Rheem · Furnace

F Continuous fan on

Normal status Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)R95PR96V/96MDV

What the display is showing

F on the display means the blower is running continuously from a fan-only call (thermostat fan switch on). Normal. A lockout fault code replaces the F while the control is locked out.

Applies to: Rheem/Ruud (-)802P / 80MDP 80% two-stage furnaces; R95P furnaces

Settings for these units

Clearance to combustibles (all models) · R95P

LocationMinimum clearance
Left side0 in.
Right side0 in.
Back0 in.
Top1 in.
Front2 in.
Vent0 in.
Service (front)24 in. recommended

Same values for R95PA040 through 115.

Column order read from a rotated drawing header - confirm on the furnace clearance label.

Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)

Model sizeCabinet width (A)Left sideRight sideBackTopFrontVent
050 (5)14 in.0 in.4 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
075 (7)17-1/2 in.0 in.3 in. (note 2)0 in.1 in.3 in.6 in. (note 3)
100 (10)21 in.0 in.00 in.1 in.3 in.6 in. (note 3)
125 (12)24-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)
150 (15)24-1/2 in.0 in.00 in.1 in.3 in.6 in. (note 3)

Note 2: right side may be 0 in. with type B vent.

Note 3: vent clearance may be 1 in. with type B vent.

Models that show this code

12 models in Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC), R95P, R96V/96MDV

96MDV115D50AR802PA050314MSAR802PA075417MSAR802PA100521MSAR802PA125524MSAR802PA150524MSAR95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSA

Other codes on the same units

  • d6 Blower HP conflict (BLWR HP CNFLCT)
  • AF Airflow readout (pushbutton status menu)
  • C Cooling or heat-pump heat (compressor call)
  • FL Fault history (pushbutton status menu)
  • Fault recall Power-up replay of the last three faults
  • Flame LED slow blink Amber flame LED - marginal flame sense
  • Flame LED steady on Amber flame LED steady - normal flame sensed
  • Fr Fire rate readout (pushbutton status menu)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem (-)802PA Installation Instructions, Diagnostics and Fault Codes (UT 1028-928 control), pp.40-41; R95P pp.87-89. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.