Refrigerant · HFO/HFC blend

R-454C pressure-temperature chart and data

R-32 / R-1234yf. Safety class A2L, GWP 148. Lower-GWP replacement for R-404A in refrigeration. Mildly flammable.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-454C data sheet

Made ofR-32 21.5 / R-1234yf 78.5 (mass %)
TypeHFO/HFC blend
Safety classA2L — lower toxicity, mildly flammable (burns slowly)
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)148
Boils at 1 atm-49.7 °F (-45.4 °C)
Critical temperature189.8 °F (87.7 °C)
Temperature glideabout 14.9 °F
Low side at 5 °F evaporating22.8 psig (157 kPa)
High side at 86 °F condensing179 psig (1236 kPa)
Old cylinder colournone assigned
OilPOE
Used forLower-GWP replacement for R-404A in refrigeration. Mildly flammable.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-454C pressure / temperature chart

°F°CDew psig (vapour)Bubble psig (liquid)Dew kPaBubble kPa
-60-51.1V 15.1V 7.3-51-25
-59-50.6V 14.6V 6.6-50-22
-58-50.0V 14.2V 6.0-48-20
-57-49.4V 13.7V 5.3-46-18
-56-48.9V 13.2V 4.6-45-16
-55-48.3V 12.7V 3.9-43-13
-54-47.8V 12.2V 3.2-41-11
-53-47.2V 11.7V 2.5-40-9
-52-46.7V 11.1V 1.8-38-6
-51-46.1V 10.6V 1.0-36-4
-50-45.6V 10.0V 0.3-34-1
-49-45.0V 9.50.3-322
-48-44.4V 8.90.7-304
-47-43.9V 8.31.1-287
-46-43.3V 7.71.5-2610
-45-42.8V 7.11.9-2413
-44-42.2V 6.42.3-2216
-43-41.7V 5.82.8-2019
-42-41.1V 5.13.2-1722
-41-40.6V 4.43.6-1525
-40-40.0V 3.74.1-1328
-39-39.4V 3.04.6-1032
-38-38.9V 2.35.1-835
-37-38.3V 1.65.5-538
-36-37.8V 0.86.0-342
-35-37.2V 0.16.6-045
-34-36.70.47.1249
-33-36.10.87.6552
-32-35.61.18.1856
-31-35.01.68.71160
-30-34.42.09.31464
-29-33.92.49.81768
-28-33.32.810.42072
-27-32.83.311.02376
-26-32.23.711.62680
-25-31.74.212.22984
-24-31.14.712.83288
-23-30.65.213.43693
-22-30.05.614.13997
-21-29.46.114.842102
-20-28.96.715.446106
-19-28.37.216.149111
-18-27.87.716.853116
-17-27.28.217.557121
-16-26.78.818.260125
-15-26.19.318.964131
-14-25.69.919.768136
-13-25.010.520.472141
-12-24.411.121.276146
-11-23.911.721.980151
-10-23.312.322.785157
-9-22.812.923.589162
-8-22.213.524.493168
-7-21.714.225.298174
-6-21.114.826.0102179
-5-20.615.526.9107185
-4-20.016.227.7111191
-3-19.416.928.6116197
-2-18.917.629.5121204
-1-18.318.330.4126210
0-17.819.031.4131216
1-17.219.732.3136223
2-16.720.533.2141229
3-16.121.234.2146236
4-15.622.035.2152243
5-15.022.836.2157249
6-14.423.637.2163256
7-13.924.438.2168263
8-13.325.239.3174271
9-12.826.140.3180278
10-12.226.941.4186285
11-11.727.842.5192293
12-11.128.743.6198300
13-10.629.644.7204308
14-10.030.545.8210316
15-9.431.447.0217324
16-8.932.448.1223332
17-8.333.349.3230340
18-7.834.350.5236348
19-7.235.351.7243357
20-6.736.353.0250365
21-6.137.354.2257374
22-5.638.355.5264383
23-5.039.356.8271391
24-4.440.458.1278400
25-3.941.559.4286410
26-3.342.560.7293419
27-2.843.762.1301428
28-2.244.863.5309438
29-1.745.964.9317447
30-1.147.166.3325457
31-0.648.367.7333467
320.049.469.2341477
330.650.670.6349487
341.151.972.1358497
351.753.173.6366507
362.254.475.1375518
372.855.676.7384529
383.356.978.2393539
393.958.379.8402550
404.459.681.4411561
415.060.983.0420573
425.662.384.7430584
436.163.786.3439595
446.765.188.0449607
457.266.589.7459619
467.868.091.5469631
478.369.493.2479643
488.970.995.0489655
499.472.496.8499667
5010.073.998.6510680
5110.675.5100520692
5211.177.0102531705
5311.778.6104542718
5412.280.2106553731
5512.881.9108564744
5613.383.5110576758
5713.985.2112587771
5814.486.9114599785
5915.088.6116611799
6015.690.3118623813
6116.192.1120635827
6216.793.8122647841
6317.295.6124659856
6417.897.5126672870
6518.399.3128685885
6618.9101131698900
6719.4103133711915
6820.0105135724930
6920.6107137737946
7021.1109139751962
7121.7111142764977
7222.2113144778993
7322.81151467921010
7423.31171498061026
7523.91191518211042
7624.41211548351059
7725.01231568501076
7825.61251598651093
7926.11281618801110
8026.71301648951127
8127.21321669111145
8227.81341699261163
8328.31371719421181
8428.91391749581199
8529.41411779741217
8630.01441799901235
8730.614618210071254
8831.114818510241273
8931.715118710401292
9032.215319010581311
9132.815619310751331
9233.315819610921350
9333.916119911101370
9434.416420211281390
9535.016620511461410
9635.616920711641431
9736.117221011831451
9836.717421312011472
9937.217721712201493
10037.818022012401514
10138.318322312591535
10238.918522612781557
10339.418822912981579
10440.019123213181601
10540.619423513381623
10641.119723913591645
10741.720024213791668
10842.220324514001691
10942.820624914211714
11043.320925214431737
11143.921225514641761
11244.421625914861784
11345.021926215081808
11445.622226615301832
11546.122526915531856
11646.722827315751881
11747.223227615981906
11847.823528016221931
11948.323928416451956
12048.924228716691981
12149.424629116932007
12250.024929517172033
12350.625329917412059
12451.125630217662085
12551.726030617912112
12652.226331018162138
12752.826731418422165
12853.327131818682192
12953.927532218942220
13054.427832619202248

