Refrigerant · HCFC blend

R-409A pressure-temperature chart and data

R-22 / R-124 / R-142b. Safety class A1, GWP 1,585. Retrofit for R-12.

Jump to: Data sheet · P/T chart · Pressure in every unit · Other refrigerants

R-409A data sheet

Made ofR-22 60 / R-124 25 / R-142b 15 (mass %)
TypeHCFC blend
Safety classA1 — lower toxicity, does not burn
Ozone depletion (ODP)0.048
Global warming (GWP, 100 yr)1,585
Boils at 1 atm-29.7 °F (-34.3 °C)
Critical temperature230.7 °F (110.4 °C)
Temperature glideabout 14.7 °F
Low side at 5 °F evaporating8.7 psig (60 kPa)
High side at 86 °F condensing118 psig (812 kPa)
Old cylinder colourMedium brown
OilAB / POE
Used forRetrofit for R-12.

Pressures are saturation values from reference equations of state. Real pressures change with load and airflow. GWP is the IPCC AR4 100-year value (blends calculated from their ingredients). Cylinder colours were an old AHRI code; since 2020 new cylinders are all one colour with the name on the label, so always read the label, never go by colour.

R-409A pressure / temperature chart

°F°CDew psig (vapour)Bubble psig (liquid)Dew kPaBubble kPa
-60-51.1V 21.8V 16.7-74-57
-59-50.6V 21.5V 16.3-73-55
-58-50.0V 21.2V 15.9-72-54
-57-49.4V 20.9V 15.5-71-52
-56-48.9V 20.6V 15.1-70-51
-55-48.3V 20.3V 14.6-69-50
-54-47.8V 20.0V 14.2-68-48
-53-47.2V 19.7V 13.7-67-47
-52-46.7V 19.4V 13.3-66-45
-51-46.1V 19.1V 12.8-65-43
-50-45.6V 18.7V 12.3-63-42
-49-45.0V 18.4V 11.8-62-40
-48-44.4V 18.0V 11.3-61-38
-47-43.9V 17.7V 10.8-60-37
-46-43.3V 17.3V 10.3-59-35
-45-42.8V 16.9V 9.8-57-33
-44-42.2V 16.5V 9.2-56-31
-43-41.7V 16.1V 8.7-55-29
-42-41.1V 15.7V 8.1-53-27
-41-40.6V 15.3V 7.5-52-25
-40-40.0V 14.8V 6.9-50-23
-39-39.4V 14.4V 6.3-49-21
-38-38.9V 14.0V 5.7-47-19
-37-38.3V 13.5V 5.0-46-17
-36-37.8V 13.0V 4.4-44-15
-35-37.2V 12.5V 3.7-42-13
-34-36.7V 12.1V 3.0-41-10
-33-36.1V 11.5V 2.3-39-8
-32-35.6V 11.0V 1.6-37-6
-31-35.0V 10.5V 0.9-36-3
-30-34.4V 10.0V 0.2-34-1
-29-33.9V 9.40.3-322
-28-33.3V 8.80.6-304
-27-32.8V 8.31.0-287
-26-32.2V 7.71.4-2610
-25-31.7V 7.11.8-2412
-24-31.1V 6.52.2-2215
-23-30.6V 5.82.6-2018
-22-30.0V 5.23.0-1821
-21-29.4V 4.53.5-1524
-20-28.9V 3.93.9-1327
-19-28.3V 3.24.3-1130
-18-27.8V 2.54.8-833
-17-27.2V 1.85.3-636
-16-26.7V 1.15.7-439
-15-26.1V 0.36.2-143
-14-25.60.26.7146
-13-25.00.67.2449
-12-24.41.07.7753
-11-23.91.48.2956
-10-23.31.88.71260
-9-22.82.29.21564
-8-22.22.69.81867
-7-21.73.010.32171
-6-21.13.410.92475
-5-20.63.911.42779
-4-20.04.312.03083
-3-19.44.812.63387
-2-18.95.213.23691
-1-18.35.713.83995
0-17.86.214.44399
1-17.26.715.046104
2-16.77.215.750108
3-16.17.716.353112
4-15.68.217.057117
5-15.08.717.660122
6-14.49.318.364126
7-13.99.819.068131
8-13.310.419.772136
9-12.810.920.475141
10-12.211.521.179146
11-11.712.121.983151
12-11.112.722.688156
13-10.613.323.492161
14-10.013.924.196166
15-9.414.624.9100172
16-8.915.225.7105177
17-8.315.826.5109183
18-7.816.527.3114188
19-7.217.228.1118194
20-6.717.929.0123200
21-6.118.529.8128206
22-5.619.330.7133212
23-5.020.031.6138218
24-4.420.732.5143224
25-3.921.433.4148230
26-3.322.234.3153236
27-2.822.935.2158243
28-2.223.736.1163249
29-1.724.537.1169256
30-1.125.338.1174262
31-0.626.139.1180269
320.026.940.0186276
330.627.841.1191283
341.128.642.1197290
351.729.543.1203297
362.230.444.2209305
372.831.245.2215312
383.332.146.3222319
393.933.047.4228327
404.434.048.5234335
415.034.949.6241342
425.635.950.8247350
436.136.852.0254358
446.737.853.1261366
457.238.854.3268374
467.839.855.5275383
478.340.956.7282391
488.941.958.0289400
499.443.059.2296408
5010.044.060.5304417
5110.645.161.8311426
5211.146.263.0319435
5311.747.364.4326444
5412.248.565.7334453
5512.849.667.0342462
5613.350.868.4350472
5713.952.069.8358481
5814.453.171.2366491
5915.054.472.6375500
6015.655.674.0383510
6116.156.875.5392520
6216.758.176.9401530
6317.259.478.4409541
6417.860.779.9418551
6518.362.081.4427561
6618.963.383.0437572
6719.464.784.5446583
6820.066.086.1455594
6920.667.487.7465605
7021.168.889.3474616
7121.770.290.9484627
7222.271.792.6494638
7322.873.194.2504650
7423.374.695.9514661
7523.976.197.6524673
7624.477.699.3535685
7725.079.1101545697
7825.680.7103556709
7926.182.2105567721
8026.783.8106578734
8127.285.4108589746
8227.887.0110600759
8328.388.7112611772
8428.990.3114623785
8529.492.0116634798
8630.093.7118646811
8730.695.5120658825
8831.197.2122670838
8931.799.0124682852
9032.2101126695866
9132.8103128707880
9233.3104130720894
9333.9106132732908
9434.4108134745923
9535.0110136758937
9635.6112138772952
9736.1114140785967
9836.7116142798982
9937.2118145812997
10037.81201478261012
10138.31221498401028
10238.91241518541044
10339.41261548681059
10440.01281568831075
10540.61301588971091
10641.11321619121108
10741.71341639271124
10842.21371659421141
10942.81391689571158
11043.31411709731175
11143.91431739881192
11244.414617510041209
11345.014817810201226
11445.615018010361244
11546.115318310521262
11646.715518610691280
11747.215718810861298
11847.816019111021316
11948.316219411191335
12048.916519611371353
12149.416719911541372
12250.017020211711391
12350.617220511891410
12451.117520712071430
12551.717821012251449
12652.218021312431469
12752.818321612621489
12853.318621912801509
12953.918822212991529
13054.419122513181550

