Rheem · Furnace
Blinking decimal point Airflow readout - blinks of right decimal point
What the display is showing
While the blower runs, the decimal point at the right of the dual display blinks once per 100 CFM of expected airflow (rounded down to the lower hundred). Example: 1049 CFM = 10 blinks, 1051 CFM = 11 blinks. For better resolution use a service tool or the thermostat STATUS menus (BLOWER CFM, which resolves to 10 CFM).
Applies to: Rheem/Ruud RGPE / RGLE modulating furnaces
Settings for these units
Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
| Cabinet width | Input | Bottom filter | Side filter | Quantity |
|---|---|---|---|---|
| 17-1/2 in. | 50, 75 (000 Btu/h) | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 21 in. | 75, 100 (000 Btu/h) | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| 24-1/2 in. | 125 (000 Btu/h) | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
Use one filter location only - do not double-filter or filter the supply side.
21 in./100K: cut 3-1/2 in. off filter and frame for a side filter; 24-1/2 in./125K: cut 7 in.
Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
| Model size | Cabinet width (A) | Left side | Right side | Back | Top | Front | Vent |
|---|---|---|---|---|---|---|---|
| RGPE upflow/horizontal 05 | 17-1/2 in. | 0 in. | 3 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGPE upflow/horizontal 07(A) | 17-1/2 in. | 0 in. | 3 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGPE upflow/horizontal 07(B), 10 | 21 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGPE upflow/horizontal 12 | 24-1/2 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGLE downflow 07(A) | 17-1/2 in. | 0 in. | 3 in. (note 2) | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGLE downflow 07(B), 10 | 21 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
| RGLE downflow 12 | 24-1/2 in. | 0 in. | 0 | 0 in. | 1 in. | 3 in. | 6 in. (note 3) |
Note 2: right side may be 0 in. with type B vent.
Note 3: vent clearance may be 1 in. with type B vent.
Models that show this code
10 models in RGPE/RGLE
Other codes on the same units
- d5 Card/hardware conflict (CARD-HRD CNFLCT)
- d6 Blower HP conflict (BLWR HP CNFLCT)
- d7 Blower manufacturer conflict (BLWR MFG CNFLCT)
- d8 Old shared data (OLD SHARED DATA)
- Blank thermostat text area Thermostat text area blank - system found OK
- C Cooling or heat-pump heat (compressor call)
- FAULT HISTORY menu Furnace user menu - FAULT HISTORY
- FIXED FIRE RATE Forced low or high fire test (SETUP menu)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: RGPE Dual Seven-Segment Diagnostic Display, p.49. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.