Refrigerant · HCFC blend

R-401A pressure-temperature chart and data

R-22 / R-152a / R-124. Safety class A1, GWP 1,182. Retrofit for R-12 (medium temperature).

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-401A data sheet

Made ofR-22 53 / R-152a 13 / R-124 34 (mass %)
TypeHCFC blend
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)0.037
Global warming (GWP, 100 yr)1,182
Boils at 1 atm-27.5 °F (-33.1 °C)
Critical temperature227.1 °F (108.4 °C)
Temperature glideabout 10.5 °F
Low side at 5 °F evaporating9.8 psig (68 kPa)
High side at 86 °F condensing114 psig (787 kPa)
Old cylinder colourCoral
OilAB / POE
Used forRetrofit for R-12 (medium temperature).

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-401A pressure / temperature chart

°F°CDew psig (vapour)Bubble psig (liquid)Dew kPaBubble kPa
-60-51.1V 21.3V 17.5-72-59
-59-50.6V 21.0V 17.1-71-58
-58-50.0V 20.7V 16.8-70-57
-57-49.4V 20.4V 16.4-69-55
-56-48.9V 20.1V 16.0-68-54
-55-48.3V 19.8V 15.6-67-53
-54-47.8V 19.5V 15.1-66-51
-53-47.2V 19.1V 14.7-65-50
-52-46.7V 18.8V 14.3-64-48
-51-46.1V 18.4V 13.8-62-47
-50-45.6V 18.1V 13.4-61-45
-49-45.0V 17.7V 12.9-60-44
-48-44.4V 17.4V 12.4-59-42
-47-43.9V 17.0V 11.9-58-40
-46-43.3V 16.6V 11.4-56-39
-45-42.8V 16.2V 10.9-55-37
-44-42.2V 15.8V 10.4-53-35
-43-41.7V 15.4V 9.9-52-33
-42-41.1V 14.9V 9.3-51-32
-41-40.6V 14.5V 8.8-49-30
-40-40.0V 14.0V 8.2-48-28
-39-39.4V 13.6V 7.6-46-26
-38-38.9V 13.1V 7.0-44-24
-37-38.3V 12.6V 6.4-43-22
-36-37.8V 12.1V 5.8-41-20
-35-37.2V 11.6V 5.2-39-17
-34-36.7V 11.1V 4.5-38-15
-33-36.1V 10.6V 3.8-36-13
-32-35.6V 10.0V 3.2-34-11
-31-35.0V 9.5V 2.5-32-8
-30-34.4V 8.9V 1.8-30-6
-29-33.9V 8.3V 1.1-28-4
-28-33.3V 7.8V 0.3-26-1
-27-32.8V 7.20.2-241
-26-32.2V 6.50.6-224
-25-31.7V 5.90.9-206
-24-31.1V 5.31.3-189
-23-30.6V 4.61.7-1612
-22-30.0V 3.92.1-1315
-21-29.4V 3.32.5-1118
-20-28.9V 2.63.0-920
-19-28.3V 1.93.4-623
-18-27.8V 1.13.8-426
-17-27.2V 0.44.3-129
-16-26.70.24.7132
-15-26.10.65.2436
-14-25.60.95.6639
-13-25.01.36.1942
-12-24.41.76.61245
-11-23.92.17.11549
-10-23.32.57.61852
-9-22.83.08.12056
-8-22.23.48.62359
-7-21.73.89.12663
-6-21.14.39.73067
-5-20.64.810.23370
-4-20.05.210.83674
-3-19.45.711.33978
-2-18.96.211.94382
-1-18.36.712.54686
0-17.87.213.14990
1-17.27.713.75394
2-16.78.214.35699
3-16.18.714.960103
4-15.69.315.664107
5-15.09.816.268112
6-14.410.416.971116
7-13.910.917.575121
8-13.311.518.279125
9-12.812.118.983130
10-12.212.719.687135
11-11.713.320.392140
12-11.113.921.096145
13-10.614.621.7100150
14-10.015.222.5105155
15-9.415.823.2109160
16-8.916.524.0114166
17-8.317.224.8118171
18-7.817.925.6123176
19-7.218.626.4128182
20-6.719.327.2133188
21-6.120.028.0138193
22-5.620.728.9143199
23-5.021.429.7148205
24-4.422.230.6153211
25-3.922.931.5158217
26-3.323.732.4164223
27-2.824.533.3169229
28-2.225.334.2175236
29-1.726.135.1180242
30-1.127.036.0186248
31-0.627.837.0192255
320.028.638.0198262
330.629.539.0203269
341.130.440.0210275
351.731.341.0216282
362.232.242.0222290
372.833.143.0228297
383.334.044.1235304
393.935.045.1241311
404.435.946.2248319
415.036.947.3255326
425.637.948.5261334
436.138.949.6268342
446.739.950.7275350
457.241.051.9282358
467.842.053.0290366
478.343.154.2297374
488.944.155.5304382
499.445.256.7312391
5010.046.357.9319399
5110.647.559.2327408
5211.148.660.4335417
5311.749.861.7343425
5412.250.963.0351435
5512.852.164.3359444
5613.353.365.7367453
5713.954.567.0376462
5814.455.868.4384472
5915.057.069.8393481
6015.658.371.2402491
6116.159.572.6411501
6216.760.974.0420510
6317.262.275.5429520
6417.863.577.0438531
6518.364.978.5447541
6618.966.280.0457551
6719.467.681.5466562
6820.069.083.0476573
6920.670.584.6486583
7021.171.986.2496594
7121.773.387.8506605
7222.274.889.4516616
7322.876.391.0526628
7423.377.892.7537639
7523.979.494.4547651
7624.480.996.1558662
7725.082.597.8569674
7825.684.199.5580686
7926.185.7101591698
8026.787.3103602711
8127.289.0105614723
8227.890.7107625735
8328.392.4109637748
8428.994.1110649761
8529.495.8112661774
8630.097.6114673787
8730.699.3116685800
8831.1101118697814
8931.7103120710827
9032.2105122723841
9132.8107124735855
9233.3109126748869
9333.9110128761883
9434.4112130775897
9535.0114132788911
9635.6116134802926
9736.1118136815941
9836.7120139829956
9937.2122141843971
10037.8124143858986
10138.31261458721001
10238.91291478861017
10339.41311509011032
10440.01331529161048
10540.61351549311064
10641.11371579461080
10741.71391599621097
10842.21421619771113
10942.81441649931130
11043.314616610091147
11143.914916910251164
11244.415117110411181
11345.015317410571198
11445.615617610741216
11546.115817910901233
11646.716118111071251
11747.216318411241269
11847.816618711421287
11948.316818911591306
12048.917119211771324
12149.417319511951343
12250.017619812131362
12350.617920012311381
12451.118120312491400
12551.718420612681420
12652.218720912861439
12752.818921213051459
12853.319221513241479
12953.919521713441499
13054.419822013631520

