Refrigerant · HCFC blend

R-408A pressure-temperature chart and data

R-125 / R-143a / R-22. Safety class A1, GWP 3,152. Retrofit for R-502.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-408A data sheet

Made ofR-125 7 / R-143a 46 / R-22 47 (mass %)
TypeHCFC blend
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)0.026
Global warming (GWP, 100 yr)3,152
Boils at 1 atm-47.6 °F (-44.2 °C)
Critical temperature182.6 °F (83.7 °C)
Temperature glidenone / very small
Low side at 5 °F evaporating33.6 psig (232 kPa)
High side at 86 °F condensing176 psig (1212 kPa)
Old cylinder colourMedium purple
OilAB / POE
Used forRetrofit for R-502.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-408A pressure / temperature chart

°F°CDew psig (vapour)Bubble psig (liquid)Dew kPaBubble kPa
-60-51.1V 9.0V 8.5-31-29
-59-50.6V 8.4V 7.9-29-27
-58-50.0V 7.8V 7.3-26-25
-57-49.4V 7.2V 6.7-24-23
-56-48.9V 6.6V 6.0-22-20
-55-48.3V 5.9V 5.4-20-18
-54-47.8V 5.2V 4.7-18-16
-53-47.2V 4.6V 4.0-15-14
-52-46.7V 3.8V 3.3-13-11
-51-46.1V 3.1V 2.6-11-9
-50-45.6V 2.4V 1.8-8-6
-49-45.0V 1.7V 1.1-6-4
-48-44.4V 0.9V 0.3-3-1
-47-43.9V 0.10.2-02
-46-43.30.30.624
-45-42.80.71.057
-44-42.21.11.4810
-43-41.71.51.91113
-42-41.12.02.31416
-41-40.62.42.71619
-40-40.02.83.21922
-39-39.43.33.62325
-38-38.93.74.12628
-37-38.34.24.52931
-36-37.84.75.03235
-35-37.25.25.53638
-34-36.75.66.03942
-33-36.16.26.54245
-32-35.66.77.04649
-31-35.07.27.65052
-30-34.47.78.15356
-29-33.98.38.75760
-28-33.38.89.26164
-27-32.89.49.86567
-26-32.29.910.46971
-25-31.710.510.97375
-24-31.111.111.67780
-23-30.611.712.28184
-22-30.012.312.88588
-21-29.413.013.48992
-20-28.913.614.19497
-19-28.314.314.798101
-18-27.814.915.4103106
-17-27.215.616.1107111
-16-26.716.316.7112115
-15-26.117.017.4117120
-14-25.617.718.2122125
-13-25.018.418.9127130
-12-24.419.119.6132135
-11-23.919.920.4137140
-10-23.320.621.1142146
-9-22.821.421.9147151
-8-22.222.222.7153157
-7-21.723.023.5158162
-6-21.123.824.3164168
-5-20.624.625.1170173
-4-20.025.426.0175179
-3-19.426.326.8181185
-2-18.927.127.7187191
-1-18.328.028.6193197
0-17.828.929.5199203
1-17.229.830.4206210
2-16.730.731.3212216
3-16.131.732.3218222
4-15.632.633.2225229
5-15.033.634.2231236
6-14.434.535.2238242
7-13.935.536.2245249
8-13.336.537.2252256
9-12.837.638.2259263
10-12.238.639.3266271
11-11.739.640.3273278
12-11.140.741.4281285
13-10.641.842.5288293
14-10.042.943.6296300
15-9.444.044.7304308
16-8.945.145.8311316
17-8.346.347.0319324
18-7.847.548.2327332
19-7.248.649.4335340
20-6.749.850.6344349
21-6.151.151.8352357
22-5.652.353.0361366
23-5.053.554.3369374
24-4.454.855.6378383
25-3.956.156.9387392
26-3.357.458.2396401
27-2.858.759.5405410
28-2.260.160.8414419
29-1.761.462.2423429
30-1.162.863.6433438
31-0.664.265.0443448
320.065.666.4452458
330.667.067.9462468
341.168.569.3472478
351.770.070.8482488
362.271.572.3493498
372.873.073.8503509
383.374.575.3514520
393.976.076.9524530
404.477.678.5535541
415.079.280.1546552
425.680.881.7557563
436.182.583.3568575
446.784.185.0580586
457.285.886.7591598
467.887.588.4603609
478.389.290.1615621
488.990.991.9627633
499.492.793.6639645
5010.094.595.4651658
5110.696.397.2664670
5211.198.199.1676683
5311.7100.0101689696
5412.2102103702709
5512.8104105715722
5613.3106107728735
5713.9108109742748
5814.4110111755762
5915.0112113769776
6015.6114115783790
6116.1116117797804
6216.7118119811818
6317.2120121825832
6417.8122123840847
6518.3124125854862
6618.9126127869877
6719.4128129884892
6820.0130132899907
6920.6133134915922
7021.1135136930938
7121.7137138946954
7222.2140141962970
7322.8142143978986
7423.31441459941002
7523.914714810111018
7624.414915010271035
7725.015115310441052
7825.615415510611069
7926.115615810781086
8026.715916010961104
8127.216116311131121
8227.816416511311139
8328.316716811491157
8428.916917011671175
8529.417217311851194
8630.017517612041212
8730.617717912231231
8831.118018112411250
8931.718318412611269
9032.218618712801288
9132.818819012991308
9233.319119313191328
9333.919419513391348
9434.419719813591368
9535.020020113801388
9635.620320414001409
9736.120620714211430
9836.720921014421451
9937.221221314631472
10037.821521714841493
10138.321822015061515
10238.922222315281537
10339.422522615501559
10440.022822915721581
10540.623123315951604
10641.123523616171627
10741.723823916401650
10842.224124316641673
10942.824524616871696
11043.324824917111720
11143.925225317341744
11244.425525617591768
11345.025926017831792
11445.626226418081817
11546.126626718321842
11646.726927118571867
11747.227327418831892
11847.827727819081918
11948.328128219341944
12048.928428619601970
12149.428829019861996
12250.029229320132023
12350.629629720402050
12451.130030120672077
12551.730430520942104
12652.230830921222132
12752.831231321502160
12853.331631721782188
12953.932032122062216
13054.432432622352245

