Refrigerant · CFC blend

R-500 pressure-temperature chart and data

R-12 / R-152a. Safety class A1, GWP 8,077. Old A/C and chillers. Banned; recovery only.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-500 data sheet

Made ofR-12 73.8 / R-152a 26.2 (mass %)
TypeCFC blend
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)0.738
Global warming (GWP, 100 yr)8,077
Boils at 1 atm-29.1 °F (-33.9 °C)
Critical temperature214.7 °F (101.5 °C)
Temperature glidenone / very small
Low side at 5 °F evaporating16.9 psig (117 kPa)
High side at 86 °F condensing114 psig (787 kPa)
Old cylinder colourYellow
OilMineral / AB
Used forOld A/C and chillers. Banned; recovery only.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-500 pressure / temperature chart

°F°CpsigkPa
-60-51.1V 16.9-57
-59-50.6V 16.5-56
-58-50.0V 16.2-55
-57-49.4V 15.7-53
-56-48.9V 15.3-52
-55-48.3V 14.9-51
-54-47.8V 14.5-49
-53-47.2V 14.0-48
-52-46.7V 13.6-46
-51-46.1V 13.1-44
-50-45.6V 12.6-43
-49-45.0V 12.2-41
-48-44.4V 11.7-40
-47-43.9V 11.2-38
-46-43.3V 10.6-36
-45-42.8V 10.1-34
-44-42.2V 9.6-32
-43-41.7V 9.0-31
-42-41.1V 8.5-29
-41-40.6V 7.9-27
-40-40.0V 7.3-25
-39-39.4V 6.7-23
-38-38.9V 6.1-21
-37-38.3V 5.5-19
-36-37.8V 4.8-16
-35-37.2V 4.2-14
-34-36.7V 3.6-12
-33-36.1V 2.9-10
-32-35.6V 2.2-7
-31-35.0V 1.5-5
-30-34.4V 0.8-3
-29-33.9V 0.0-0
-28-33.30.32
-27-32.80.75
-26-32.21.18
-25-31.71.510
-24-31.11.913
-23-30.62.316
-22-30.02.718
-21-29.43.121
-20-28.93.524
-19-28.34.027
-18-27.84.430
-17-27.24.833
-16-26.75.336
-15-26.15.840
-14-25.66.243
-13-25.06.746
-12-24.47.250
-11-23.97.753
-10-23.38.257
-9-22.88.760
-8-22.29.364
-7-21.79.867
-6-21.110.371
-5-20.610.975
-4-20.011.479
-3-19.412.083
-2-18.912.687
-1-18.313.291
0-17.813.895
1-17.214.499
2-16.715.0103
3-16.115.6108
4-15.616.3112
5-15.016.9117
6-14.417.6121
7-13.918.2126
8-13.318.9130
9-12.819.6135
10-12.220.3140
11-11.721.0145
12-11.121.8150
13-10.622.5155
14-10.023.2160
15-9.424.0165
16-8.924.8171
17-8.325.5176
18-7.826.3182
19-7.227.1187
20-6.727.9193
21-6.128.8198
22-5.629.6204
23-5.030.5210
24-4.431.3216
25-3.932.2222
26-3.333.1228
27-2.834.0234
28-2.234.9241
29-1.735.9247
30-1.136.8254
31-0.637.8260
320.038.7267
330.639.7274
341.140.7281
351.741.7288
362.242.7295
372.843.8302
383.344.8309
393.945.9316
404.447.0324
415.048.0331
425.649.2339
436.150.3347
446.751.4355
457.252.6363
467.853.7371
478.354.9379
488.956.1387
499.457.3395
5010.058.6404
5110.659.8412
5211.161.1421
5311.762.3430
5412.263.6439
5512.864.9448
5613.366.3457
5713.967.6466
5814.469.0476
5915.070.3485
6015.671.7495
6116.173.1504
6216.774.6514
6317.276.0524
6417.877.5534
6518.378.9544
6618.980.4555
6719.482.0565
6820.083.5576
6920.685.0586
7021.186.6597
7121.788.2608
7222.289.8619
7322.891.4630
7423.393.0641
7523.994.7653
7624.496.4665
7725.098.1676
7825.699.8688
7926.1102700
8026.7103712
8127.2105724
8227.8107737
8328.3109749
8428.9110762
8529.4112775
8630.0114788
8730.6116801
8831.1118814
8931.7120827
9032.2122841
9132.8124854
9233.3126868
9333.9128882
9434.4130896
9535.0132910
9635.6134925
9736.1136939
9836.7138954
9937.2140969
10037.8143984
10138.3145999
10238.91471014
10339.41491029
10440.01521045
10540.61541061
10641.11561077
10741.71591093
10842.21611109
10942.81631125
11043.31661142
11143.91681159
11244.41711176
11345.01731193
11445.61751210
11546.11781227
11646.71811245
11747.21831263
11847.81861281
11948.31881299
12048.91911317
12149.41941335
12250.01961354
12350.61991373
12451.12021392
12551.72051411
12652.22071430
12752.82101450
12853.32131469
12953.92161489
13054.42191509

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-500 pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-60-51.1V 16.96.4-57440.44
-55-48.3V 14.97.4-51510.51
-50-45.6V 12.68.5-43590.59
-45-42.8V 10.19.7-34670.67
-40-40.0V 7.311.1-25770.77
-35-37.2V 4.212.6-14870.87
-30-34.4V 0.814.3-3990.99
-25-31.71.516.2101121.12
-20-28.93.518.2241261.26
-15-26.15.820.5401411.41
-10-23.38.222.9571581.58
-5-20.610.925.6751761.76
0-17.813.828.5951961.96
5-15.016.931.61172182.18
10-12.220.335.01402412.41
15-9.424.038.71652672.67
20-6.727.942.61932942.94
25-3.932.246.92223233.23
30-1.136.851.52543553.55
351.741.756.42883893.89
404.447.061.73244254.25
457.252.667.33634644.64
5010.058.673.34045055.05
5512.864.979.64485495.49
6015.671.786.44955965.96
6518.378.993.65446466.46
7021.186.6101.35976986.98
7523.994.7109.46537547.54
8026.7103118.07128138.13
8529.4112127.07758768.76
9032.2122136.68419429.42
9535.0132146.7910101210.12
10037.8143157.3984108510.85
10540.6154168.61061116211.62
11043.3166180.31142124312.43
11546.1178192.71227132913.29
12048.9191205.71317141814.18
12551.7205219.31411151215.12
13054.4219233.61509161116.11

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.