Refrigerant · HFC blend

R-407A pressure-temperature chart and data

R-32 / R-125 / R-134a. Safety class A1, GWP 2,107. Commercial refrigeration (medium and low temperature); replaced R-22 and R-404A.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-407A data sheet

Made ofR-32 20 / R-125 40 / R-134a 40 (mass %)
TypeHFC blend
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)2,107
Boils at 1 atm-49 °F (-45.0 °C)
Critical temperature180 °F (82.2 °C)
Temperature glideabout 10.4 °F
Low side at 5 °F evaporating26.9 psig (185 kPa)
High side at 86 °F condensing193 psig (1328 kPa)
Old cylinder colourLime green
OilPOE
Used forCommercial refrigeration (medium and low temperature); replaced R-22 and R-404A.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-407A pressure / temperature chart

°F°CDew psig (vapour)Bubble psig (liquid)Dew kPaBubble kPa
-60-51.1V 14.5V 7.9-49-27
-59-50.6V 14.0V 7.2-47-24
-58-50.0V 13.5V 6.6-46-22
-57-49.4V 12.9V 5.9-44-20
-56-48.9V 12.4V 5.2-42-18
-55-48.3V 11.9V 4.5-40-15
-54-47.8V 11.3V 3.8-38-13
-53-47.2V 10.8V 3.1-36-10
-52-46.7V 10.2V 2.3-34-8
-51-46.1V 9.6V 1.6-32-5
-50-45.6V 9.0V 0.8-30-3
-49-45.0V 8.30.0-280
-48-44.4V 7.70.4-263
-47-43.9V 7.00.8-246
-46-43.3V 6.41.2-228
-45-42.8V 5.71.7-1911
-44-42.2V 5.02.1-1714
-43-41.7V 4.32.5-1418
-42-41.1V 3.53.0-1221
-41-40.6V 2.83.5-924
-40-40.0V 2.03.9-727
-39-39.4V 1.24.4-430
-38-38.9V 0.44.9-134
-37-38.30.25.4137
-36-37.80.65.9441
-35-37.21.06.4744
-34-36.71.47.01048
-33-36.11.97.51352
-32-35.62.38.11656
-31-35.02.88.61960
-30-34.43.39.22264
-29-33.93.79.82667
-28-33.34.210.42972
-27-32.84.711.03376
-26-32.25.211.63680
-25-31.75.812.34084
-24-31.16.312.94389
-23-30.66.813.64793
-22-30.07.414.25198
-21-29.47.914.955103
-20-28.98.515.659107
-19-28.39.116.363112
-18-27.89.717.067117
-17-27.210.317.771122
-16-26.710.918.575127
-15-26.111.519.279133
-14-25.612.220.084138
-13-25.012.820.888143
-12-24.413.521.693149
-11-23.914.222.498154
-10-23.314.923.2102160
-9-22.815.624.0107166
-8-22.216.324.9112172
-7-21.717.025.8117178
-6-21.117.826.6122184
-5-20.618.527.5128190
-4-20.019.328.4133196
-3-19.420.129.4138202
-2-18.920.930.3144209
-1-18.321.731.3149216
0-17.822.532.2155222
1-17.223.433.2161229
2-16.724.234.2167236
3-16.125.135.2173243
4-15.626.036.3179250
5-15.026.937.3185257
6-14.427.838.4192265
7-13.928.739.5198272
8-13.329.740.6204280
9-12.830.641.7211287
10-12.231.642.8218295
11-11.732.644.0225303
12-11.133.645.1232311
13-10.634.646.3239319
14-10.035.747.5246328
15-9.436.848.8253336
16-8.937.850.0261345
17-8.338.951.2268353
18-7.840.052.5276362
19-7.241.253.8284371
20-6.742.355.1292380
21-6.143.556.5300389
22-5.644.757.8308399
23-5.045.959.2316408
24-4.447.160.6325418
25-3.948.462.0333427
26-3.349.663.4342437
27-2.850.964.9351447
28-2.252.266.3360457
29-1.753.567.8369468
30-1.154.869.3378478
31-0.656.270.9387489
320.057.672.4397499
330.659.074.0407510
341.160.475.6416521
351.761.877.2426532
362.263.378.8436544
372.864.880.5447555
383.366.382.2457567
393.967.883.9468578
404.469.485.6478590
415.070.987.4489602
425.672.589.2500615
436.174.190.9511627
446.775.892.8522640
457.277.494.6534652
467.879.196.5546665
478.380.898.4557678
488.982.5100569691
499.484.3102581705
5010.086.1104594718
5110.687.9106606732
5211.189.7108619746
5311.791.6110631760
5412.293.4112644774
5512.895.3114657788
5613.397.3116671803
5713.999.2119684818
5814.4101121698833
5915.0103123711848
6015.6105125725863
6116.1107127740878
6216.7109130754894
6317.2111132768910
6417.8114134783926
6518.3116137798942
6618.9118139813959
6719.4120141828975
6820.0122144844992
6920.61251468601009
7021.11271498751026
7121.71291518911043
7222.21321549081061
7322.81341569241079
7423.31361599411097
7523.91391629581115
7624.41411649751133
7725.01441679921152
7825.614617010101171
7926.114917310271189
8026.715217510451209
8127.215417810631228
8227.815718110821248
8328.316018411001267
8428.916218711191288
8529.416519011381308
8630.016819311571328
8730.617119611771349
8831.117419911961370
8931.717620212161391
9032.217920512361412
9132.818220812571434
9233.318521112771456
9333.918821412981478
9434.419121813191500
9535.019422113411523
9635.619822413621545
9736.120122713841568
9836.720423114061591
9937.220723414281615
10037.821023814511639
10138.321424114741662
10238.921724514971687
10339.422024815201711
10440.022425215441736
10540.622725515681761
10641.123125915921786
10741.723426316161811
10842.223826616411837
10942.824227016661863
11043.324527416911889
11143.924927817161915
11244.425328217421942
11345.025628617681969
11445.626028917941996
11546.126429318212023
11646.726829718482051
11747.227230218752079
11847.827630619022107
11948.328031019302136
12048.928431419582165
12149.428831819872194
12250.029232220152223
12350.629632720442253
12451.130133120732283
12551.730533521032313
12652.230934021332343
12752.831434421632374
12853.331834921932405
12953.932335322242436
13054.432735822562468

