Refrigerant · CFC

R-11 pressure-temperature chart and data

Trichlorofluoromethane. Safety class A1, GWP 4,750. Old low-pressure centrifugal chillers. Banned; recovery only. Replaced by R-123.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-11 data sheet

NameTrichlorofluoromethane
TypeCFC
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)1
Global warming (GWP, 100 yr)4,750
Boils at 1 atm74.7 °F (23.7 °C)
Critical temperature388.3 °F (197.9 °C)
Temperature glidenone / very small
Low side at 5 °F evaporatingV 24.0 psig (-81 kPa)
High side at 86 °F condensing3.6 psig (25 kPa)
Old cylinder colourOrange
OilMineral / AB
Used forOld low-pressure centrifugal chillers. Banned; recovery only. Replaced by R-123.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-11 pressure / temperature chart

°F°CpsigkPa
-50-45.6V 28.9-98
-49-45.0V 28.8-98
-48-44.4V 28.8-97
-47-43.9V 28.7-97
-46-43.3V 28.7-97
-45-42.8V 28.7-97
-44-42.2V 28.6-97
-43-41.7V 28.6-97
-42-41.1V 28.5-97
-41-40.6V 28.5-96
-40-40.0V 28.4-96
-39-39.4V 28.4-96
-38-38.9V 28.3-96
-37-38.3V 28.3-96
-36-37.8V 28.2-95
-35-37.2V 28.1-95
-34-36.7V 28.1-95
-33-36.1V 28.0-95
-32-35.6V 28.0-95
-31-35.0V 27.9-94
-30-34.4V 27.8-94
-29-33.9V 27.8-94
-28-33.3V 27.7-94
-27-32.8V 27.6-93
-26-32.2V 27.5-93
-25-31.7V 27.4-93
-24-31.1V 27.4-93
-23-30.6V 27.3-92
-22-30.0V 27.2-92
-21-29.4V 27.1-92
-20-28.9V 27.0-92
-19-28.3V 26.9-91
-18-27.8V 26.9-91
-17-27.2V 26.8-91
-16-26.7V 26.7-90
-15-26.1V 26.5-90
-14-25.6V 26.4-90
-13-25.0V 26.3-89
-12-24.4V 26.2-89
-11-23.9V 26.1-88
-10-23.3V 26.0-88
-9-22.8V 25.9-88
-8-22.2V 25.8-87
-7-21.7V 25.7-87
-6-21.1V 25.5-86
-5-20.6V 25.4-86
-4-20.0V 25.3-86
-3-19.4V 25.1-85
-2-18.9V 25.0-85
-1-18.3V 24.9-84
0-17.8V 24.7-84
1-17.2V 24.6-83
2-16.7V 24.4-83
3-16.1V 24.3-82
4-15.6V 24.1-82
5-15.0V 24.0-81
6-14.4V 23.8-81
7-13.9V 23.6-80
8-13.3V 23.5-79
9-12.8V 23.3-79
10-12.2V 23.1-78
11-11.7V 22.9-78
12-11.1V 22.7-77
13-10.6V 22.5-76
14-10.0V 22.3-76
15-9.4V 22.1-75
16-8.9V 21.9-74
17-8.3V 21.7-74
18-7.8V 21.5-73
19-7.2V 21.3-72
20-6.7V 21.1-71
21-6.1V 20.8-71
22-5.6V 20.6-70
23-5.0V 20.4-69
24-4.4V 20.2-68
25-3.9V 19.9-67
26-3.3V 19.6-67
27-2.8V 19.4-66
28-2.2V 19.1-65
29-1.7V 18.9-64
30-1.1V 18.6-63
31-0.6V 18.3-62
320.0V 18.1-61
330.6V 17.8-60
341.1V 17.5-59
351.7V 17.2-58
362.2V 16.9-57
372.8V 16.6-56
383.3V 16.2-55
393.9V 15.9-54
404.4V 15.6-53
415.0V 15.3-52
425.6V 14.9-51
436.1V 14.6-49
446.7V 14.3-48
457.2V 13.9-47
467.8V 13.5-46
478.3V 13.2-45
488.9V 12.8-43
499.4V 12.4-42
5010.0V 12.0-41
5110.6V 11.6-39
5211.1V 11.2-38
5311.7V 10.8-37
5412.2V 10.4-35
5512.8V 10.0-34
5613.3V 9.5-32
5713.9V 9.1-31
5814.4V 8.6-29
5915.0V 8.2-28
6015.6V 7.7-26
6116.1V 7.2-25
6216.7V 6.8-23
6317.2V 6.3-21
6417.8V 5.8-20
6518.3V 5.3-18
6618.9V 4.8-16
6719.4V 4.3-14
6820.0V 3.7-13
6920.6V 3.2-11
7021.1V 2.6-9
7121.7V 2.1-7
7222.2V 1.5-5
7322.8V 1.0-3
7423.3V 0.4-1
7523.90.11
7624.40.43
7725.00.75
7825.61.07
7926.11.39
8026.71.611
8127.21.913
8227.82.215
8328.32.618
8428.92.920
8529.43.222
8630.03.625
8730.63.927
8831.14.329
8931.74.632
9032.25.034
9132.85.337
9233.35.739
9333.96.142
9434.46.545
9535.06.947
9635.67.350
9736.17.753
9836.78.156
9937.28.558
10037.88.961
10138.39.364
10238.99.767
10339.410.270
10440.010.673
10540.611.176
10641.111.579
10741.711.982
10842.212.486
10942.812.989
11043.313.492
11143.913.895
11244.414.399
11345.014.8102
11445.615.3106
11546.115.8109
11646.716.3113
11747.216.9116
11847.817.4120
11948.317.9123
12048.918.4127
12149.419.0131
12250.019.6135
12350.620.1139
12451.120.7143
12551.721.3147
12652.221.8151
12752.822.4155
12853.323.0159
12953.923.6163
13054.424.2167

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-11 pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-50-45.6V 28.90.5-9840.04
-45-42.8V 28.70.6-9740.04
-40-40.0V 28.40.7-9650.05
-35-37.2V 28.10.9-9560.06
-30-34.4V 27.81.0-9470.07
-25-31.7V 27.41.2-9380.08
-20-28.9V 27.01.4-92100.10
-15-26.1V 26.51.7-90110.11
-10-23.3V 26.01.9-88130.13
-5-20.6V 25.42.2-86150.15
0-17.8V 24.72.6-84180.18
5-15.0V 24.02.9-81200.20
10-12.2V 23.13.4-78230.23
15-9.4V 22.13.8-75260.26
20-6.7V 21.14.3-71300.30
25-3.9V 19.94.9-67340.34
30-1.1V 18.65.6-63380.38
351.7V 17.26.3-58430.43
404.4V 15.67.0-53480.48
457.2V 13.97.9-47540.54
5010.0V 12.08.8-41610.61
5512.8V 10.09.8-34680.68
6015.6V 7.710.9-26750.75
6518.3V 5.312.1-18830.83
7021.1V 2.613.4-9920.92
7523.90.114.811021.02
8026.71.616.3111121.12
8529.43.217.9221241.24
9032.25.019.7341361.36
9535.06.921.6471491.49
10037.88.923.6611631.63
10540.611.125.7761781.78
11043.313.428.1921931.93
11546.115.830.51092102.10
12048.918.433.11272292.29
12551.721.335.91472482.48
13054.424.238.91672682.68

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.