Rheem · Furnace

h (lowercase) Low-fire gas heat on

Normal status Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)RGPE/RGLER96V/96MDV

What the display is showing

A lowercase h on the display means the furnace is running its low gas heat stage. On RGPE/RGLE the troubleshooting chart accepts either H or h as normal while a 24 V thermostat calls for heat. A flashing h on RGPE/RGLE is a different thing (calibration, listed separately).

Applies to: Rheem/Ruud (-)802P / 80MDP 80% two-stage furnaces; Rheem/Ruud RGPE / RGLE modulating furnaces

Settings for these units

Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE

Cabinet widthInputBottom filterSide filterQuantity
17-1/2 in.50, 75 (000 Btu/h)15-3/4 x 25 in.15-3/4 x 25 in.1
21 in.75, 100 (000 Btu/h)19-1/4 x 25 in.15-3/4 x 25 in.1
24-1/2 in.125 (000 Btu/h)22-3/4 x 25 in.15-3/4 x 25 in.1

Use one filter location only - do not double-filter or filter the supply side.

21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.

Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)

Model sizeCabinet width (A)Left sideRight sideBackTopFrontVent
050 (5)14 in.0 in.4 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
075 (7)17-1/2 in.0 in.3 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
100 (10)21 in.0 in.00 in.1 in.3 in.6 in. (note 3)
125 (12)24-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)
150 (15)24-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)

Note 2: right side may be 0 in. with type B vent.

Note 3: vent clearance may be 1 in. with type B vent.

Models that show this code

16 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), RGPE/RGLE, R96V/96MDV

96MDV115D50AR802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSARGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem (-)802PA Installation Instructions, Diagnostics and Fault Codes (UT 1028-928 control), pp.40-41; RGPE Troubleshooting chart (Figure 45, p.64). Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.