Rheem · Furnace
1 blink Soft lockout (failed ignition)
What the control is telling you
Green STATUS LED blinks once: the control has given up after 4 ignition attempts and is in a 1-hour soft lockout; it ignores the heat call (W) until reset. The chart says to kill power 30 s to reset; the Sequence of Operation says 5 s (or cycle W off/on) and also 5-10 s at the thermostat or disconnect - see notes.
Applies to: Rheem (-)GRC upflow and (-)GTC downflow/horizontal 90 Plus condensing gas furnaces (UT Electronic Controls 1012-925 / 1028-928 and Invensys ICC-H1MC7-01 IFC); Rheem 90RJ and 90TJ 90 Plus condensing gas furnaces (UT Electronic Controls 1012-925 or Invensys ICC-H1MC7-01 IFC, hot surface ignition)
Likely causes
- No or low gas supply / wrong manifold pressure
- Igniter not heating (HSI open, cracked, mis-placed) or spark electrode not sparking (DSI)
- Weak or no flame signal - dirty flame sensor rod, poor ground, L1/Neutral reversed
- Gas valve not opening (wiring, manual switch OFF, open aux. limit or drain pressure switch)
- Restricted orifice or poor flame carry-over across burners
Test and repair steps
- Reset shut off main power to the furnace, wait 30 seconds, restore power and make a fresh heat call.
- Watch the cycle the inducer pre-purges, the igniter heats (HSI glow or DSI spark), then the gas valve is powered for about 7-8 s per trial; the system tries 4 times and the blower + inducer run 180 s between the 2nd and 3rd attempts.
- No glow/spark HSI - check igniter is connected, wires, resistance (replace if open, too low or too high), cracks and placement; DSI - check electrode wire/connections, gap/alignment, ground, arcing to metal before the tip, clean with sandpaper or replace.
- Igniter OK but burners do not light check gas supply and manifold pressure (verify gas valve inlet and outlet pressure), orifices for restriction, gas valve manual switch ON, 24 V on the IFC gas valve pins and wiring/continuity to the valve.
- On 90+ furnaces check the auxiliary limit is closed and, on upflow models, that the drain pressure switch is closed - clear a blocked drain, or replace the switch if the drain is clear.
- Burners light then drop out confirm L1 and Neutral are not swapped at the IFC and junction box, check IFC and unit ground, clean the flame sense rod (sandpaper) and check its wire to the IFC.
- Check that flame carries across all burners and all burners stay lit.
- Only replace the IFC after all of the above - most failures are not the control.
Settings for these units
Filter sizes (Table 12) · Rheem 90RJ/90TJ 90 Plus
| Configuration | Cabinet width | Input (MBTU/h) | Bottom filter | Side filter | Qty |
|---|---|---|---|---|---|
| Upflow | 17-1/2 in. | 45, 60, 75 | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| Upflow | 21 in. | 90, 105 | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| Upflow | 24-1/2 in. | 120 | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| Downflow | 17-1/2 in. | 45, 60, 75 | 12 x 20 in. | - | 2 |
| Downflow | 21 in. | 90, 105 | 12 x 20 in. | - | 2 |
| Downflow | 24-1/2 in. | 120 | 14 x 20 in. | - | 2 |
Filters are not factory-installed; they must be field supplied.
Side filter on 21 in. units: cut 3.5 in. off the filter and frame; on 24.5 in. units cut 7 in.
Minimum clearance to combustibles · Rheem 90RJ/90TJ 90 Plus
| Configuration | Left side | Right side | Back | Top | Front | Vent |
|---|---|---|---|---|---|---|
| Upflow | 0 in. | 0 in. | 0 in. | 1 in. | 2 in. (24 in. service) | 0 in. |
| Downflow | 0 in. | 0 in. | 0 in. | 1 in. | 2 in. (24 in. service) | 0 in. |
| Horizontal | 0 in. | 0 in. | 0 in. | 1 in. | 2 in. (24 in. service) | 0 in. |
Same values for every cabinet size.
24 in. service clearance recommended in front of all furnaces.
- Filter sizes (Table 9) · Rheem (-)GRC/(-)GTC 90 Plus
- Minimum clearance to combustibles · Rheem (-)GRC/(-)GTC 90 Plus
Models that show this code
23 models in Rheem (-)GRC/(-)GTC 90 Plus, Rheem 90RJ/90TJ 90 Plus
Other codes on the same units
- 2 blinks Pressure switch circuit open
- 3 blinks Limit circuit open
- 4 blinks Pressure switch circuit closed (stuck closed)
- 5 blinks Twinning fault (optional)
- Flame LED off No flame sensed (troubleshooting aid)
- Flame LED slow blink Amber flame LED - marginal flame sense
- Flame LED steady on Amber flame LED steady - normal flame sensed
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)GRC/(-)GTC Installation Instructions 92-24161-88-00, Figure 56 IFC Troubleshooting Guide, p.54 (printed); Rheem 90RJ/90TJ Installation Instructions 92-24161-32-08, Figure 53 IFC Troubleshooting Guide, p.54 (printed p.53). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.