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-454C pressure in psig, psia, kPa and bar

°F°CDew psigpsiakPa gaugekPa absolutebar absoluteBubble psig
-60-51.1V 15.17.3-51500.50V 7.3
-55-48.3V 12.78.5-43580.58V 3.9
-50-45.6V 10.09.8-34670.67V 0.3
-45-42.8V 7.111.2-24770.771.9
-40-40.0V 3.712.9-13890.894.1
-35-37.2V 0.114.7-01011.016.6
-30-34.42.016.7141151.159.3
-25-31.74.218.9291301.3012.2
-20-28.96.721.3461471.4715.4
-15-26.19.324.0641661.6618.9
-10-23.312.327.0851861.8622.7
-5-20.615.530.21072082.0826.9
0-17.819.033.71312322.3231.4
5-15.022.837.51572592.5936.2
10-12.226.941.61862872.8741.4
15-9.431.446.12173183.1847.0
20-6.736.350.92503513.5153.0
25-3.941.556.22863873.8759.4
30-1.147.161.83254264.2666.3
351.753.167.83664684.6873.6
404.459.674.34115125.1281.4
457.266.581.24595605.6089.7
5010.073.988.65106116.1198.6
5512.881.996.65646666.66108
6015.690.3105.06237247.24118
6518.399.3114.06857867.86128
7021.1109123.67518528.52139
7523.9119133.78219229.22151
8026.7130144.58959969.96164
8529.4141156.0974107510.75177
9032.2153168.11058115911.59190
9535.0166180.91146124712.47205
10037.8180194.51240134113.41220
10540.6194208.81338144014.40235
11043.3209223.91443154415.44252
11546.1225239.91553165416.54269
12048.9242256.71669177017.70287
12551.7260274.51791189218.92306
13054.4278293.21920202120.21326

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.