R-422D pressure-temperature chart and data

R-125 / R-134a / R-600a. Safety class A1, GWP 2,729. Retrofit for R-22 in chillers and refrigeration.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-422D data sheet

Made ofR-125 65.1 / R-134a 31.5 / R-600a 3.4 (mass %)
TypeHFC blend
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)0
Global warming (GWP, 100 yr)2,729
Boils at 1 atm-46.1 °F (-43.4 °C)
Critical temperature172.6 °F (78.1 °C)
Temperature glideabout 7.2 °F
Low side at 5 °F evaporating25.9 psig (179 kPa)
High side at 86 °F condensing173 psig (1191 kPa)
Old cylinder colourGreen-yellow
OilPOE
Used forRetrofit for R-22 in chillers and refrigeration.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-422D pressure / temperature chart

°F°CDew psig (vapour)Bubble psig (liquid)Dew kPaBubble kPa
-60-51.1V 14.6V 9.4-49-32
-59-50.6V 14.1V 8.9-48-30
-58-50.0V 13.6V 8.2-46-28
-57-49.4V 13.1V 7.6-44-26
-56-48.9V 12.5V 7.0-42-24
-55-48.3V 12.0V 6.4-41-22
-54-47.8V 11.5V 5.7-39-19
-53-47.2V 10.9V 5.0-37-17
-52-46.7V 10.3V 4.3-35-15
-51-46.1V 9.8V 3.6-33-12
-50-45.6V 9.1V 2.9-31-10
-49-45.0V 8.5V 2.2-29-7
-48-44.4V 7.9V 1.4-27-5
-47-43.9V 7.3V 0.7-25-2
-46-43.3V 6.60.0-220
-45-42.8V 5.90.4-203
-44-42.2V 5.20.8-186
-43-41.7V 4.51.2-159
-42-41.1V 3.81.6-1311
-41-40.6V 3.12.1-1014
-40-40.0V 2.32.5-817
-39-39.4V 1.63.0-520
-38-38.9V 0.83.4-323
-37-38.30.03.9027
-36-37.80.44.3330
-35-37.20.84.8633
-34-36.71.35.3936
-33-36.11.75.81240
-32-35.62.16.31543
-31-35.02.66.81847
-30-34.43.07.32151
-29-33.93.57.92454
-28-33.34.08.42758
-27-32.84.49.03162
-26-32.24.99.53466
-25-31.75.410.13870
-24-31.16.010.74174
-23-30.66.511.34578
-22-30.07.011.94882
-21-29.47.612.55286
-20-28.98.113.15691
-19-28.38.713.86095
-18-27.89.314.46499
-17-27.29.815.168104
-16-26.710.415.872109
-15-26.111.116.476113
-14-25.611.717.181118
-13-25.012.317.985123
-12-24.413.018.689128
-11-23.913.619.394133
-10-23.314.320.199138
-9-22.815.020.8103144
-8-22.215.721.6108149
-7-21.716.422.4113154
-6-21.117.123.2118160
-5-20.617.824.0123165
-4-20.018.624.8128171
-3-19.419.325.6133177
-2-18.920.126.5139183
-1-18.320.927.4144189
0-17.821.728.2150195
1-17.222.529.1155201
2-16.723.330.0161207
3-16.124.231.0167213
4-15.625.031.9173220
5-15.025.932.9179226
6-14.426.833.8185233
7-13.927.734.8191240
8-13.328.635.8197247
9-12.829.536.8203254
10-12.230.437.8210261
11-11.731.438.9216268
12-11.132.439.9223275
13-10.633.441.0230283
14-10.034.442.1237290
15-9.435.443.2244298
16-8.936.444.3251305
17-8.337.545.4258313
18-7.838.546.6266321
19-7.239.647.8273329
20-6.740.749.0281337
21-6.141.850.1288346
22-5.643.051.4296354
23-5.044.152.6304363
24-4.445.353.9312371
25-3.946.555.1321380
26-3.347.756.4329389
27-2.848.957.7337398
28-2.250.259.1346407
29-1.751.460.4354417
30-1.152.761.8363426
31-0.654.063.1372435
320.055.364.5381445
330.656.666.0390455
341.158.067.4400465
351.759.468.9409475
362.260.870.3419485
372.862.271.8429495
383.363.673.4438506
393.965.074.9448516
404.466.576.5459527
415.068.078.0469538
425.669.579.6479549
436.171.081.2490560
446.772.682.9501571
457.274.284.5511583
467.875.886.2522594
478.377.487.9534606
488.979.089.6545618
499.480.791.4556630
5010.082.493.2568642
5110.684.194.9580655
5211.185.896.8592667
5311.787.598.6604680
5412.289.3100616693
5512.891.1102628705
5613.392.9104641719
5713.994.8106653732
5814.496.6108666745
5915.098.5110679759
6015.6100112692772
6116.1102114706786
6216.7104116719800
6317.2106118733815
6417.8108120747829
6518.3110122761844
6618.9112125775858
6719.4114127789873
6820.0117129804888
6920.6119131819904
7021.1121133834919
7121.7123136849935
7222.2125138864951
7322.8128140879966
7423.3130143895983
7523.9132145911999
7624.41341479271015
7725.01371509431032
7825.61391529591049
7926.11421559761066
8026.71441579931083
8127.214616010101101
8227.814916210271118
8328.315116510441136
8428.915416710621154
8529.415717010791172
8630.015917310971191
8730.616217511151209
8831.116417811341228
8931.716718111521247
9032.217018411711266
9132.817318611901286
9233.317518912091305
9333.917819212291325
9434.418119512481345
9535.018419812681365
9635.618720112881386
9736.119020413091407
9836.719320713291427
9937.219621013501448
10037.819921313711470
10138.320221613921491
10238.920521914131513
10339.420822314351535
10440.021122614571557
10540.621522914791580
10641.121823215011602
10741.722123615241625
10842.222423915471648
10942.822824215701671
11043.323124615931695
11143.923424916171719
11244.423825316401743
11345.024125616641767
11445.624526016891791
11546.124826317131816
11646.725226717381841
11747.225627117631866
11847.825927417881892
11948.326327818141918
12048.926728218401943
12149.427128618661970
12250.027429018921996
12350.627829319192023
12451.128229719462050
12551.728630119732077
12652.229030520012104
12752.829430920292132
12853.329831320572160
12953.930231720852188
13054.430732221142217

