Rheem · Furnace

dF Defrost in progress (dual fuel)

Normal status RGPE/RGLER96V/96MDV

What the display is showing

In a dual-fuel system the furnace display shows dF while the heat pump is in a defrost cycle. With the supply air sensor fitted, gas heat is allowed only while outlet air stays under 110 F; it is cut off above that and comes back on when supply air falls to 95 F. All other codes apply as usual.

Applies to: Rheem/Ruud RGPE / RGLE modulating furnaces

Settings for these units

Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE

Cabinet widthInputBottom filterSide filterQuantity
17-1/2 in.50, 75 (000 Btu/h)15-3/4 x 25 in.15-3/4 x 25 in.1
21 in.75, 100 (000 Btu/h)19-1/4 x 25 in.15-3/4 x 25 in.1
24-1/2 in.125 (000 Btu/h)22-3/4 x 25 in.15-3/4 x 25 in.1

Use one filter location only - do not double-filter or filter the supply side.

21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.

Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE

Model sizeCabinet width (A)Left sideRight sideBackTopFrontVent
RGPE upflow/horizontal 0517-1/2 in.0 in.3 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
RGPE upflow/horizontal 07(A)17-1/2 in.0 in.3 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
RGPE upflow/horizontal 07(B), 1021 in.0 in.00 in.1 in.3 in.6 in. (note 3)
RGPE upflow/horizontal 1224-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)
RGLE downflow 07(A)17-1/2 in.0 in.3 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
RGLE downflow 07(B), 1021 in.0 in.00 in.1 in.3 in.6 in. (note 3)
RGLE downflow 1224-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)

Note 2: right side may be 0 in. with type B vent.

Note 3: vent clearance may be 1 in. with type B vent.

Models that show this code

11 models in RGPE/RGLE, R96V/96MDV

96MDV115D50ARGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: RGPE Dual-fuel operation in communicating mode, p.56. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.