Refrigerant · Natural (hydrocarbon)

R-600a pressure-temperature chart and data

Isobutane. Safety class A3, GWP 3. Domestic fridges and freezers. Replaced R-12 and R-134a. Highly flammable.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-600a data sheet

NameIsobutane
TypeNatural (hydrocarbon)
Safety classA3 — lower toxicity, highly flammable
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)3
Boils at 1 atm10.9 °F (-11.7 °C)
Critical temperature274.4 °F (134.7 °C)
Temperature glidenone / very small
Low side at 5 °F evaporatingV 3.7 psig (-12 kPa)
High side at 86 °F condensing44.0 psig (303 kPa)
Old cylinder colournone assigned
OilMineral / POE
Used forDomestic fridges and freezers. Replaced R-12 and R-134a. Highly flammable.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-600a pressure / temperature chart

°F°CpsigkPa
-60-51.1V 25.3-86
-59-50.6V 25.1-85
-58-50.0V 25.0-85
-57-49.4V 24.8-84
-56-48.9V 24.6-83
-55-48.3V 24.5-83
-54-47.8V 24.3-82
-53-47.2V 24.1-82
-52-46.7V 24.0-81
-51-46.1V 23.8-81
-50-45.6V 23.6-80
-49-45.0V 23.4-79
-48-44.4V 23.2-79
-47-43.9V 23.0-78
-46-43.3V 22.8-77
-45-42.8V 22.6-76
-44-42.2V 22.4-76
-43-41.7V 22.1-75
-42-41.1V 21.9-74
-41-40.6V 21.7-73
-40-40.0V 21.4-73
-39-39.4V 21.2-72
-38-38.9V 21.0-71
-37-38.3V 20.7-70
-36-37.8V 20.4-69
-35-37.2V 20.2-68
-34-36.7V 19.9-67
-33-36.1V 19.6-66
-32-35.6V 19.3-66
-31-35.0V 19.1-65
-30-34.4V 18.8-64
-29-33.9V 18.5-63
-28-33.3V 18.1-61
-27-32.8V 17.8-60
-26-32.2V 17.5-59
-25-31.7V 17.2-58
-24-31.1V 16.8-57
-23-30.6V 16.5-56
-22-30.0V 16.1-55
-21-29.4V 15.8-54
-20-28.9V 15.4-52
-19-28.3V 15.1-51
-18-27.8V 14.7-50
-17-27.2V 14.3-48
-16-26.7V 13.9-47
-15-26.1V 13.5-46
-14-25.6V 13.1-44
-13-25.0V 12.7-43
-12-24.4V 12.2-41
-11-23.9V 11.8-40
-10-23.3V 11.4-38
-9-22.8V 10.9-37
-8-22.2V 10.4-35
-7-21.7V 10.0-34
-6-21.1V 9.5-32
-5-20.6V 9.0-31
-4-20.0V 8.5-29
-3-19.4V 8.0-27
-2-18.9V 7.5-25
-1-18.3V 7.0-24
0-17.8V 6.4-22
1-17.2V 5.9-20
2-16.7V 5.3-18
3-16.1V 4.8-16
4-15.6V 4.2-14
5-15.0V 3.6-12
6-14.4V 3.0-10
7-13.9V 2.4-8
8-13.3V 1.8-6
9-12.8V 1.2-4
10-12.2V 0.5-2
11-11.70.10
12-11.10.43
13-10.60.75
14-10.01.07
15-9.41.49
16-8.91.712
17-8.32.114
18-7.82.417
19-7.22.819
20-6.73.222
21-6.13.524
22-5.63.927
23-5.04.330
24-4.44.732
25-3.95.135
26-3.35.538
27-2.85.941
28-2.26.344
29-1.76.847
30-1.17.250
31-0.67.653
320.08.156
330.68.559
341.19.062
351.79.465
362.29.968
372.810.472
383.310.975
393.911.478
404.411.982
415.012.485
425.612.989
436.113.493
446.714.096
457.214.5100
467.815.0104
478.315.6107
488.916.1111
499.416.7115
5010.017.3119
5110.617.9123
5211.118.5127
5311.719.1132
5412.219.7136
5512.820.3140
5613.320.9144
5713.921.6149
5814.422.2153
5915.022.9158
6015.623.5162
6116.124.2167
6216.724.9172
6317.225.6176
6417.826.3181
6518.327.0186
6618.927.7191
6719.428.4196
6820.029.1201
6920.629.9206
7021.130.6211
7121.731.4216
7222.232.2222
7322.832.9227
7423.333.7233
7523.934.5238
7624.435.3244
7725.036.2249
7825.637.0255
7926.137.8261
8026.738.7267
8127.239.5273
8227.840.4279
8328.341.3285
8428.942.2291
8529.443.1297
8630.044.0303
8730.644.9310
8831.145.9316
8931.746.8323
9032.247.8329
9132.848.7336
9233.349.7343
9333.950.7350
9434.451.7356
9535.052.7363
9635.653.7371
9736.154.8378
9836.755.8385
9937.256.9392
10037.858.0400
10138.359.0407
10238.960.1415
10339.461.2422
10440.062.4430
10540.663.5438
10641.164.6446
10741.765.8454
10842.266.9462
10942.868.1470
11043.369.3478
11143.970.5486
11244.471.7495
11345.073.0503
11445.674.2512
11546.175.5520
11646.776.7529
11747.278.0538
11847.879.3547
11948.380.6556
12048.982.0565
12149.483.3574
12250.084.6584
12350.686.0593
12451.187.4602
12551.788.8612
12652.290.2622
12752.891.6632
12853.393.0641
12953.994.5651
13054.495.9661

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-600a pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-60-51.1V 25.32.3-86160.16
-55-48.3V 24.52.7-83180.18
-50-45.6V 23.63.1-80210.21
-45-42.8V 22.63.6-76250.25
-40-40.0V 21.44.2-73290.29
-35-37.2V 20.24.8-68330.33
-30-34.4V 18.85.5-64380.38
-25-31.7V 17.26.3-58430.43
-20-28.9V 15.47.1-52490.49
-15-26.1V 13.58.1-46560.56
-10-23.3V 11.49.1-38630.63
-5-20.6V 9.010.3-31710.71
0-17.8V 6.411.5-22800.80
5-15.0V 3.612.9-12890.89
10-12.2V 0.514.4-2990.99
15-9.41.416.191111.11
20-6.73.217.9221231.23
25-3.95.119.8351361.36
30-1.17.221.9501511.51
351.79.424.1651661.66
404.411.926.6821831.83
457.214.529.21002012.01
5010.017.332.01192212.21
5512.820.335.01402412.41
6015.623.538.21622642.64
6518.327.041.71862872.87
7021.130.645.32113133.13
7523.934.549.22383393.39
8026.738.753.42673683.68
8529.443.157.82973983.98
9032.247.862.53294314.31
9535.052.767.43634654.65
10037.858.072.64005015.01
10540.663.578.24385395.39
11043.369.384.04785795.79
11546.175.590.25206226.22
12048.982.096.65656666.66
12551.788.8103.56127137.13
13054.495.9110.66617637.63

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.