Refrigerant · Natural (hydrocarbon)

R-600 pressure-temperature chart and data

Butane. Safety class A3, GWP 4. Mostly used in blends and some domestic refrigeration. Highly flammable.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-600 data sheet

NameButane
TypeNatural (hydrocarbon)
Safety classA3 — lower toxicity, highly flammable
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)4
Boils at 1 atm31.1 °F (-0.5 °C)
Critical temperature305.6 °F (152.0 °C)
Temperature glidenone / very small
Low side at 5 °F evaporatingV 13.2 psig (-45 kPa)
High side at 86 °F condensing26.4 psig (182 kPa)
Old cylinder colournone assigned
OilMineral
Used forMostly used in blends and some domestic refrigeration. Highly flammable.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-600 pressure / temperature chart

°F°CpsigkPa
-60-51.1V 27.3-92
-59-50.6V 27.2-92
-58-50.0V 27.1-92
-57-49.4V 27.0-92
-56-48.9V 26.9-91
-55-48.3V 26.8-91
-54-47.8V 26.7-91
-53-47.2V 26.6-90
-52-46.7V 26.5-90
-51-46.1V 26.4-89
-50-45.6V 26.3-89
-49-45.0V 26.2-89
-48-44.4V 26.0-88
-47-43.9V 25.9-88
-46-43.3V 25.8-87
-45-42.8V 25.7-87
-44-42.2V 25.5-86
-43-41.7V 25.4-86
-42-41.1V 25.2-85
-41-40.6V 25.1-85
-40-40.0V 25.0-85
-39-39.4V 24.8-84
-38-38.9V 24.7-83
-37-38.3V 24.5-83
-36-37.8V 24.3-82
-35-37.2V 24.2-82
-34-36.7V 24.0-81
-33-36.1V 23.8-81
-32-35.6V 23.6-80
-31-35.0V 23.5-79
-30-34.4V 23.3-79
-29-33.9V 23.1-78
-28-33.3V 22.9-77
-27-32.8V 22.7-77
-26-32.2V 22.5-76
-25-31.7V 22.3-75
-24-31.1V 22.0-75
-23-30.6V 21.8-74
-22-30.0V 21.6-73
-21-29.4V 21.4-72
-20-28.9V 21.1-71
-19-28.3V 20.9-71
-18-27.8V 20.6-70
-17-27.2V 20.4-69
-16-26.7V 20.1-68
-15-26.1V 19.9-67
-14-25.6V 19.6-66
-13-25.0V 19.3-65
-12-24.4V 19.0-64
-11-23.9V 18.8-64
-10-23.3V 18.5-63
-9-22.8V 18.2-62
-8-22.2V 17.9-60
-7-21.7V 17.6-59
-6-21.1V 17.2-58
-5-20.6V 16.9-57
-4-20.0V 16.6-56
-3-19.4V 16.2-55
-2-18.9V 15.9-54
-1-18.3V 15.5-53
0-17.8V 15.2-51
1-17.2V 14.8-50
2-16.7V 14.4-49
3-16.1V 14.1-48
4-15.6V 13.7-46
5-15.0V 13.3-45
6-14.4V 12.9-44
7-13.9V 12.5-42
8-13.3V 12.1-41
9-12.8V 11.6-39
10-12.2V 11.2-38
11-11.7V 10.8-36
12-11.1V 10.3-35
13-10.6V 9.9-33
14-10.0V 9.4-32
15-9.4V 8.9-30
16-8.9V 8.4-29
17-8.3V 7.9-27
18-7.8V 7.4-25
19-7.2V 6.9-23
20-6.7V 6.4-22
21-6.1V 5.9-20
22-5.6V 5.3-18
23-5.0V 4.8-16
24-4.4V 4.2-14
25-3.9V 3.7-12
26-3.3V 3.1-10
27-2.8V 2.5-8
28-2.2V 1.9-6
29-1.7V 1.3-4
30-1.1V 0.7-2
31-0.6V 0.1-0
320.00.32
330.60.64
341.10.96
351.71.29
362.21.611
372.81.913
383.32.316
393.92.618
404.43.020
415.03.323
425.63.725
436.14.128
446.74.431
457.24.833
467.85.236
478.35.639
488.96.041
499.46.444
5010.06.847
5110.67.350
5211.17.753
5311.78.156
5412.28.659
5512.89.062
5613.39.465
5713.99.968
5814.410.472
5915.010.875
6015.611.378
6116.111.881
6216.712.385
6317.212.888
6417.813.392
6518.313.895
6618.914.499
6719.414.9103
6820.015.4106
6920.616.0110
7021.116.5114
7121.717.1118
7222.217.6122
7322.818.2126
7423.318.8130
7523.919.4134
7624.420.0138
7725.020.6142
7825.621.2146
7926.121.8151
8026.722.5155
8127.223.1159
8227.823.7164
8328.324.4168
8428.925.1173
8529.425.7177
8630.026.4182
8730.627.1187
8831.127.8192
8931.728.5197
9032.229.2201
9132.829.9206
9233.330.7211
9333.931.4217
9434.432.2222
9535.032.9227
9635.633.7232
9736.134.5238
9836.735.3243
9937.236.1249
10037.836.9254
10138.337.7260
10238.938.5266
10339.439.4271
10440.040.2277
10540.641.1283
10641.141.9289
10741.742.8295
10842.243.7301
10942.844.6307
11043.345.5314
11143.946.4320
11244.447.3326
11345.048.3333
11445.649.2339
11546.150.2346
11646.751.1353
11747.252.1359
11847.853.1366
11948.354.1373
12048.955.1380
12149.456.2387
12250.057.2394
12350.658.3402
12451.159.3409
12551.760.4416
12652.261.5424
12752.862.6431
12853.363.7439
12953.964.8447
13054.465.9454

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-600 pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-60-51.1V 27.31.3-9290.09
-55-48.3V 26.81.5-91100.10
-50-45.6V 26.31.8-89120.12
-45-42.8V 25.72.1-87140.14
-40-40.0V 25.02.4-85170.17
-35-37.2V 24.22.8-82190.19
-30-34.4V 23.33.3-79230.23
-25-31.7V 22.33.8-75260.26
-20-28.9V 21.14.3-71300.30
-15-26.1V 19.94.9-67340.34
-10-23.3V 18.55.6-63390.39
-5-20.6V 16.96.4-57440.44
0-17.8V 15.27.2-51500.50
5-15.0V 13.38.2-45560.56
10-12.2V 11.29.2-38630.63
15-9.4V 8.910.3-30710.71
20-6.7V 6.411.5-22800.80
25-3.9V 3.712.9-12890.89
30-1.1V 0.714.4-2990.99
351.71.215.991101.10
404.43.017.7201221.22
457.24.819.5331351.35
5010.06.821.5471481.48
5512.89.023.7621631.63
6015.611.326.0781791.79
6518.313.828.5951971.97
7021.116.531.21142152.15
7523.919.434.11342352.35
8026.722.537.21552562.56
8529.425.740.41772792.79
9032.229.243.92013033.03
9535.032.947.62273283.28
10037.836.951.62543563.56
10540.641.155.82833843.84
11043.345.560.23144154.15
11546.150.264.93464474.47
12048.955.169.83804824.82
12551.760.475.14165185.18
13054.465.980.64545565.56

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.