Refrigerant · HFO/HFC blend

R-454B pressure-temperature chart and data

R-32 / R-1234yf. Safety class A2L, GWP 466. New A/C and heat pumps replacing R-410A (low GWP). Mildly flammable.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-454B data sheet

Made ofR-32 68.9 / R-1234yf 31.1 (mass %)
TypeHFO/HFC blend
Safety classA2L — lower toxicity, mildly flammable (burns slowly)
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)466
Boils at 1 atm-59.3 °F (-50.7 °C)
Critical temperature172.9 °F (78.3 °C)
Temperature glideabout 2.6 °F
Low side at 5 °F evaporating49.1 psig (339 kPa)
High side at 86 °F condensing247 psig (1704 kPa)
Old cylinder colournone assigned
OilPOE
Used forNew A/C and heat pumps replacing R-410A (low GWP). Mildly flammable.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-454B pressure / temperature chart

°F°CDew psig (vapour)Bubble psig (liquid)Dew kPaBubble kPa
-60-51.1V 2.3V 0.5-8-2
-59-50.6V 1.50.1-51
-58-50.0V 0.70.6-24
-57-49.40.11.007
-56-48.90.51.4310
-55-48.30.91.9613
-54-47.81.32.3916
-53-47.21.82.81219
-52-46.72.23.31522
-51-46.12.73.81926
-50-45.63.24.32229
-49-45.03.64.82533
-48-44.44.15.32936
-47-43.94.65.83240
-46-43.35.26.33644
-45-42.85.76.93948
-44-42.26.27.54351
-43-41.76.88.04755
-42-41.17.38.65059
-41-40.67.99.25464
-40-40.08.59.85868
-39-39.49.110.46272
-38-38.99.711.16776
-37-38.310.311.77181
-36-37.810.912.47585
-35-37.211.513.07990
-34-36.712.213.78495
-33-36.112.814.48999
-32-35.613.515.193104
-31-35.014.215.998109
-30-34.414.916.6103114
-29-33.915.617.3108120
-28-33.316.418.1113125
-27-32.817.118.9118130
-26-32.217.919.7123136
-25-31.718.620.5128141
-24-31.119.421.3134147
-23-30.620.222.1139153
-22-30.021.023.0145159
-21-29.421.823.9151165
-20-28.922.724.8156171
-19-28.323.525.6162177
-18-27.824.426.6168183
-17-27.225.327.5174190
-16-26.726.228.4181196
-15-26.127.129.4187203
-14-25.628.130.4193209
-13-25.029.031.4200216
-12-24.430.032.4207223
-11-23.931.033.4213230
-10-23.332.034.5220238
-9-22.833.035.5227245
-8-22.234.036.6234252
-7-21.735.137.7242260
-6-21.136.138.8249268
-5-20.637.240.0257276
-4-20.038.341.1264283
-3-19.439.442.3272292
-2-18.940.643.5280300
-1-18.341.744.7288308
0-17.842.945.9296317
1-17.244.147.2304325
2-16.745.348.4312334
3-16.146.549.7321343
4-15.647.851.0330352
5-15.049.152.4338361
6-14.450.453.7347370
7-13.951.755.1356380
8-13.353.056.5365389
9-12.854.457.9375399
10-12.255.759.3384409
11-11.757.160.8394419
12-11.158.562.2404429
13-10.660.063.7413439
14-10.061.465.3424450
15-9.462.966.8434461
16-8.964.468.4444471
17-8.365.969.9455482
18-7.867.571.5465493
19-7.269.073.2476505
20-6.770.674.8487516
21-6.172.276.5498528
22-5.673.978.2509539
23-5.075.580.0521551
24-4.477.281.7532563
25-3.978.983.5544576
26-3.380.785.3556588
27-2.882.487.1568601
28-2.284.289.0580613
29-1.786.090.8593626
30-1.187.892.7605639
31-0.689.794.7618653
320.091.596.6631666
330.693.498.6644680
341.195.4101657694
351.797.3103671708
362.299.3105685722
372.8101107698736
383.3103109713751
393.9105111727765
404.4107113741780
415.0110115756796
425.6112118770811
436.1114120785826
446.7116122801842
457.2118124816858
467.8121127831874
478.3123129847891
488.9125132863907
499.4128134879924
5010.0130136896941
5110.6132139912958
5211.1135141929975
5311.7137144946993
5412.21401479631011
5512.81421499811029
5613.31451529981047
5713.914715510161065
5814.415015710341084
5915.015316010521103
6015.615516310711122
6116.115816610891141
6216.716116811081161
6317.216417111271181
6417.816617411471201
6518.316917711661221
6618.917218011861242
6719.417518312061262
6820.017818612271283
6920.618118912471304
7021.118419212681326
7121.718719512891348
7222.219019913101370
7322.819320213321392
7423.319620513541414
7523.920020813761437
7624.420321213981460
7725.020621514201483
7825.620921914431507
7926.121322214661530
8026.721622514891554
8127.221922915131578
8227.822323215371603
8328.322623615611628
8428.923024015851653
8529.423324316101678
8630.023724716351703
8730.624125116601729
8831.124425516851755
8931.724825817111782
9032.225226217371809
9132.825626617631835
9233.326027017901863
9333.926327418171890
9434.426727818441918
9535.027128218711946
9635.627528618991975
9736.127929119272003
9836.728429519552032
9937.228829919842061
10037.829230320132091
10138.329630820422121
10238.930031220712151
10339.430531621012182
10440.030932121312212
10540.631432521622243
10641.131833021932275
10741.732333522242307
10842.232733922552339
10942.833234422872371
11043.333634923192404
11143.934135323512437
11244.434635823842470
11345.035136324172503
11445.635536824502537
11546.136037324842572
11646.736537825182606
11747.237038325532641
11847.837538825882677
11948.338039326232712
12048.938639926582748
12149.439140426942785
12250.039640927302821
12350.640141527672858
12451.140742028042896
12551.741242528412934
12652.241843128792972
12752.842343729173010
12853.342944229553049
12953.943444829943088
13054.444045430343128

