Rheem · Furnace

Fault recall Power-up replay of the last three faults

Menu / mode display Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)R95P

What the display is showing

After the furnace control is power-cycled, the seven-segment display replays the three most recent faults younger than one week, newest first, as a diagnostic aid. Faults older than a week drop out of the memory by themselves. Seeing an old code here does not mean the fault is active now.

Applies to: Rheem/Ruud (-)802P / 80MDP 80% two-stage furnaces; R95P furnaces

What to do

  1. Switch the furnace power off and back on (power reset).
  2. Watch the seven-segment display up to three stored faults flash one after another, newest first.
  3. To wipe the history, flip the fault-clear DIP switch (SW8 on the 802P control, SW4 on R95P) six times in a row, alternating, starting from either position, all inside 30 seconds, then put the switch back where it was.

Settings for these units

Clearance to combustibles (all models) · R95P

LocationMinimum clearance
Left side0 in.
Right side0 in.
Back0 in.
Top1 in.
Front2 in.
Vent0 in.
Service (front)24 in. recommended

Same values for R95PA040 through 115.

Column order read from a rotated drawing header - confirm on the furnace clearance label.

Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)

Model sizeCabinet width (A)Left sideRight sideBackTopFrontVent
050 (5)14 in.0 in.4 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
075 (7)17-1/2 in.0 in.3 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
100 (10)21 in.0 in.00 in.1 in.3 in.6 in. (note 3)
125 (12)24-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)
150 (15)24-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)

Note 2: right side may be 0 in. with type B vent.

Note 3: vent clearance may be 1 in. with type B vent.

Models that show this code

11 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P

R802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSAR95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem (-)802PA Installation Instructions, Diagnostics and Fault Codes (UT 1028-928 control), pp.40-41; Flame Status LED and Fault Recall (pp.43-44); R95P Fault Recall (printed p.90). Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.