Refrigerant · HFO

R-1234yf pressure-temperature chart and data

Tetrafluoropropene. Safety class A2L, GWP 4. Car A/C (replaced R-134a) and some refrigeration. Mildly flammable.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-1234yf data sheet

NameTetrafluoropropene
TypeHFO
Safety classA2L — lower toxicity, mildly flammable (burns slowly)
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)4
Boils at 1 atm-21 °F (-29.4 °C)
Critical temperature202.5 °F (94.7 °C)
Temperature glidenone / very small
Low side at 5 °F evaporating11.9 psig (82 kPa)
High side at 86 °F condensing99.0 psig (683 kPa)
Old cylinder colournone assigned
OilPAG (car A/C) / POE
Used forCar A/C (replaced R-134a) and some refrigeration. Mildly flammable.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-1234yf pressure / temperature chart

°F°CpsigkPa
-60-51.1V 19.6-66
-59-50.6V 19.3-65
-58-50.0V 18.9-64
-57-49.4V 18.6-63
-56-48.9V 18.2-62
-55-48.3V 17.9-61
-54-47.8V 17.6-59
-53-47.2V 17.2-58
-52-46.7V 16.8-57
-51-46.1V 16.4-56
-50-45.6V 16.0-54
-49-45.0V 15.6-53
-48-44.4V 15.2-52
-47-43.9V 14.8-50
-46-43.3V 14.4-49
-45-42.8V 13.9-47
-44-42.2V 13.5-46
-43-41.7V 13.0-44
-42-41.1V 12.5-42
-41-40.6V 12.1-41
-40-40.0V 11.5-39
-39-39.4V 11.1-37
-38-38.9V 10.5-36
-37-38.3V 10.0-34
-36-37.8V 9.5-32
-35-37.2V 8.9-30
-34-36.7V 8.4-28
-33-36.1V 7.8-26
-32-35.6V 7.2-24
-31-35.0V 6.6-22
-30-34.4V 6.0-20
-29-33.9V 5.4-18
-28-33.3V 4.8-16
-27-32.8V 4.1-14
-26-32.2V 3.5-12
-25-31.7V 2.8-9
-24-31.1V 2.1-7
-23-30.6V 1.4-5
-22-30.0V 0.7-2
-21-29.40.00
-20-28.90.43
-19-28.30.75
-18-27.81.18
-17-27.21.510
-16-26.71.913
-15-26.12.316
-14-25.62.719
-13-25.03.121
-12-24.43.524
-11-23.94.027
-10-23.34.430
-9-22.84.833
-8-22.25.336
-7-21.75.840
-6-21.16.243
-5-20.66.746
-4-20.07.250
-3-19.47.753
-2-18.98.256
-1-18.38.760
0-17.89.264
1-17.29.767
2-16.710.371
3-16.110.875
4-15.611.478
5-15.011.982
6-14.412.586
7-13.913.190
8-13.313.794
9-12.814.399
10-12.214.9103
11-11.715.5107
12-11.116.2111
13-10.616.8116
14-10.017.5120
15-9.418.1125
16-8.918.8130
17-8.319.5134
18-7.820.2139
19-7.220.9144
20-6.721.6149
21-6.122.3154
22-5.623.1159
23-5.023.8164
24-4.424.6170
25-3.925.4175
26-3.326.2180
27-2.826.9186
28-2.227.8191
29-1.728.6197
30-1.129.4203
31-0.630.3209
320.031.1215
330.632.0221
341.132.9227
351.733.8233
362.234.7239
372.835.6245
383.336.5252
393.937.5258
404.438.4265
415.039.4272
425.640.4278
436.141.4285
446.742.4292
457.243.4299
467.844.5307
478.345.5314
488.946.6321
499.447.7329
5010.048.8336
5110.649.9344
5211.151.0352
5311.752.2360
5412.253.3368
5512.854.5376
5613.355.7384
5713.956.9392
5814.458.1401
5915.059.3409
6015.660.6418
6116.161.8426
6216.763.1435
6317.264.4444
6417.865.7453
6518.367.1462
6618.968.4472
6719.469.8481
6820.071.1490
6920.672.5500
7021.174.0510
7121.775.4520
7222.276.8530
7322.878.3540
7423.379.8550
7523.981.3560
7624.482.8571
7725.084.3581
7825.685.9592
7926.187.4603
8026.789.0614
8127.290.6625
8227.892.3636
8328.393.9647
8428.995.6659
8529.497.3671
8630.099.0682
8730.6101694
8831.1102706
8931.7104718
9032.2106731
9132.8108743
9233.3110756
9333.9111768
9434.4113781
9535.0115794
9635.6117807
9736.1119820
9836.7121834
9937.2123847
10037.8125861
10138.3127875
10238.9129889
10339.4131903
10440.0133917
10540.6135932
10641.1137946
10741.7139961
10842.2142976
10942.8144991
11043.31461006
11143.91481021
11244.41501037
11345.01531053
11445.61551068
11546.11571084
11646.71601101
11747.21621117
11847.81641133
11948.31671150
12048.91691167
12149.41721184
12250.01741201
12350.61771218
12451.11791236
12551.71821254
12652.21841271
12752.81871289
12853.31901308
12953.91921326
13054.41951345

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-1234yf pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-60-51.1V 19.65.1-66350.35
-55-48.3V 17.95.9-61410.41
-50-45.6V 16.06.8-54470.47
-45-42.8V 13.97.9-47540.54
-40-40.0V 11.59.0-39620.62
-35-37.2V 8.910.3-30710.71
-30-34.4V 6.011.7-20810.81
-25-31.7V 2.813.3-9920.92
-20-28.90.415.131041.04
-15-26.12.317.0161171.17
-10-23.34.419.1301321.32
-5-20.66.721.4461481.48
0-17.89.223.9641651.65
5-15.011.926.6821841.84
10-12.214.929.61032042.04
15-9.418.132.81252262.26
20-6.721.636.31492502.50
25-3.925.440.11752762.76
30-1.129.444.12033043.04
351.733.848.52333343.34
404.438.453.12653663.66
457.243.458.12994014.01
5010.048.863.53364384.38
5512.854.569.23764774.77
6015.660.675.34185195.19
6518.367.181.84625645.64
7021.174.088.65106116.11
7523.981.396.05606626.62
8026.789.0103.76147157.15
8529.497.3112.06717727.72
9032.2106120.77318328.32
9535.0115129.97948958.95
10037.8125139.68619629.62
10540.6135149.8932103310.33
11043.3146160.61006110711.07
11546.1157172.01084118611.86
12048.9169183.91167126812.68
12551.7182196.51254135513.55
13054.4195209.71345144614.46

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.