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-454B pressure in psig, psia, kPa and bar

°F°CDew psigpsiakPa gaugekPa absolutebar absoluteBubble psig
-60-51.1V 2.313.6-8940.94V 0.5
-55-48.30.915.661081.081.9
-50-45.63.217.9221231.234.3
-45-42.85.720.4391401.406.9
-40-40.08.523.2581601.609.8
-35-37.211.526.2791811.8113.0
-30-34.414.929.61032042.0416.6
-25-31.718.633.31282302.3020.5
-20-28.922.737.41562582.5824.8
-15-26.127.141.81872882.8829.4
-10-23.332.046.72203223.2234.5
-5-20.637.251.92573583.5840.0
0-17.842.957.62963973.9745.9
5-15.049.163.83384404.4052.4
10-12.255.770.43844864.8659.3
15-9.462.977.64345355.3566.8
20-6.770.685.34875885.8874.8
25-3.978.993.65446456.4583.5
30-1.187.8102.56057077.0792.7
351.797.3112.06717727.72103
404.4107122.27418428.42113
457.2118133.08169179.17124
5010.0130144.68969979.97136
5512.8142156.9981108210.82149
6015.6155170.01071117211.72163
6518.3169183.91166126812.68177
7021.1184198.61268136913.69192
7523.9200214.21376147714.77208
8026.7216230.71489159115.91225
8529.4233248.21610171117.11243
9032.2252266.61737183818.38262
9535.0271286.11871197219.72282
10037.8292306.62013211421.14303
10540.6314328.22162226322.63325
11043.3336351.02319242024.20349
11546.1360375.02484258625.86373
12048.9386400.22658275927.59399
12551.7412426.82841294229.42425
13054.4440454.73034313531.35454

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.