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-407A pressure in psig, psia, kPa and bar

°F°CDew psigpsiakPa gaugekPa absolutebar absoluteBubble psig
-60-51.1V 14.57.6-49520.52V 7.9
-55-48.3V 11.98.9-40610.61V 4.5
-50-45.6V 9.010.3-30710.71V 0.8
-45-42.8V 5.711.9-19820.821.7
-40-40.0V 2.013.7-7940.943.9
-35-37.21.015.771081.086.4
-30-34.43.318.0221241.249.2
-25-31.75.820.4401411.4112.3
-20-28.98.523.2591601.6015.6
-15-26.111.526.2791811.8119.2
-10-23.314.929.61022042.0423.2
-5-20.618.533.21282292.2927.5
0-17.822.537.21552572.5732.2
5-15.026.941.61852872.8737.3
10-12.231.646.32183193.1942.8
15-9.436.851.42533553.5548.8
20-6.742.357.02923933.9355.1
25-3.948.463.03334354.3562.0
30-1.154.869.53784794.7969.3
351.761.876.54265285.2877.2
404.469.484.14785805.8085.6
457.277.492.15346356.3594.6
5010.086.1100.85946956.95104
5512.895.3110.06577597.59114
6015.6105119.97258278.27125
6518.3116130.47988998.99137
7021.1127141.78759779.77149
7523.9139153.6958105910.59162
8026.7152166.31045114711.47175
8529.4165179.81138123912.39190
9032.2179194.01236133813.38205
9535.0194209.11341144214.42221
10037.8210225.11451155215.52238
10540.6227242.11568166916.69255
11043.3245259.91691179217.92274
11546.1264278.81821192219.22293
12048.9284298.71958206020.60314
12551.7305319.72103220422.04335
13054.4327341.82256235723.57358

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.