Rheem · Furnace
h (lowercase) Low-fire gas heat on
What the display is showing
A lowercase h on the display means the furnace is running its low gas heat stage. On RGPE/RGLE the troubleshooting chart accepts either H or h as normal while a 24 V thermostat calls for heat. A flashing h on RGPE/RGLE is a different thing (calibration, listed separately).
Applies to: Rheem/Ruud (-)802P / 80MDP 80% two-stage furnaces; Rheem/Ruud RGPE / RGLE modulating furnaces
Settings for these units
Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
| Cabinet width | Input | Bottom filter | Side filter | Quantity |
|---|---|---|---|---|
| 17-1/2 in. | 50, 75 (000 Btu/h) | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 21 in. | 75, 100 (000 Btu/h) | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 24-1/2 in. | 125 (000 Btu/h) | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
Use one filter location only - do not double-filter or filter the supply side.
21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.
Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
| Model size | Cabinet width (A) | Left side | Right side | Back | Top | Front | Vent |
|---|---|---|---|---|---|---|---|
| 050 (5) | 14 in. | 0 in. | 4 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| 075 (7) | 17-1/2 in. | 0 in. | 3 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| 100 (10) | 21 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| 125 (12) | 24-1/2 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| 150 (15) | 24-1/2 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
Note 2: right side may be 0 in. with type B vent.
Note 3: vent clearance may be 1 in. with type B vent.
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Models that show this code
27 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), RGPE/RGLE, R96V/96MDV
Other codes on the same units
- Top and bottom bars (right digit) Fault history cleared confirmation
- UI Unit input readout (pushbutton status menu)
- UNIT INFO menu Furnace user menu - UNIT INFO
- cd / Cd Dehumidification cooling
- dF Defrost in progress (dual fuel)
- h flashing Calibrating (CALIBRATE-NO V)
- r Lockout indicator
- tr Temperature rise readout (pushbutton status menu)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)802PA Installation Instructions, Diagnostics and Fault Codes (UT 1028-928 control), pp.40-41; RGPE Troubleshooting chart (Figure 45, p.64). Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.