Refrigerant · HFC

R-32 pressure-temperature chart and data

Difluoromethane. Safety class A2L, GWP 675. New residential and commercial A/C and heat pumps. Mildly flammable, so follow the equipment maker’s charge limits and A2L rules.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-32 data sheet

NameDifluoromethane
TypeHFC
Safety classA2L — lower toxicity, mildly flammable (burns slowly)
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)675
Boils at 1 atm-61 °F (-51.7 °C)
Critical temperature172.6 °F (78.1 °C)
Temperature glidenone / very small
Low side at 5 °F evaporating56.1 psig (387 kPa)
High side at 86 °F condensing265 psig (1826 kPa)
Old cylinder colourLight blue-green
OilPOE (PVE in some)
Used forNew residential and commercial A/C and heat pumps. Mildly flammable, so follow the equipment maker’s charge limits and A2L rules.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-32 pressure / temperature chart

°F°CpsigkPa
-60-51.10.43
-59-50.60.86
-58-50.01.39
-57-49.41.712
-56-48.92.215
-55-48.32.718
-54-47.83.122
-53-47.23.625
-52-46.74.128
-51-46.14.632
-50-45.65.236
-49-45.05.739
-48-44.46.243
-47-43.96.847
-46-43.37.451
-45-42.88.055
-44-42.28.559
-43-41.79.263
-42-41.19.867
-41-40.610.472
-40-40.011.076
-39-39.411.781
-38-38.912.485
-37-38.313.090
-36-37.813.795
-35-37.214.4100
-34-36.715.2105
-33-36.115.9110
-32-35.616.6115
-31-35.017.4120
-30-34.418.2125
-29-33.919.0131
-28-33.319.8136
-27-32.820.6142
-26-32.221.4148
-25-31.722.3154
-24-31.123.2160
-23-30.624.1166
-22-30.025.0172
-21-29.425.9178
-20-28.926.8185
-19-28.327.8191
-18-27.828.7198
-17-27.229.7205
-16-26.730.7212
-15-26.131.7219
-14-25.632.8226
-13-25.033.8233
-12-24.434.9241
-11-23.936.0248
-10-23.337.1256
-9-22.838.2264
-8-22.239.4271
-7-21.740.5280
-6-21.141.7288
-5-20.642.9296
-4-20.044.1304
-3-19.445.4313
-2-18.946.7322
-1-18.348.0331
0-17.849.3340
1-17.250.6349
2-16.751.9358
3-16.153.3367
4-15.654.7377
5-15.056.1387
6-14.457.5397
7-13.959.0407
8-13.360.5417
9-12.862.0427
10-12.263.5438
11-11.765.0448
12-11.166.6459
13-10.668.2470
14-10.069.8481
15-9.471.5493
16-8.973.1504
17-8.374.8516
18-7.876.5528
19-7.278.3540
20-6.780.0552
21-6.181.8564
22-5.683.6577
23-5.085.5589
24-4.487.3602
25-3.989.2615
26-3.391.1628
27-2.893.1642
28-2.295.1655
29-1.797.1669
30-1.199.1683
31-0.6101697
320.0103712
330.6105726
341.1107741
351.7110756
362.2112771
372.8114787
383.3116802
393.9119818
404.4121834
415.0123850
425.6126867
436.1128883
446.7131900
457.2133917
467.8136934
478.3138952
488.9141969
499.4143987
5010.01461006
5110.61491024
5211.11511043
5311.71541061
5412.21571081
5512.81601100
5613.31621119
5713.91651139
5814.41681159
5915.01711179
6015.61741200
6116.11771221
6216.71801242
6317.21831263
6417.81861285
6518.31891306
6618.91931328
6719.41961351
6820.01991373
6920.62021396
7021.12061419
7121.72091442
7222.22131466
7322.82161490
7423.32201514
7523.92231539
7624.42271563
7725.02301588
7825.62341614
7926.12381639
8026.72411665
8127.22451691
8227.82491718
8328.32531744
8428.92571771
8529.42611799
8630.02651826
8730.62691854
8831.12731882
8931.72771911
9032.22811940
9132.82861969
9233.32901998
9333.92942028
9434.42992058
9535.03032088
9635.63072119
9736.13122150
9836.73162182
9937.23212213
10037.83262245
10138.33302278
10238.93352311
10339.43402344
10440.03452377
10540.63502411
10641.13552445
10741.73602479
10842.23652514
10942.83702549
11043.33752585
11143.93802621
11244.43852657
11345.03912693
11445.63962730
11546.14012768
11646.74072805
11747.24122844
11847.84182882
11948.34242921
12048.94292960
12149.44353000
12250.04413040
12350.64473080
12451.14533121
12551.74593162
12652.24653204
12752.84713246
12853.34773289
12953.94833331
13054.44893375

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-32 pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-60-51.10.415.131041.04
-55-48.32.717.4181201.20
-50-45.65.219.9361371.37
-45-42.88.022.6551561.56
-40-40.011.025.7761771.77
-35-37.214.429.11002012.01
-30-34.418.232.91252272.27
-25-31.722.337.01542552.55
-20-28.926.841.51852862.86
-15-26.131.746.42193203.20
-10-23.337.151.82563573.57
-5-20.642.957.62963973.97
0-17.849.363.93404414.41
5-15.056.170.83874884.88
10-12.263.578.24385395.39
15-9.471.586.14935945.94
20-6.780.094.75526536.53
25-3.989.2103.96157167.16
30-1.199.1113.86837857.85
351.7110124.47568578.57
404.4121135.68349359.35
457.2133147.7917101810.18
5010.0146160.51006110711.07
5512.8160174.21100120112.01
6015.6174188.71200130113.01
6518.3189204.21306140814.08
7021.1206220.51419152015.20
7523.9223237.81539164016.40
8026.7241256.21665176617.66
8529.4261275.61799190019.00
9032.2281296.01940204120.41
9535.0303317.62088219021.90
10037.8326340.42245234723.47
10540.6350364.32411251225.12
11043.3375389.62585268626.86
11546.1401416.12768286928.69
12048.9429444.02960306230.62
12551.7459473.43162326432.64
13054.4489504.23375347634.76

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.