Rheem · Furnace
3 blinks Limit circuit open
What the control is telling you
Green STATUS LED blinks 3 times: the limit circuit (main limit, rollout / overtemperature switches, or the aux. limit that the inducer wire passes through) is open or opening and closing.
Applies to: Rheem (-)GRC upflow and (-)GTC downflow/horizontal 90 Plus condensing gas furnaces (UT Electronic Controls 1012-925 / 1028-928 and Invensys ICC-H1MC7-01 IFC); Rheem 90RJ and 90TJ 90 Plus condensing gas furnaces (UT Electronic Controls 1012-925 or Invensys ICC-H1MC7-01 IFC, hot surface ignition)
Likely causes
- Restricted airflow - dirty filter, closed dampers or registers
- Over-firing - temperature rise above the rating plate range from high gas pressure or wrong orifices
- Tripped manual-reset rollout / overtemperature switch from flame rollout (blocked flue or heat exchanger)
- Loose wiring or connections between IFC and limits
- Faulty limit
Test and repair steps
- Warning: Hazardous line voltage - disconnect power before servicing; work must be done by a trained, qualified service technician.
- Check airflow filter, dampers, closed registers and other restrictions.
- Measure temperature rise; if above the stated range, check gas valve, gas pressure and orifice size for over-firing.
- Check whether a rollout or overtemperature switch needs manual reset. WARNING: do not jumper these switches and do not reset one without finding and correcting the cause (inadequate combustion air, blocked flue or heat exchanger) - CO poisoning risk.
- Check the wiring and connections between the IFC and every limit, including the aux. limit wire through which the IDM is fed on 90+ units.
- Confirm limits are not open while circulating air temperature is within the normal range; replace only with the identical part.
Settings for these units
Filter sizes (Table 12) · Rheem 90RJ/90TJ 90 Plus
| Configuration | Cabinet width | Input (MBTU/h) | Bottom filter | Side filter | Qty |
|---|---|---|---|---|---|
| Upflow | 17-1/2 in. | 45, 60, 75 | 15-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| Upflow | 21 in. | 90, 105 | 19-1/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| Upflow | 24-1/2 in. | 120 | 22-3/4 x 25 in. | 15-3/4 x 25 in. | 1 |
| Downflow | 17-1/2 in. | 45, 60, 75 | 12 x 20 in. | - | 2 |
| Downflow | 21 in. | 90, 105 | 12 x 20 in. | - | 2 |
| Downflow | 24-1/2 in. | 120 | 14 x 20 in. | - | 2 |
Filters are not factory-installed; they must be field supplied.
Side filter on 21 in. units: cut 3.5 in. off the filter and frame; on 24.5 in. units cut 7 in.
Minimum clearance to combustibles · Rheem 90RJ/90TJ 90 Plus
| Configuration | Left side | Right side | Back | Top | Front | Vent |
|---|---|---|---|---|---|---|
| Upflow | 0 in. | 0 in. | 0 in. | 1 in. | 2 in. (24 in. service) | 0 in. |
| Downflow | 0 in. | 0 in. | 0 in. | 1 in. | 2 in. (24 in. service) | 0 in. |
| Horizontal | 0 in. | 0 in. | 0 in. | 1 in. | 2 in. (24 in. service) | 0 in. |
Same values for every cabinet size.
24 in. service clearance recommended in front of all furnaces.
- Filter sizes (Table 9) · Rheem (-)GRC/(-)GTC 90 Plus
- Minimum clearance to combustibles · Rheem (-)GRC/(-)GTC 90 Plus
Models that show this code
23 models in Rheem (-)GRC/(-)GTC 90 Plus, Rheem 90RJ/90TJ 90 Plus
Other codes on the same units
- 1 blink Soft lockout (failed ignition)
- 2 blinks Pressure switch circuit open
- 4 blinks Pressure switch circuit closed (stuck closed)
- 5 blinks Twinning fault (optional)
- Flame LED off No flame sensed (troubleshooting aid)
- Flame LED slow blink Amber flame LED - marginal flame sense
- Flame LED steady on Amber flame LED steady - normal flame sensed
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)GRC/(-)GTC Installation Instructions 92-24161-88-00, Figure 56 IFC Troubleshooting Guide, p.54 (printed); Rheem 90RJ/90TJ Installation Instructions 92-24161-32-08, Figure 53 IFC Troubleshooting Guide, p.54 (printed p.53). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.