Refrigerant · CFC

R-12 pressure-temperature chart and data

Dichlorodifluoromethane. Safety class A1, GWP 10,900. Old fridges, freezers and car A/C. Banned; recovery only. Replaced by R-134a, R-401A, R-409A.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-12 data sheet

NameDichlorodifluoromethane
TypeCFC
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)1
Global warming (GWP, 100 yr)10,900
Boils at 1 atm-21.6 °F (-29.8 °C)
Critical temperature233.5 °F (111.9 °C)
Temperature glidenone / very small
Low side at 5 °F evaporating11.7 psig (81 kPa)
High side at 86 °F condensing93.2 psig (643 kPa)
Old cylinder colourWhite
OilMineral / AB
Used forOld fridges, freezers and car A/C. Banned; recovery only. Replaced by R-134a, R-401A, R-409A.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-12 pressure / temperature chart

°F°CpsigkPa
-60-51.1V 19.0-64
-59-50.6V 18.7-63
-58-50.0V 18.4-62
-57-49.4V 18.0-61
-56-48.9V 17.7-60
-55-48.3V 17.3-59
-54-47.8V 17.0-58
-53-47.2V 16.6-56
-52-46.7V 16.2-55
-51-46.1V 15.8-54
-50-45.6V 15.5-52
-49-45.0V 15.0-51
-48-44.4V 14.6-50
-47-43.9V 14.2-48
-46-43.3V 13.8-47
-45-42.8V 13.3-45
-44-42.2V 12.9-44
-43-41.7V 12.4-42
-42-41.1V 12.0-41
-41-40.6V 11.5-39
-40-40.0V 11.0-37
-39-39.4V 10.5-36
-38-38.9V 10.0-34
-37-38.3V 9.5-32
-36-37.8V 8.9-30
-35-37.2V 8.4-28
-34-36.7V 7.8-27
-33-36.1V 7.3-25
-32-35.6V 6.7-23
-31-35.0V 6.1-21
-30-34.4V 5.5-19
-29-33.9V 4.9-17
-28-33.3V 4.3-15
-27-32.8V 3.7-12
-26-32.2V 3.0-10
-25-31.7V 2.4-8
-24-31.1V 1.7-6
-23-30.6V 1.0-3
-22-30.0V 0.3-1
-21-29.40.21
-20-28.90.64
-19-28.30.96
-18-27.81.39
-17-27.21.611
-16-26.72.014
-15-26.12.417
-14-25.62.819
-13-25.03.222
-12-24.43.625
-11-23.94.028
-10-23.34.531
-9-22.84.934
-8-22.25.337
-7-21.75.840
-6-21.16.243
-5-20.66.746
-4-20.07.249
-3-19.47.653
-2-18.98.156
-1-18.38.659
0-17.89.163
1-17.29.666
2-16.710.170
3-16.110.774
4-15.611.277
5-15.011.881
6-14.412.385
7-13.912.989
8-13.313.493
9-12.814.097
10-12.214.6101
11-11.715.2105
12-11.115.8109
13-10.616.4113
14-10.017.0117
15-9.417.7122
16-8.918.3126
17-8.319.0131
18-7.819.6135
19-7.220.3140
20-6.721.0145
21-6.121.7149
22-5.622.4154
23-5.023.1159
24-4.423.8164
25-3.924.6169
26-3.325.3174
27-2.826.1180
28-2.226.8185
29-1.727.6190
30-1.128.4196
31-0.629.2201
320.030.0207
330.630.8212
341.131.6218
351.732.5224
362.233.4230
372.834.2236
383.335.1242
393.936.0248
404.436.9254
415.037.8261
425.638.7267
436.139.7274
446.740.6280
457.241.6287
467.842.6294
478.343.6300
488.944.6307
499.445.6314
5010.046.6321
5110.647.6329
5211.148.7336
5311.749.8343
5412.250.9351
5512.852.0358
5613.353.1366
5713.954.2374
5814.455.3381
5915.056.5389
6015.657.6397
6116.158.8405
6216.760.0414
6317.261.2422
6417.862.4430
6518.363.7439
6618.964.9448
6719.466.2456
6820.067.5465
6920.668.8474
7021.170.1483
7121.771.4492
7222.272.7501
7322.874.1511
7423.375.5520
7523.976.8530
7624.478.2539
7725.079.7549
7825.681.1559
7926.182.5569
8026.784.0579
8127.285.5590
8227.887.0600
8328.388.5610
8428.990.0621
8529.491.6632
8630.093.2642
8730.694.7653
8831.196.3664
8931.798.0675
9032.299.6687
9132.8101698
9233.3103710
9333.9105721
9434.4106733
9535.0108745
9635.6110757
9736.1112769
9836.7113781
9937.2115794
10037.8117806
10138.3119819
10238.9121832
10339.4122844
10440.0124858
10540.6126871
10641.1128884
10741.7130897
10842.2132911
10942.8134925
11043.3136938
11143.9138952
11244.4140967
11345.0142981
11445.6144995
11546.11461010
11646.71491024
11747.21511039
11847.81531054
11948.31551069
12048.91571084
12149.41601100
12250.01621115
12350.61641131
12451.11661147
12551.71691163
12652.21711179
12752.81731195
12853.31761212
12953.91781228
13054.41811245

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-12 pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-60-51.1V 19.05.4-64370.37
-55-48.3V 17.36.2-59430.43
-50-45.6V 15.57.1-52490.49
-45-42.8V 13.38.1-45560.56
-40-40.0V 11.09.3-37640.64
-35-37.2V 8.410.6-28730.73
-30-34.4V 5.512.0-19830.83
-25-31.7V 2.413.5-8930.93
-20-28.90.615.241051.05
-15-26.12.417.1171181.18
-10-23.34.519.2311321.32
-5-20.66.721.4461471.47
0-17.89.123.8631641.64
5-15.011.826.4811821.82
10-12.214.629.31012022.02
15-9.417.732.41222232.23
20-6.721.035.71452462.46
25-3.924.639.21692712.71
30-1.128.443.11962972.97
351.732.547.22243253.25
404.436.951.62543563.56
457.241.656.32873883.88
5010.046.661.33214234.23
5512.852.066.63584604.60
6015.657.672.33974994.99
6518.363.778.44395405.40
7021.170.184.84835845.84
7523.976.891.55306316.31
8026.784.098.75796816.81
8529.491.6106.36327337.33
9032.299.6114.36877887.88
9535.0108122.77458468.46
10037.8117131.68069079.07
10540.6126141.08719729.72
11043.3136150.8938104010.40
11546.1146161.11010111111.11
12048.9157172.01084118611.86
12551.7169183.31163126412.64
13054.4181195.21245134613.46

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.