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-422D pressure in psig, psia, kPa and bar

°F°CDew psigpsiakPa gaugekPa absolutebar absoluteBubble psig
-60-51.1V 14.67.5-49520.52V 9.4
-55-48.3V 12.08.8-41610.61V 6.4
-50-45.6V 9.110.2-31700.70V 2.9
-45-42.8V 5.911.8-20810.810.4
-40-40.0V 2.313.6-8930.932.5
-35-37.20.815.561071.074.8
-30-34.43.017.7211221.227.3
-25-31.75.420.1381391.3910.1
-20-28.98.122.8561571.5713.1
-15-26.111.125.8761781.7816.4
-10-23.314.329.0992002.0020.1
-5-20.617.832.51232242.2424.0
0-17.821.736.41502512.5128.2
5-15.025.940.61792802.8032.9
10-12.230.445.12103113.1137.8
15-9.435.450.12443453.4543.2
20-6.740.755.42813823.8249.0
25-3.946.561.23214224.2255.1
30-1.152.767.43634654.6561.8
351.759.474.14095115.1168.9
404.466.581.24595605.6076.5
457.274.288.95116136.1384.5
5010.082.497.15686696.6993.2
5512.891.1105.86287297.29102
6015.6100115.16927947.94112
6518.3110125.07618628.62122
7021.1121135.68349359.35133
7523.9132146.8911101210.12145
8026.7144158.7993109410.94157
8529.4157171.21079118111.81170
9032.2170184.61171127212.72184
9535.0184198.61268137013.70198
10037.8199213.51371147214.72213
10540.6215229.21479158015.80229
11043.3231245.71593169416.94246
11546.1248263.21713181518.15263
12048.9267281.61840194119.41282
12551.7286300.91973207520.75301
13054.4307321.22114221522.15322

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-409A R-410A R-417A R-422A R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.