Refrigerant data

Data sheet for every refrigerant: pressures, safety, GWP, oil, uses.

Refrigerant data sheet

Pick a refrigerant to see its data sheet and P/T chart.

All refrigerants at a glance

RefrigerantTypeSafetyGWPBoils at (°F)Low side (psig)High side (psig)Old colourOil
R-11CFCA14,75074.7V 24.03.6OrangeMineral / AB
R-12CFCA110,900-21.611.793.2WhiteMineral / AB
R-22HCFCA11,810-41.528.3158Light greenMineral / AB (POE in retrofits)
R-23HFCA114,800-115.6221–Light blue-grayPOE
R-32HFCA2L675-6156.1265Light blue-greenPOE (PVE in some)
R-123HCFCB17782.1V 25.21.2Light blue-grayMineral / AB
R-125HFCA13,500-54.644.0213Medium brownPOE
R-134aHFCA11,430-14.99.197.0Light bluePOE (PAG in car A/C)
R-143aHFCA2L4,470-5340.0193–POE
R-152aHFCA2124-11.26.985.4–POE / Mineral
R-170Natural (hydrocarbon)A36-127.4222––Mineral / POE
R-245faHFCB11,03059.1V 22.411.1MaroonPOE
R-290Natural (hydrocarbon)A33-43.827.6142–Mineral / POE / AB
R-401AHCFC blendA11,182-27.59.8114CoralAB / POE
R-401BHCFC blendA11,288-30.411.9122MustardAB / POE
R-404AHFC blendA13,922-51.237.7193OrangePOE
R-407AHFC blendA12,107-4926.9193Lime greenPOE
R-407CHFC blendA11,774-46.523.5182BrownPOE
R-407FHFC blendA11,824-50.928.9202Green-yellow-whitePOE
R-408AHCFC blendA13,152-47.633.6176Medium purpleAB / POE
R-409AHCFC blendA11,585-29.78.7118Medium brownAB / POE
R-410AHFC blendA12,088-60.654.9259RosePOE
R-417AHFC blendA12,346-38.419.1149GreenPOE (mineral tolerated)
R-422AHFC blendA13,143-52.136.2197Yellow-orangePOE
R-422DHFC blendA12,729-46.125.9173Green-yellowPOE
R-427AHFC blendA12,138-45.422.6175Jungle greenPOE
R-448AHFO/HFC blendA11,387-51.128.3199Gentian bluePOE
R-449AHFO/HFC blendA11,397-50.628.4196Grayish bluePOE
R-450AHFO/HFC blendA1604-10.56.185.1Sapphire bluePOE
R-452AHFO/HFC blendA12,140-52.533.1201Metallic bluePOE
R-452BHFO/HFC blendA2L698-59.650.1249–POE
R-454AHFO/HFC blendA2L239-54.630.6208–POE
R-454BHFO/HFC blendA2L466-59.349.1247–POE
R-454CHFO/HFC blendA2L148-49.722.8179–POE
R-455AHFO/HFC blendA2L148-61.925.4212Sea foam greenPOE
R-500CFC blendA18,077-29.116.9114YellowMineral / AB
R-502CFC/HCFC blendA14,657-48.634.0172LavenderMineral / AB
R-507AHFC blend (azeotrope)A13,985-52.140.0197TealPOE
R-508BHFC blendA113,396-125.8259–NavyPOE
R-513AHFO/HFC blendA1631-2112.2104Sky bluePOE
R-600Natural (hydrocarbon)A3431.1V 13.226.4–Mineral
R-600aNatural (hydrocarbon)A3310.9V 3.744.0–Mineral / POE
R-717NaturalB2L0-2819.5155SilverMineral / PAO
R-744NaturalA11-126.5318––POE / PAG / PAO
R-1233zd(E)HFOA1164.6V 22.87.8–POE / Mineral
R-1234yfHFOA2L4-2111.999.0–PAG (car A/C) / POE
R-1234ze(E)HFOA2L6-2.22.769.2–POE
R-1270Natural (hydrocarbon)A32-53.738.0175–Mineral / POE

Low side = 5 °F evaporating (dew), high side = 86 °F condensing (bubble). V = vacuum in inches of mercury. Pick a refrigerant above for the full data sheet.

Reading the safety class

Oil rules

Handling rules

Refrigerant numbers

Take it with you

All of these tables, plus the calculators, are in the HVACopedia app, offline.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.