Refrigerant · Natural

R-717 pressure-temperature chart and data

Ammonia. Safety class B2L, GWP 0. Industrial refrigeration. Toxic and attacks copper and brass; steel piping only.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-717 data sheet

NameAmmonia
TypeNatural
Safety classB2L — higher toxicity, mildly flammable
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)0
Boils at 1 atm-28 °F (-33.3 °C)
Critical temperature270.3 °F (132.4 °C)
Temperature glidenone / very small
Low side at 5 °F evaporating19.5 psig (134 kPa)
High side at 86 °F condensing155 psig (1065 kPa)
Old cylinder colourSilver
OilMineral / PAO
Used forIndustrial refrigeration. Toxic and attacks copper and brass; steel piping only.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-717 pressure / temperature chart

°F°CpsigkPa
-60-51.1V 18.6-63
-59-50.6V 18.3-62
-58-50.0V 17.9-61
-57-49.4V 17.5-59
-56-48.9V 17.1-58
-55-48.3V 16.6-56
-54-47.8V 16.2-55
-53-47.2V 15.8-53
-52-46.7V 15.3-52
-51-46.1V 14.8-50
-50-45.6V 14.4-49
-49-45.0V 13.8-47
-48-44.4V 13.3-45
-47-43.9V 12.8-43
-46-43.3V 12.3-42
-45-42.8V 11.7-40
-44-42.2V 11.2-38
-43-41.7V 10.6-36
-42-41.1V 10.0-34
-41-40.6V 9.4-32
-40-40.0V 8.8-30
-39-39.4V 8.1-28
-38-38.9V 7.5-25
-37-38.3V 6.8-23
-36-37.8V 6.1-21
-35-37.2V 5.4-18
-34-36.7V 4.7-16
-33-36.1V 4.0-13
-32-35.6V 3.2-11
-31-35.0V 2.4-8
-30-34.4V 1.6-6
-29-33.9V 0.9-3
-28-33.3V 0.0-0
-27-32.80.43
-26-32.20.86
-25-31.71.39
-24-31.11.712
-23-30.62.115
-22-30.02.618
-21-29.43.121
-20-28.93.625
-19-28.34.128
-18-27.84.632
-17-27.25.135
-16-26.75.639
-15-26.16.242
-14-25.66.746
-13-25.07.350
-12-24.47.854
-11-23.98.458
-10-23.39.062
-9-22.89.666
-8-22.210.371
-7-21.710.975
-6-21.111.579
-5-20.612.284
-4-20.012.989
-3-19.413.693
-2-18.914.398
-1-18.315.0103
0-17.815.7108
1-17.216.4113
2-16.717.2119
3-16.118.0124
4-15.618.8129
5-15.019.6135
6-14.420.4140
7-13.921.2146
8-13.322.0152
9-12.822.9158
10-12.223.8164
11-11.724.7170
12-11.125.6176
13-10.626.5183
14-10.027.5189
15-9.428.4196
16-8.929.4203
17-8.330.4210
18-7.831.4217
19-7.232.4224
20-6.733.5231
21-6.134.5238
22-5.635.6246
23-5.036.7253
24-4.437.9261
25-3.939.0269
26-3.340.2277
27-2.841.4285
28-2.242.5293
29-1.743.8302
30-1.145.0310
31-0.646.3319
320.047.6328
330.648.9337
341.150.2346
351.751.5355
362.252.9365
372.854.3374
383.355.7384
393.957.1394
404.458.6404
415.060.1414
425.661.6425
436.163.1435
446.764.7446
457.266.2457
467.867.8468
478.369.5479
488.971.1490
499.472.8502
5010.074.5513
5110.676.2525
5211.177.9537
5311.779.7550
5412.281.5562
5512.883.3575
5613.385.2587
5713.987.1600
5814.489.0613
5915.090.9627
6015.692.9640
6116.194.9654
6216.796.9668
6317.298.9682
6417.8101696
6518.3103711
6618.9105726
6719.4107741
6820.0110756
6920.6112771
7021.1114787
7121.7116802
7222.2119818
7322.8121834
7423.3123851
7523.9126867
7624.4128884
7725.0131901
7825.6133919
7926.1136936
8026.7138954
8127.2141972
8227.8144990
8328.31461008
8428.91491027
8529.41521046
8630.01551065
8730.61571085
8831.11601104
8931.71631124
9032.21661144
9132.81691165
9233.31721185
9333.91751206
9434.41781227
9535.01811249
9635.61841270
9736.11871292
9836.71911314
9937.21941337
10037.81971360
10138.32011383
10238.92041406
10339.42071429
10440.02111453
10540.62141477
10641.12181502
10741.72211526
10842.22251551
10942.82291576
11043.32321602
11143.92361628
11244.42401654
11345.02441680
11445.62481707
11546.12521734
11646.72551761
11747.22591789
11847.82641817
11948.32681845
12048.92721874
12149.42761902
12250.02801932
12350.62841961
12451.12891991
12551.72932021
12652.22982052
12752.83022082
12853.33072113
12953.93112145
13054.43162177

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-717 pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-60-51.1V 18.65.5-63380.38
-55-48.3V 16.66.5-56450.45
-50-45.6V 14.47.6-49530.53
-45-42.8V 11.78.9-40620.62
-40-40.0V 8.810.4-30720.72
-35-37.2V 5.412.0-18830.83
-30-34.4V 1.613.9-6960.96
-25-31.71.316.091101.10
-20-28.93.618.3251261.26
-15-26.16.220.9421441.44
-10-23.39.023.7621641.64
-5-20.612.226.9841851.85
0-17.815.730.41082102.10
5-15.019.634.21352362.36
10-12.223.838.51642652.65
15-9.428.443.11962972.97
20-6.733.548.22313323.32
25-3.939.053.72693703.70
30-1.145.059.73104124.12
351.751.566.23554574.57
404.458.673.34045055.05
457.266.280.94575585.58
5010.074.589.25136156.15
5512.883.398.05756766.76
6015.692.9107.66407427.42
6518.3103117.87118128.12
7021.1114128.87878888.88
7523.9126140.58679699.69
8026.7138153.0954105510.55
8529.4152166.41046114711.47
9032.2166180.71144124612.46
9535.0181195.81249135013.50
10037.8197211.91360146114.61
10540.6214229.01477157915.79
11043.3232247.01602170317.03
11546.1252266.21734183518.35
12048.9272286.41874197519.75
12551.7293307.82021212221.22
13054.4316330.42177227822.78

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.