Rheem · Furnace
d4 No valid model data on memory card
What the control is telling you
The memory card in P6 is blank, corrupt, or not present. A valid copy of model data is still stored in the furnace microprocessor, so the furnace keeps running and d4 shows only in standby.
Applies to: R96V memory card
Likely causes
- No memory card installed
- Card corrupted or cannot be read
- Card lost or disconnected when the furnace control was replaced
Test and repair steps
- Remove the memory card and check it is seated in P6.
- Install the original card from the furnace or the correct replacement card.
- Never use a card from another furnace or component such as a condenser or air handler. This can cause blower operation problems and possible heat exchanger damage.
- When replacing the control, move the memory card to the new control.
Settings for these units
- Filter sizes · Rheem RGRM/RGTM 90 Plus
- Filter sizes (Table 12) · Rheem 90RJ/90TJ 90 Plus
- Minimum clearance to combustibles · Rheem 90RJ/90TJ 90 Plus
- Filter sizes (Table 9) · Rheem (-)GRC/(-)GTC 90 Plus
- Minimum clearance to combustibles · Rheem (-)GRC/(-)GTC 90 Plus
- Clearance to combustibles (all models) · R95P
Models that show this code
12 models in 96V, 96MDV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem 96V installation manual, p. 109. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.