V = vacuum in inches of mercury. Saturation pressure in psig at sea level, calculated from reference equations of state. The chart gives the boiling temperature at that pressure, not the pipe temperature. Air in the system adds pressure and throws it off.

R-409A pressure in psig, psia, kPa and bar

°F°CDew psigpsiakPa gaugekPa absolutebar absoluteBubble psig
-60-51.1V 21.84.0-74280.28V 16.7
-55-48.3V 20.34.7-69320.32V 14.6
-50-45.6V 18.75.5-63380.38V 12.3
-45-42.8V 16.96.4-57440.44V 9.8
-40-40.0V 14.87.4-50510.51V 6.9
-35-37.2V 12.58.5-42590.59V 3.7
-30-34.4V 10.09.8-34680.68V 0.2
-25-31.7V 7.111.2-24770.771.8
-20-28.9V 3.912.8-13880.883.9
-15-26.1V 0.314.5-11001.006.2
-10-23.31.816.5121131.138.7
-5-20.63.918.6271281.2811.4
0-17.86.220.9431441.4414.4
5-15.08.723.4601621.6217.6
10-12.211.526.2791811.8121.1
15-9.414.629.31002022.0224.9
20-6.717.932.51232242.2429.0
25-3.921.436.11482492.4933.4
30-1.125.340.01742762.7638.1
351.729.544.22033053.0543.1
404.434.048.72343363.3648.5
457.238.853.52683693.6954.3
5010.044.058.73044054.0560.5
5512.849.664.33424434.4367.0
6015.655.670.33834854.8574.0
6518.362.076.74275295.2981.4
7021.168.883.54745765.7689.3
7523.976.190.85246266.2697.6
8026.783.898.55786796.79106
8529.492.0106.76347367.36116
9032.2101115.46957967.96126
9535.0110124.77588608.60136
10037.8120134.58269279.27147
10540.6130144.88979999.99158
11043.3141155.8973107410.74170
11546.1153167.31052115411.54183
12048.9165179.51137123812.38196
12551.7178192.41225132613.26210
13054.4191205.91318142014.20225

V = vacuum in inches of mercury. Absolute pressure = gauge + 14.7 psi at sea level; use absolute pressure for gas-law work. For blends the dew column is the vapour (suction) side and the bubble column the liquid side.

Other refrigerants

R-11 R-12 R-22 R-23 R-32 R-123 R-125 R-134a R-143a R-152a R-170 R-245fa R-290 R-401A R-401B R-404A R-407A R-407C R-407F R-408A R-410A R-417A R-422A R-422D R-427A R-448A R-449A R-450A R-452A R-452B R-454A R-454B R-454C R-455A R-500 R-502 R-507A R-508B R-513A R-600 R-600a R-717 R-744 R-1233zd(E) R-1234yf R-1234ze(E) R-1270

P/T charts in your pocket

The HVACopedia app has every chart, calculator and table offline, with a refrigerant picker.

Open the app

Calculation aids and reference figures for licensed technicians. Always follow the manufacturer’s data plate and manual for the exact model, and local codes. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Pressures are typical saturation values and change with load and airflow.