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-408A pressure in psig, psia, kPa and bar

°F°CDew psigpsiakPa gaugekPa absolutebar absoluteBubble psig
-60-51.1V 9.010.3-31710.71V 8.5
-55-48.3V 5.911.8-20810.81V 5.4
-50-45.6V 2.413.5-8930.93V 1.8
-45-42.80.715.451061.061.0
-40-40.02.817.5191211.213.2
-35-37.25.219.8361371.375.5
-30-34.47.722.4531541.548.1
-25-31.710.525.2731741.7410.9
-20-28.913.628.3941951.9514.1
-15-26.117.031.71172182.1817.4
-10-23.320.635.31422432.4321.1
-5-20.624.639.31702712.7125.1
0-17.828.943.61993013.0129.5
5-15.033.648.32313333.3334.2
10-12.238.653.32663673.6739.3
15-9.444.058.73044054.0544.7
20-6.749.864.53444454.4550.6
25-3.956.170.83874884.8856.9
30-1.162.877.54335345.3463.6
351.770.084.74825845.8470.8
404.477.692.35356366.3678.5
457.285.8100.55916936.9386.7
5010.094.5109.26517537.5395.4
5512.8104118.47158168.16105
6015.6114128.27838848.84115
6518.3124138.68549569.56125
7021.1135149.6930103210.32136
7523.9147161.31011111211.12148
8026.7159173.61096119711.97160
8529.4172186.61185128712.87173
9032.2186200.31280138113.81187
9535.0200214.81380148114.81201
10037.8215230.01484158615.86217
10540.6231246.01595169616.96233
11043.3248262.81711181218.12249
11546.1266280.51832193419.34267
12048.9284299.01960206220.62286
12551.7304318.42094219621.96305
13054.4324338.82235233623.36326

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.