition
- Two-stage gas heat call, ignition on high fire and retry · Ignition
Related
Rheem error codes · Rheem tips · Rheem parts · All Rheem sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: 96V series installation instructions, p. 67. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.