Refrigerant · HFO/HFC blend

R-513A pressure-temperature chart and data

R-1234yf / R-134a. Safety class A1, GWP 631. Lower-GWP replacement for R-134a in chillers and refrigeration.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-513A data sheet

Made ofR-1234yf 56 / R-134a 44 (mass %)
TypeHFO/HFC blend
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)631
Boils at 1 atm-21 °F (-29.4 °C)
Critical temperature203.7 °F (95.4 °C)
Temperature glidenone / very small
Low side at 5 °F evaporating12.2 psig (84 kPa)
High side at 86 °F condensing104 psig (716 kPa)
Old cylinder colourSky blue
OilPOE
Used forLower-GWP replacement for R-134a in chillers and refrigeration.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-513A pressure / temperature chart

°F°CpsigkPa
-60-51.1V 19.9-67
-59-50.6V 19.6-66
-58-50.0V 19.2-65
-57-49.4V 18.9-64
-56-48.9V 18.6-63
-55-48.3V 18.2-62
-54-47.8V 17.9-60
-53-47.2V 17.5-59
-52-46.7V 17.1-58
-51-46.1V 16.7-57
-50-45.6V 16.3-55
-49-45.0V 15.9-54
-48-44.4V 15.5-53
-47-43.9V 15.1-51
-46-43.3V 14.7-50
-45-42.8V 14.2-48
-44-42.2V 13.7-47
-43-41.7V 13.3-45
-42-41.1V 12.8-43
-41-40.6V 12.3-42
-40-40.0V 11.8-40
-39-39.4V 11.3-38
-38-38.9V 10.8-37
-37-38.3V 10.3-35
-36-37.8V 9.7-33
-35-37.2V 9.2-31
-34-36.7V 8.6-29
-33-36.1V 8.0-27
-32-35.6V 7.5-25
-31-35.0V 6.8-23
-30-34.4V 6.2-21
-29-33.9V 5.6-19
-28-33.3V 4.9-17
-27-32.8V 4.3-14
-26-32.2V 3.6-12
-25-31.7V 2.9-10
-24-31.1V 2.2-8
-23-30.6V 1.5-5
-22-30.0V 0.8-3
-21-29.4V 0.1-0
-20-28.90.32
-19-28.30.75
-18-27.81.18
-17-27.21.510
-16-26.71.913
-15-26.12.316
-14-25.62.719
-13-25.03.122
-12-24.43.625
-11-23.94.028
-10-23.34.531
-9-22.84.934
-8-22.25.437
-7-21.75.940
-6-21.16.344
-5-20.66.847
-4-20.07.351
-3-19.47.854
-2-18.98.458
-1-18.38.961
0-17.89.465
1-17.210.069
2-16.710.573
3-16.111.176
4-15.611.780
5-15.012.384
6-14.412.889
7-13.913.493
8-13.314.197
9-12.814.7101
10-12.215.3106
11-11.716.0110
12-11.116.6115
13-10.617.3119
14-10.018.0124
15-9.418.7129
16-8.919.4134
17-8.320.1138
18-7.820.8143
19-7.221.5149
20-6.722.3154
21-6.123.0159
22-5.623.8164
23-5.024.6170
24-4.425.4175
25-3.926.2181
26-3.327.0186
27-2.827.8192
28-2.228.7198
29-1.729.6204
30-1.130.4210
31-0.631.3216
320.032.2222
330.633.1228
341.134.0235
351.735.0241
362.235.9248
372.836.9254
383.337.9261
393.938.8268
404.439.9275
415.040.9282
425.641.9289
436.143.0296
446.744.0304
457.245.1311
467.846.2318
478.347.3326
488.948.4334
499.449.6342
5010.050.7350
5110.651.9358
5211.153.1366
5311.754.3374
5412.255.5383
5512.856.7391
5613.358.0400
5713.959.3409
5814.460.5417
5915.061.8426
6015.663.1435
6116.164.5445
6216.765.8454
6317.267.2463
6417.868.6473
6518.370.0483
6618.971.4492
6719.472.8502
6820.074.3512
6920.675.8522
7021.177.3533
7121.778.8543
7222.280.3554
7322.881.9564
7423.383.4575
7523.985.0586
7624.486.6597
7725.088.3608
7825.689.9620
7926.191.6631
8026.793.3643
8127.295.0655
8227.896.7667
8328.398.4679
8428.9100691
8529.4102703
8630.0104716
8730.6106728
8831.1107741
8931.7109754
9032.2111767
9132.8113780
9233.3115793
9333.9117807
9434.4119820
9535.0121834
9635.6123848
9736.1125862
9836.7127877
9937.2129891
10037.8131906
10138.3133920
10238.9136935
10339.4138950
10440.0140965
10540.6142981
10641.1145996
10741.71471012
10842.21491028
10942.81511044
11043.31541060
11143.91561076
11244.41591093
11345.01611110
11445.61631127
11546.11661144
11646.71681161
11747.21711179
11847.81731196
11948.31761214
12048.91791232
12149.41811250
12250.01841268
12350.61871287
12451.11891306
12551.71921325
12652.21951344
12752.81981363
12853.32011382
12953.92031402
13054.42061422

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-513A pressure in psig, psia, kPa and bar

°F°CpsigpsiakPa gaugekPa absolutebar absolute
-60-51.1V 19.94.9-67340.34
-55-48.3V 18.25.8-62400.40
-50-45.6V 16.36.7-55460.46
-45-42.8V 14.27.7-48530.53
-40-40.0V 11.88.9-40610.61
-35-37.2V 9.210.2-31700.70
-30-34.4V 6.211.6-21800.80
-25-31.7V 2.913.3-10910.91
-20-28.90.315.021041.04
-15-26.12.317.0161171.17
-10-23.34.519.2311321.32
-5-20.66.821.5471481.48
0-17.89.424.1651661.66
5-15.012.326.9841861.86
10-12.215.330.01062072.07
15-9.418.733.41292302.30
20-6.722.337.01542552.55
25-3.926.240.91812822.82
30-1.130.445.12103113.11
351.735.049.72413423.42
404.439.954.62753763.76
457.245.159.83114124.12
5010.050.765.43504514.51
5512.856.771.43914924.92
6015.663.177.84355375.37
6518.370.084.74835845.84
7021.177.392.05336346.34
7523.985.099.75866886.88
8026.793.3107.96437447.44
8529.4102116.77038048.04
9032.2111125.97678688.68
9535.0121135.78349369.36
10037.8131146.0906100710.07
10540.6142156.9981108210.82
11043.3154168.51060116111.61
11546.1166180.61144124512.45
12048.9179193.41232133313.33
12551.7192206.81325142614.26
13054.4206220.91422152315.23

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.