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-401A pressure in psig, psia, kPa and bar

°F°CDew psigpsiakPa gaugekPa absolutebar absoluteBubble psig
-60-51.1V 21.34.2-72290.29V 17.5
-55-48.3V 19.85.0-67340.34V 15.6
-50-45.6V 18.15.8-61400.40V 13.4
-45-42.8V 16.26.7-55470.47V 10.9
-40-40.0V 14.07.8-48540.54V 8.2
-35-37.2V 11.69.0-39620.62V 5.2
-30-34.4V 8.910.3-30710.71V 1.8
-25-31.7V 5.911.8-20810.810.9
-20-28.9V 2.613.4-9930.933.0
-15-26.10.615.241051.055.2
-10-23.32.517.2181191.197.6
-5-20.64.819.4331341.3410.2
0-17.87.221.9491511.5113.1
5-15.09.824.5681691.6916.2
10-12.212.727.4871891.8919.6
15-9.415.830.51092112.1123.2
20-6.719.333.91332342.3427.2
25-3.922.937.61582602.6031.5
30-1.127.041.71862872.8736.0
351.731.346.02163173.1741.0
404.435.950.62483493.4946.2
457.241.055.62823843.8451.9
5010.046.361.03194214.2157.9
5512.852.166.83594614.6164.3
6015.658.373.04025035.0371.2
6518.364.979.64475495.4978.5
7021.171.986.64965975.9786.2
7523.979.494.15476496.4994.4
8026.787.3102.06027047.04103
8529.495.8110.56617627.62112
9032.2105119.57238248.24122
9535.0114129.07888898.89132
10037.8124139.18589599.59143
10540.6135149.7931103210.32154
11043.3146161.01009111011.10166
11546.1158172.81090119211.92179
12048.9171185.41177127812.78192
12551.7184198.51268136913.69206
13054.4198212.41363146514.65220

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.